Page 221

Motion axis attributes

Appendix B

Attribute

Axis Type

Data Type

Access

Description

Hard Overtravel Fault Action

AXIS_SERVO_DRIVE

SINT

GSV SSV

Home Configuration Bits

AXIS_GENERIC AXIS_SERVO AXIS_SERVO_DRIVE AXIS_VIRTUAL

DINT

GSV SSV

0 = (Reserved) 1 = Home Switch Normally Closed 2 = Marker Edge Negative Home Switch Normally Closed The Home Switch Normally Closed bit attribute determines the normal state of the home limit switch used by the homing sequence. The normal state of the switch is its state before being engaged by the axis during the homing sequence. For example, if the Home Switch Normally Closed bit is set (true) then the condition of the switch before homing is closed. When the switch is engaged by the axis during the homing sequence, the switch is opened, which constitutes a homing event.

Home Direction

AXIS_GENERIC AXIS_SERVO AXIS_SERVO_DRIVE AXIS_VIRTUAL

SINT

GSV SSV

0 = unidirectional forward 1 = bidirectional forward 2 = unidirectional reverse 3 = bidirectional reverse

Home Event Armed Status

AXIS_CONSUMED AXIS_GENERIC AXIS_SERVO AXIS_SERVO_DRIVE AXIS_VIRTUAL

BOOL

Tag

Set when a home event is armed through execution of the MAH (Motion Axis Home) instruction. Cleared when a home event occurs.

Home Event Status

AXIS_CONSUMED AXIS_GENERIC AXIS_SERVO AXIS_SERVO_DRIVE AXIS_VIRTUAL

BOOL

Tag

Set when a home event occurs. Cleared when another MAH (Motion Axis Home) instruction is executed.

Home Event Task

AXIS_CONSUMED AXIS_GENERIC AXIS_SERVO AXIS_SERVO_DRIVE AXIS_VIRTUAL

DINT

MSG

User Event Task that is triggered to execute when a Home event occurs. An instance value of 0 indicates that no event task is configured to be triggered by the Home Event. This attribute indicates which user Task is triggered when a home event occurs. The triggering of the user Task occurs simultaneously with the setting of the Process Complete bit for the instruction that armed the home event. This attribute is set through internal communication from the user Task object to the Axis object when the Task trigger attribute is set to select the Home Event Task Instance attribute of the Axis. This attribute should not be set directly by an external device. This attribute is available to be read externally (Get attributes List) for diagnostic information.

Home Input Status

AXIS_SERVO AXIS_SERVO_DRIVE

BOOL

Tag

If this bit is: • ON, The home input is active. • OFF, The home input is inactive.

Home Mode

AXIS_GENERIC AXIS_SERVO AXIS_SERVO_DRIVE AXIS_VIRTUAL

SINT

GSV SSV

0 = passive 1 = active (default) 2 = absolute

Rockwell Automation Publication MOTION-UM001H-EN-P - November 2018

221

Page 222

Appendix B

Motion axis attributes

Attribute

Axis Type

Data Type

Access

Description

Home Offset

AXIS_GENERIC AXIS_SERVO AXIS_SERVO_DRIVE AXIS_VIRTUAL

REAL

GSV SSV

Position Units When applied to an active or passive Homing Mode, using a non-immediate Home Sequence, the Home Offset is the desired position offset of the axis Home Position from the position at which the home event occurred. The Home Offset is applied at the end of the specified homing sequence before the axis moves to the Home Position. In most cases, Home Offset is set to zero. After an active bidirectional homing sequence completes, the axis is left at the specified Home Position. If the Home Offset is non-zero, the axis is then offset from the marker or home switch event point by the Home Offset value. If the Home Offset is zero, the axis sits right ‘on top of’ the marker or home switch point.

Home Position

AXIS_GENERIC AXIS_SERVO AXIS_SERVO_DRIVE AXIS_VIRTUAL

REAL

GSV SSV

Position Units The Home Position is the desired absolute position for the axis after the specified homing sequence completes. After an active homing sequence completes, the axis is left at the specified Home Position. In most cases, Home Position is set to zero, although any value, within the Maximum Positive and Negative Travel limits of the axis (if enabled), may also be used. (A description of the Maximum Positive and Negative Travel configuration attributes may be found in the Servo and Drive Axis Object specifications). For a rotary axis, the Home Position is constrained to be a positive number less than the Position Unwind value divided by the Conversion Constant. When configured for absolute Homing Mode, the Home Position value is applied directly to the absolute feedback device to establish an absolute position reference for the system.

Home Return Speed

AXIS_GENERIC AXIS_SERVO AXIS_SERVO_DRIVE

REAL

GSV SSV

Position Units / Seconds The Home Return Speed attribute controls the speed of the jog profile used after the first leg of an active bidirectional homing sequence.

Home Sequence

AXIS_GENERIC AXIS_SERVO AXIS_SERVO_DRIVE AXIS_VIRTUAL

SINT

GSV SSV

0 = immediate (default) 1 = switch 2 = marker 3 = switch then marker 4 = torque limit 5 = torque limit then marker

Home Speed

AXIS_GENERIC AXIS_SERVO AXIS_SERVO_DRIVE

REAL

GSV SSV

Position Units / Seconds The Home Speed attribute controls the speed of the jog profile used in the first leg of an active homing sequence as described in the above discussion of the Home Sequence Type attribute.

Axis Homed Status

AXIS_CONSUMED AXIS_GENERIC AXIS_SERVO AXIS_SERVO_DRIVE AXIS_VIRTUAL

BOOL

Tag

The HomedStatus bit is set by the MAH instruction upon successful completion of the configured homing sequence. This bit indicates that an absolute machine reference position is established. When this bit is set, operations that require a machine reference, such as Software Overtravel checking can be meaningfully enabled. For CIP Drive axis data types, the HomedStatus bit, is cleared under these conditions: • MRP instruction For non-CIP Drive axis data types, the HomedStatus bit is cleared under these conditions: • Download • Control power cycle • Reconnection to Motion Module • Feedback Loss Fault • Shutdown

222

Rockwell Automation Publication MOTION-UM001H-EN-P - November 2018

Page 223

Motion axis attributes

Appendix B

Attribute

Axis Type

Data Type

Access

Description

Homing Status

AXIS_CONSUMED AXIS_SERVO AXIS_SERVO_DRIVE AXIS_VIRTUAL

BOOL

Tag

Set if a Home motion profile is currently in progress. Cleared when the homing operation is stopped or is superseded by some other motion operation.

Inhibit Status

AXIS_SERVO AXIS_SERVO_DRIVE

BOOL

Tag

Use the InhibitStatus bit of an axis to see if the axis is inhibited or uninhibited. If the bit is: • ON, The axis is inhibited. • OFF, The axis is uninhibited. The controller changes the InhibitStatus bit only after this occurs. • The axis changes to inhibited or uninhibited. • All uninhibited axes are ready. • The connections to the motion module are running again.

InhibitAxis

AXIS_SERVO AXIS_SERVO_DRIVE

INT

GSV SSV

Integrator Hold Enable

AXIS_SERVO AXIS_SERVO_DRIVE

SINT

GSV SSV

When the Integrator Hold Enable attribute value is configured TRUE, the servo loop temporarily disables any enabled integrators while the command position is changing. This feature is used by point-to-point moves to minimize the integrator wind-up during motion. When the Integrator Hold Enable attribute value is FALSE, all active integrators are enabled. 0 = disabled 1 = enabled

Inter Module Sync Fault AXIS_SERVO

BOOL

Tag

If this bit is on, the analog servo cards of a SoftLogix5800 controller aren’t synchronized. The hardware or vbfirmware of the card causes this fault. For example, the cable between 2 cards isn’t connected.

Interpolated Actual Position

AXIS_CONSUMED AXIS_GENERIC AXIS_SERVO AXIS_SERVO_DRIVE AXIS_VIRTUAL

REAL

GSV Tag

Interpolated Actual Position in Position Units Interpolated Actual Position is the interpolation of the actual position, based on past axis trajectory history, at the time specified by the ‘Interpolated Time’ attribute.

Interpolated Command AXIS_CONSUMED Position AXIS_GENERIC AXIS_SERVO AXIS_SERVO_DRIVE AXIS_VIRTUAL

REAL

GSV Tag

Interpolated Command Position in Position Units Interpolated Command Position is the interpolation of the commanded position, based on past axis trajectory history, at the time specified by the ‘Interpolated Time’ attribute.

Interpolation Time

AXIS_CONSUMED AXIS_GENERIC AXIS_SERVO AXIS_SERVO_DRIVE AXIS_VIRTUAL

DINT

GSV/SSV Tag

CST time to interpolate to Interpolated Time is the 32-bit CST time used to calculate the interpolated positions. When this attribute is updated with a CST value, the Interpolated Actual Position and Interpolated Command Position values are automatically calculated.

Jog Status

AXIS_CONSUMED AXIS_GENERIC AXIS_SERVO AXIS_SERVO_DRIVE AXIS_VIRTUAL

BOOL

Tag

Set if a Jog motion profile is currently in progress. Cleared when the Jog is complete or is superseded by some other motion operation.

Rockwell Automation Publication MOTION-UM001H-EN-P - November 2018

223

Page 224

Appendix B

Motion axis attributes

Attribute

Axis Type

Data Type

Access

Description

LDT Calibration Constant

AXIS_SERVO

REAL

GSV

This attribute provides for setting a calibration constant for LDT devices. This attribute is only active if the Transducer Type is set to LDT.

LDT Calibration Constant Units

AXIS_SERVO

SINT

GSV

0 = m/sec 1 = Usec/in This attribute provides a selection for the units of the LDT calibration constant attribute. This attribute is only active if the Transducer Type is set to LDT.

LDT Length

AXIS_SERVO

REAL

GSV

This attribute provides for setting the length of an LDT device. This attribute is only active if the Transducer Type is set to LDT.

LDT Length Units

AXIS_SERVO

SINT

GSV

0=m 1 = in This attribute provides a selection for the units of the LDT length attribute. This attribute is only active if the Transducer Type is set to LDT.

LDT Recirculations

AXIS_SERVO

SINT

GSV

This attribute provides the number of recirculations. This attribute is only active if the Transducer Type is set to LDT and LDT Type is set to PWM.

LDT Scaling

AXIS_SERVO

REAL

GSV

This attribute provides for setting the scaling factor for LDT devices. This attribute is only active if the Transducer Type is set to LDT.

LDT Scaling Units

AXIS_SERVO

SINT

GSV

0 = Position Units/m 1 = Position Units/in This attribute provides a selection for the units of the LDT scaling attribute. This attribute is only active if the Transducer Type is set to LDT.

LDT Type

AXIS_SERVO

SINT

GSV

0 = PWM 1 = Start/Stop Rising 2 = Start/Stop Falling This attribute provides a selection for the LDT Type. It provides these enumerated values: PWM, Start/Stop Rising, and Start/Stop Falling. This attribute is only active if the Transducer Type is set to LDT.

Linear Motor Mass

AXIS_SERVO_DRIVE

REAL

SSV

The Linear Motor Mass attribute is a float that specifies the unloaded moving mass of a linear motor.

Linear Motor Rated Speed

AXIS_SERVO_DRIVE

REAL

GSV

The Linear Motor Rated Speed attribute is a float that specifies the nameplate rated speed of a linear motor. For PM motors, this is generally specified at rated voltage based on rated current, rated force, or rated power. For induction motors, this value is the speed of the motor driven at rated frequency under rated force load. This value is synonymous with the term base speed.

Load Inertia Ratio

AXIS_SERVO_DRIVE

REAL

GSV SSV

%Rated / Pos Units per Sec2 The Motor Inertia value represents the inertia of the motor without any load attached to the motor shaft in Torque Scaling units of %Rated / Pos Units per Sec2. The Load Inertia Ratio attribute’s value represents the ratio of the load inertia to the motor inertia. Auto-tuning uses the Motor Inertia value to calculate the Load Inertia Ratio based on this equation. Load Inertia Ratio = (Total Inertia - Motor Inertia) / Motor Inertia. Total Inertia is directly measured by the auto-tuning algorithm and applied to the Torque Scaling attribute in units of %Rated / Pos Units per Sec2. If the Load Inertia Ratio value is known, the Motor Inertia value can also be used to calculate a suitable Torque Scaling value for the fully loaded motor without performing an auto-tune. The equation used by RSLogix5000 and the Logix Designer application to calculate the Torque Scaling value is: Torque Scaling = (1 + Load Inertia Ratio) * Motor Inertia. The value for Load Inertia may be automatically calculated using Rockwell’s MotionBook program while the value for Motor Inertia is derived from the Motion database file based on the motor selection.

224

Rockwell Automation Publication MOTION-UM001H-EN-P - November 2018

Page 225

Motion axis attributes

Appendix B

Attribute

Axis Type

Data Type

Access

Description

Map Instance

AXIS_GENERIC AXIS_SERVO AXIS_SERVO_DRIVE

DINT

GSV

I/O Map Instance Number. This is 0 for virtual and consumed Data Types. The axis is associated to a motion compatible module by specifying the instance of the map entry representing the module.

Marker Distance

AXIS_SERVO AXIS_SERVO_DRIVE

REAL

GSV Tag

Important: To use this attribute, choose it as one of the attributes for Real Time Axis Information for the axis. Otherwise, the right value is not seen as the axis runs. See Axis Info Select 1. Marker Distance in Position Units Marker Distance is the distance between the axis position at which a home switch input was detected and the axis position at which the marker event was detected. This value is useful in aligning a home limit switch relative to a feedback marker pulse to provide repeatable homing operation.

Rockwell Automation Publication MOTION-UM001H-EN-P - November 2018

225

Page 226

Appendix B

Motion axis attributes

Master Input Configuration Bits

AXIS_GENERIC AXIS_SERVO AXIS_SERVO_DRIVE AXIS_VIRTUAL

226

DINT

GSV SSV

Bits 0 = Master Delay Compensation 1 = Master Position Filter Master Delay Compensation By default, the Position Camming and Gearing functions, when applied to a slave axis, perform Master Delay Compensation to compensate for the delay time between reading the master axis command position and applying the associated slave command position to the input of the slave’s servo loop. When the master axis is running at a fixed speed, this compensation technique insures that the slave axis command position accurately tracks the actual position of the master axis; in other words, Master Delay Compensation allows for zero tracking error when gearing or camming to the actual position of a master axis. The Master Delay Compensation algorithm extrapolates the position of the master axis at the predicted time when the command position is applied to the slave’s servo loop. Because master axis position is measured in discrete feedback counts and is inherently noisy, the extrapolation process amplifies that noise according to the total position update delay. The total position update delay is proportional to the Base Update Period of the motion group, and, if the master or the slave involves an AXIS_SERVO_DRIVE data type, it also includes the delay term that is proportional to the SERCOS Update Period. The greater the delay, the greater the noise introduced by the extrapolator. The Master Delay Compensation feature also has an extrapolation filter to filter the noise introduced by the extrapolation process. The time constant of the filter is fixed at 4x the total position update delay (independent of the Master Position Filter Bandwidth), which again is a function of the Base Update Period (and the SERCOS Update Period, if a AXIS_SERVO_DRIVE data type). The controller uses a 1st order extrapolation algorithm that results in zero tracking error while the master axis is moving at constant velocity. If the master axis accelerates or decelerates the tracking error is non-zero and proportional to the acceleration or deceleration rate and also proportional to the square of the total position update delay time. From a noise and acceleration error perspective, minimizing the base update period is vital. Some applications do not need zero tracking error between the master and the slave axis. In these cases, it may be beneficial to disable the Master Delay Compensation feature to eliminate the disturbances the extrapolation algorithm introduces to the slave axis. When the Master Delay Compensation feature is disabled (bit cleared), the slave axis appears to be more responsive to movements of the master and run generally smoother than when the Master Delay Compensation feature is enabled (bit set). However, when the master axis is running at a constant velocity, the slave lags the master by a tracking error that is proportional to the speed of the master. This function does not get applied when the Master is a Virtual Axis. Master Delay Compensation, even if explicitly enabled, is not applied in cases where a slave axis is gearing or camming to the master axis’ command position. Because the controller generates the command position directly, there is no intrinsic master position delay to compensate for. Master Position Filter The Master Position Filter bit controls the activity of an independent single-pole low-pass filter that effectively filters the specified master axis position input to the slave’s gearing or position camming operation. When enabled (bit set), this filter has the effect of smoothing out the actual position signal from the master axis, and thus smoothing out the corresponding motion of the slave axis. The trade-off for smoothness is an increase in lag time between the response of the slave axis to changes in motion of the master. Note that the Master Position Filter also provides filtering to the extrapolation noise introduced by the Master Delay Compensation algorithm, if enabled. When the Master Position Filter bit is set, the bandwidth of the Master Position Filter is controlled by the Master Position Filter Bandwidth attribute, see below. This can be done by setting the Master Position Filter bit and controlling the Master Position Filter Bandwidth directly. Setting the Master Position Filter Bandwidth to zero can be used to effectively disable the filter.

Rockwell Automation Publication MOTION-UM001H-EN-P - November 2018

Page 227

Motion axis attributes

Appendix B

Attribute

Axis Type

Data Type

Access

Description

Master Offset

AXIS_CONSUMED AXIS_GENERIC AXIS_SERVO AXIS_SERVO_DRIVE AXIS_VIRTUAL

REAL

GSV Tag

Important: To use this attribute, make sure Auto Tag Update is Enabled for the motion group (default setting). Otherwise, the right value is not seen as the axis runs. Master Offset in Master Position Units The Master Offset is the position offset that is currently applied to the master side of the position cam. The Master Offset is returned in master position units. The Master Offset shows the same unwind characteristic as the position of a linear axis.

Master Offset Move Status

AXIS_CONSUMED AXIS_GENERIC AXIS_SERVO AXIS_SERVO_DRIVE AXIS_VIRTUAL

BOOL

Tag

Set if a Master Offset Move motion profile is currently in progress. This bit is cleared when the Master Offset Move is complete or is superseded by some other motion operation.

Master Position Filter Bandwidth

AXIS_GENERIC AXIS_SERVO AXIS_SERVO_DRIVE AXIS_VIRTUAL

REAL

GSV SSV

Hertz The Master Position Filter Bandwidth attribute controls the activity of the single-pole lowpass filter that filters the specified master axis position input to the slave’s gearing or position camming operation. When enabled, this filter smooths out the actual position signal from the master axis, and thus smooths out the corresponding motion of the slave axis. The trade-off for smoothness is an increase in lag time between the response of the slave axis to changes in motion of the master. If the Master Position Filter is disabled, the Master Position Filter Bandwidth does not function.

Maximum Acceleration AXIS_GENERIC AXIS_SERVO AXIS_SERVO_DRIVE AXIS_VIRTUAL

REAL

GSV SSV

Position Units / Sec2 The Maximum Acceleration and Deceleration attribute values are frequently used by motion instructions such as MAJ, MAM, MCD, to determine the acceleration and deceleration rates to apply to the axis. These instructions all have the option of specifying acceleration and deceleration as a percent of the Maximum Acceleration and Maximum Deceleration attributes for the axis. The Maximum Acceleration and Maximum Deceleration values for the axis are automatically set to ~ 85% of the measured Tune Acceleration and Tune Deceleration by the MAAT (Motion Apply Axis Tune) instruction. If set manually, these values should typically be set to ~85% of the maximum acceleration and maximum deceleration rate of the axis. This provides sufficient ‘head-room’ for the axis to operate at all times within the acceleration and deceleration limits of the drive and motor.

Maximum Deceleration AXIS_GENERIC AXIS_SERVO AXIS_SERVO_DRIVE AXIS_VIRTUAL

REAL

GSV SSV

Position Units / Sec2 The Maximum Acceleration and Deceleration attribute values are frequently used by motion instructions such as MAJ, MAM, MCD, to determine the acceleration and deceleration rates to apply to the axis. These instructions all have the option of specifying acceleration and deceleration as a percent of the Maximum Acceleration and Maximum Deceleration attributes for the axis. The Maximum Acceleration and Maximum Deceleration values for the axis are automatically set to ~ 85% of the measured Tune Acceleration and Tune Deceleration by the MAAT (Motion Apply Axis Tune) instruction. If set manually, these values should typically be set to ~85% of the maximum acceleration and maximum deceleration rate of the axis. This provides sufficient ‘head-room’ for the axis to operate at all times within the acceleration and deceleration limits of the drive and motor.

Rockwell Automation Publication MOTION-UM001H-EN-P - November 2018

227

Page 228

Appendix B

Motion axis attributes

Attribute

Axis Type

Data Type

Access

Description

Maximum Negative Travel

AXIS_SERVO AXIS_SERVO_DRIVE

REAL

GSV SSV

Position Units The Axis Object provides configurable software travel limits via the Maximum Positive and Negative Travel attributes. If the axis is configured for software overtravel limit checking by setting the Soft Overtravel Bit and the axis passes outside these maximum travel limits, a Software Overtravel Fault is issued. When software overtravel checking is enabled, values for the maximum travel in the Maximum Positive and Maximum Negative Travel attributes need to be established with Maximum Positive Travel greater than Maximum Negative Travel. These values are specified in the configured Position Units of the axis. Soft Travel limits are checked if the Soft Travel Limit enable attribute is true. This controller attribute is replicated in the motion module.

Maximum Positive Travel

AXIS_SERVO AXIS_SERVO_DRIVE

REAL

GSV SSV

Position Units The Axis Object provides configurable software travel limits via the Maximum Positive and Negative Travel attributes. If the axis is configured for software overtravel limit checking by setting the Soft Overtravel Bit and the axis passes outside these maximum travel limits, a Software Overtravel Fault is issued. When software overtravel checking is enabled, values for the maximum travel in the Maximum Positive and Maximum Negative Travel attributes need to be established with Maximum Positive Travel greater than Maximum Negative Travel. These values are specified in the configured Position Units of the axis. Soft Travel limits are checked if the Soft Travel Limit enable attribute is true. This controller attribute is replicated in the motion module

Maximum Speed

AXIS_GENERIC AXIS_SERVO AXIS_SERVO_DRIVE AXIS_VIRTUAL

REAL

GSV SSV

Position Units / Sec The value of the Maximum Speed attribute is used by various motion instructions (for example, MAJ, MAM, MCD) to determine the steady-state speed of the axis. These instructions all have the option of specifying speed as a percent of the Maximum Speed attribute value for the axis. The Maximum Speed value for the axis is automatically set to the Tuning Speed by the MAAT (Motion Apply Axis Tune) instruction. This value is typically set to ~90% of the maximum speed rating of the motor. This provides sufficient ‘headroom’ for the axis to operate at all times within the speed limitations of the motor.

Memory Usage

AXIS_CONSUMED AXIS_GENERIC AXIS_SERVO AXIS_SERVO_DRIVE AXIS_VIRTUAL

DINT

MSG

Amount of memory consumed for this instance (in bytes)

Memory Use

AXIS_CONSUMED AXIS_GENERIC AXIS_SERVO AXIS_SERVO_DRIVE AXIS_VIRTUAL

INT

GSV

Controller memory space where instance exists. 105 (0x69) = I/O space 106 (0x6a) = Data Table space Logix Designer software uses this attribute to create axis instances in I/O memory for axes that are to be produced or consumed. The Memory Use attribute can only be set as part of an axis create service and is used to control which controller memory the object instance is created in.

Module Channel

AXIS_GENERIC AXIS_SERVO AXIS_SERVO_DRIVE

SINT

GSV

Zero based channel number of the module. 0xff, indicates unassigned. The axis is associated to a channel on a motion module by specifying the Module Channel attribute.

Module Class Code

AXIS_SERVO AXIS_SERVO_DRIVE

DINT

GSV

ASA Object class code of the motion engine in the module; for example, 0xAF for the M02AE module. The ASA class code of the object in the motion module that is supporting motion; for example, 0xAF is the ASA object ID of the ‘Servo Module Axis Object’ residing in the 1756M02AE module.

228

Rockwell Automation Publication MOTION-UM001H-EN-P - November 2018

Page 229

Motion axis attributes

Appendix B

Attribute

Axis Type

Data Type

Access

Description

Module Fault

AXIS_CONSUMED AXIS_GENERIC AXIS_SERVO AXIS_SERVO_DRIVE AXIS_VIRTUAL

BOOL

Tag

Set when a serious fault occurs with the motion module associated with the selected axis. Usually a module fault affects all axes associated with the motion module. A module fault generally results in the shutdown of all associated axes. Reconfiguration of the motion module is required to recover from a module fault condition. Should this fault give the controller a major fault? • YES, Set the General Fault Type of the motion group = Major Fault. • NO, Write code to handle these faults.

Module Fault Bits

AXIS_CONSUMED AXIS_SERVO AXIS_SERVO_DRIVE

DINT

GSV*

Allows access to the module fault bits in one 32-bit word. This attribute is the same as the Module Faults tag.

These faults have module scope instead of axis scope. • These faults show up in all axes that are connected to the motion module. • The motion planner updates these fault bits every base update period. Should any of these faults to give the controller a major fault? • YES, Set the General Fault Type of the motion group = Major Fault. • NO, Write code to handle these faults. Module Faults

AXIS_SERVO AXIS_SERVO_DRIVE

DINT

Tag

Allows access to the module fault bits in one 32-bit word. This tag is the same as the Module Fault Bits attribute.

These faults have module scope instead of axis scope. • These faults show up in all axes that are connected to the motion module. • The motion planner updates these fault bits every base update period. Should any of these faults give the controller a major fault? • YES, Set the General Fault Type of the motion group = Major Fault. • NO, Write code to handle these faults. Module Hardware Fault AXIS_SERVO AXIS_SERVO_DRIVE

BOOL

Tag

If this bit is set, there is a hardware issue with the motion module that, in general, is going to require replacement of the module.

Rockwell Automation Publication MOTION-UM001H-EN-P - November 2018

229

Page 230

Appendix B

Motion axis attributes

Attribute

Axis Type

Data Type

Access

Description

Module Sync Fault

AXIS_SERVO AXIS_SERVO_DRIVE

BOOL

Tag

If this bit is set, the motion module lost communication with the controller and missed several position updates in a row. • The motion module can miss up to 4 position updates. After that, the motion module shuts down. • This bit clears when communication is reestablished.

Mot Feedback Fault

AXIS_SERVO_DRIVE

BOOL

Tag

Set for the A Quad B feedback device when one of these happens: • The differential electrical signals for one or more of the feedback channels (for example, A+ and A-, B+ and B-, or Z+ and Z-) are at the same level (high or low). Under normal operation, the differential signals are at opposite levels. The most common cause of this situation is a broken wire between the feedback transducer and the servo module or drive. • Loss of feedback ‘power’ or feedback ‘common’ electrical connection between the servo module or drive and the feedback device. The controller latches this fault. Use a Motion Axis Fault Reset (MAFR) or Motion Axis Shutdown Reset (MASR) instruction to clear the fault.

Motor Feedback Noise Fault

AXIS_SERVO_DRIVE

BOOL

Tag

Set when there is noise on the feedback device’s signal lines. • For example, simultaneous transitions of the feedback A and B channels of an A Quad B is referred to generally as feedback noise. • Feedback noise (shown below) is most often caused by loss of quadrature in the feedback device itself or radiated common-mode noise signals being picked up by the feedback device wiring. This can be seen on an oscilloscope.

• To troubleshoot the loss of channel quadrature, look for: • physical misalignment of the feedback transducer components

• excessive capacitance (or other delays) on the encoder signals

• Proper grounding and shielding usually cures radiated noise problems. The controller latches this fault. Use a Motion Axis Fault Reset (MAFR) or Motion Axis Shutdown Reset (MASR) instruction to clear the fault. Motion Status

230

AXIS_CONSUMED AXIS_GENERIC AXIS_SERVO AXIS_SERVO_DRIVE AXIS_VIRTUAL

DINT

Tag

Allows access to all motion status bits in one 32-bit word. This tag is the same as the Motion Status Bits attribute.

Rockwell Automation Publication MOTION-UM001H-EN-P - November 2018