Page 21
Configure SERCOS motion
Chapter 1
8. In the Security Authority list, select a security option: •
No Protection - All users can view and edit the project.
•
FactoryTalk Security - Only users authenticated through FactoryTalk Security can view and edit the project
9. (optional) Select Use only the selected Security Authority for authentication and authorization to associate this project with a specific Security Authority. When this check box is selected, users interacting with this project must be authenticated and authorized by the same Security Authority that was used to secure the project. Otherwise, unauthenticated users must rely on Guest User permissions. Tip:
Guest User permissions are cached within the project. The Logix Designer application uses Guest User permissions when the project is opened but not connected to the FactoryTalk Security Authority that secures the project. By default, all Guest User permissions are denied. Guest User permissions are configured in the FactoryTalk Administration Console.
10. Select Logical Name <Controller Name> or Permission Set to apply specific permissions to the controller. Select Logical Name <Controller Name> to apply a Logical Name in FactoryTalk Services Platform that has the same name as the controller. If there is no existing Logical Name that matches the controller name, a new Logical Name is created with the controller's name. The new Logical Name inherits permissions from its parent resource. See FactoryTalk Help for more information on how networks and devices inherit security permissions. Select Permission Set to apply a specific set of permissions to the controller. The permission sets in the list are maintained in FactoryTalk Services Platform and identify a set of actions that are allowed or denied for a particular user and computer combination. 11. (optional) In the Description box, type a description for the controller. Tip:
The description is limited to 128 bytes. Standard ASCII characters consume 1 byte per character, allowing for 128 characters. Characters in some languages require up to three bytes per character, resulting in less than 128 characters.
12. (optional) Select Enable redundancy if this project supports an automatic transfer of project control to a redundant controller in case of primary controller failure. 13. Select Finish.
Rockwell Automation Publication MOTION-UM001H-EN-P - November 2018
21
Page 22
Chapter 1
Configure SERCOS motion
See also Add a SERCOS motion module on page 23 Add a SERCOS interface drive module on page 27 Add a motion group for Configure SERCOS motion on page 32 Add an axis on page 34
Set time synchronization for Configure SERCOS Motion
Time Synchronization in ControlLogix is called CIP Sync. CIP Sync is a layer of functionality that Rockwell Automation has developed on top of the IEEE 1588 PTP protocol. CIP Sync maintains accurate time synchronization of automation solutions. This setting establishes the module to participate in time synchronization. In systems with multiple processors, all controllers must have time synchronization enabled if they use CSmainT/PTP time. The 1756-ENxT communication modules win the arbitration over any processor. To set time synchronization for Configure SERCOS Motion: 1. In the Controller Organizer, double-click the controller. 2. On the Controller Properties dialog box, select the Date/Time tab.
3. Select Enable Time Synchronization. 22
Rockwell Automation Publication MOTION-UM001H-EN-P - November 2018
Page 23
Configure SERCOS motion
Chapter 1
4. Select OK. Without intervention, the Grandmaster is PTP and CST master. Use the settings on the Advanced dialog box to let this module win the arbitration over other processors and communication modules in the chassis. See also Integrated Architecture and CIP Sync Configuration Application Technique, publication IA-AT003
Add a SERCOS motion module
Use these instructions to add a SERCOS module to the system. Important:
For all modules, use the firmware revision that goes with the firmware revision of the controller. See the release notes for the controller’s firmware.
To add a SERCOS motion module: 1. In the Controller Organizer, right-click the backplane and select New Module.
2. On the Select Module Type dialog box, choose the module to add to the project.
Rockwell Automation Publication MOTION-UM001H-EN-P - November 2018
23
Page 24
Chapter 1
Configure SERCOS motion
3. Select Close on Create, and select Create. 4. On the New Module dialog box, in Name, type a name for the module.
5. In Slot, choose the number that corresponds to the physical slot that contains the module. 6. (optional) In Description, type a description. 7. In Electronic Keying, choose a keying option of either Compatible Keying or Exact Match. WARNING: Disable Keying should never be used with motion modules.
8. Select Open Module Properties, and select OK. Continue with the instructions to modify the properties for the motion module. See also Electronic Keying on page 24 Modify properties for a SERCOS motion module on page 25
Electronic Keying
Electronic Keying reduces the possibility of using the wrong device in a control system. Electronic Keying compares the device defined in the project to the installed device. If keying fails, a fault occurs. These attributes are compared:
24
Attribute
Description
Vendor
The device manufacturer.
Device Type
The general type of the device, for example, digital I/O module.
Product Code
The specific type of device. The Product Code maps to a catalog number. Rockwell Automation Publication MOTION-UM001H-EN-P - November 2018
Page 25
Configure SERCOS motion
Chapter 1
Major Revision
A number that represents the functional capabilities of a device.
Minor Revision
A number that represents behavior changes in the device.
These Electronic Keying options are available: Keying Option
Description
Compatible Module
Lets the installed device accept the key of the device that is defined in the project when the installed device can emulate the defined device. Typically, use Compatible Module, to replace a device with another device that has the following characteristics: • Same catalog number • Same or higher Major Revision • Minor Revision as follows: •
If the Major Revision is the same, the Minor Revision must be the same or higher.
•
If the Major Revision is higher, the Minor Revision can be any number.
Disable Keying
Indicates that the keying attributes are not considered when attempting to communicate with a device. With Disable Keying, communication can occur with a device other than the type specified in the project. ATTENTION: Be extremely cautious when using Disable Keying. If used incorrectly, this option can lead to personal injury or death, property damage, or economic loss. We strongly recommend not using Disable Keying. If using Disable Keying, take full responsibility for understanding whether the device being used can fulfill the functional requirements of the application.
Exact Match
Indicates that all keying attributes must match to establish communication. If any attribute does not match precisely, communication with the device does not occur.
Carefully consider the implications of each keying option when selecting one. Important:
Modify properties for a SERCOS motion module
Changing Electronic Keying parameters online interrupts connections to the device and any devices that are connected through the device. Connections from other controllers can also be broken. If an I/O connection to a device is interrupted, the result can be a loss of data.
Use these instructions to modify the module properties. To modify properties for a SERCOS motion module: 1. If the Module Properties Report dialog box is not already open, in the Controller Organizer, double-click the motion module. 2. On the Module Properties Report dialog box, select the Connection tab.
Rockwell Automation Publication MOTION-UM001H-EN-P - November 2018
25
Page 26
Chapter 1
Configure SERCOS motion
3. Verify that Major Fault on Controller If Connection Fails While in Run Mode is clear.
Tip:
Keep this check box clear until the program executes the first time. Otherwise the controller generates a Major Fault when the SERCOS ring attempts to phase up the first time.
4. Select the SERCOS Interface tab.
5. In Data Rate and Cycle Time, choose the baud rate and update rate for the SERCOS ring using this table as a guide. The data rate and the number of drives associated with the module dictate the minimum cycle time.
26
Baud Rate of Drives
Number of Drives on the Ring
Type of Drives
Cycle Time
4 Mbps
Up to 2
Kinetix 2000 Kinetix 6000 Kinetix 6200 Kinetix 7000
0.5 ms
Rockwell Automation Publication MOTION-UM001H-EN-P - November 2018
Page 27
Configure SERCOS motion
Baud Rate of Drives
Chapter 1
Number of Drives on the Ring
Type of Drives
Cycle Time
Up to 4, 1 ms
Up to 8, 2 ms
9…16, No Support
Tip: The Ultra 3000 must be 1 or 2 ms SERCOS cycle time because the position loop update time minimum is 1 ms. 8 Mbps
Kinetix 2000 Kinetix 6000 Kinetix 6200 Kinetix 7000
Up to 4
0.5 ms
Up to 8, 1 ms
Up to 16, 2 ms
For more information about configuring the Kinetix 6200 and Kinetix 6500 servo drive systems, see the Kinetix 6200 and Kinetix 6500 Modular Multi-axis Servo Drive User Manual, publication 2094-UM002. 6. Select OK. See also Add a motion group for Configure SERCOS Motion on page 32 Add an axis for Configure SERCOS Motion on page 34
More information
For more detailed information on Electronic Keying, see Electronic Keying in Logix 5000 Control Systems Application Technique, publication LOGIXAT001.
Add a SERCOS interface drive module
Use these instructions to add a SERCOS interface drive module to the I/O configuration of the controller.
Rockwell Automation Publication MOTION-UM001H-EN-P - November 2018
27
Page 28
Chapter 1
Configure SERCOS motion
Important:
For all modules, use the firmware revision that goes with the firmware revision of the controller. See the release notes for the controller’s firmware.
To add a SERCOS interface drive module: 1. In the Controller Organizer, right-click SERCOS Network and select New Module.
2. On the Select Module Type dialog box, choose the module to add to the project.
3. Select Close on Create, and select Create.
28
Rockwell Automation Publication MOTION-UM001H-EN-P - November 2018
Page 29
Configure SERCOS motion
Chapter 1
4. On the New Module dialog box, in the Name box, type a name for the interface drive.
5. In the Node box, choose the SERCOS node number of the interface drive (see the module's rotary switch). 6. (optional) In the Description box, type a description. 7. In the Revision boxes, choose the Major Revision and Minor Revision of the module. 8. In the Electronic Keying list, choose a keying option of either Compatible Keying or Exact Match. WARNING: Disable Keying should never be used with motion modules.
9. Select Open Module Properties, and select OK. Continue with the instructions to modify the properties for the interface drive. See also Electronic Keying on page 24
Modify properties for a SERCOS interface drive module
Use these instructions to modify drive properties. To modify properties for a SERCOS interface drive module: 1. If the Module Properties Report dialog box is not already open, in the Controller Organizer, double-click the interface drive.
Rockwell Automation Publication MOTION-UM001H-EN-P - November 2018
29
Page 30
Chapter 1
Configure SERCOS motion
2. On the Module Properties Report dialog box, select the Associated Axes tab.
3. Select New Axis to create an AXIS_SERVO tag to associate to one of the nodes. 4. On the New Tag dialog box, in Name, type a name for the axis tag.
5. Select Create. 6. (optional) Repeat steps 3 through 5 if an additional axis is required.
30
Rockwell Automation Publication MOTION-UM001H-EN-P - November 2018