The text of a manual · part 8 of 30
SERCOS and Analog Motion Configuration and Startup User Manual, pages 71 to 80
Pages 71 to 80 of 297
The original document is the PDF (13 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
For the Allen-Bradley 1756-M16SE/A
Page 71
Commission and tune
Chapter 3
Blocks the controller from using an axis because the axis is faulted or not installed. Lets the controller use the other axes.
Example 1 If the equipment needs between 8 and 12 axes, depending on the application, create one project for all 12 axes. When determining how many axes are needed, inhibit the axes that are not needed. Example 2 If two production lines use the same SERCOS ring and one of the lines gets a fault, inhibit the axes on that line. This allows the other line to run while the fault is addressed. If an axis is faulted, all axes are still available. If there is a hardware issue with one of the "drives," inhibit the axis and remove the faulty hardware. When the ring phases back up, the inhibited axis (with its missing hardware) does prevent the rest of the axes from operating.
Tip:
See also Example: Inhibit an axis on page 73 Example: Uninhibit an axis on page 74
Before you begin
This table explains what to do before beginning.
Rockwell Automation Publication MOTION-UM001H-EN-P - November 2018
71
Page 72
Chapter 3
Commission and tune
Before inhibiting or uninhibiting an axis, turn off all axes.
Before beginning: 1. Stop all motion. 2. Open the servo loops of all axes. Use an instruction such as the Motion Servo Off (MSF) instruction. This allows motion to stop under control. Otherwise the axes turn off on their own when inhibiting or uninhibiting one of them.
The controller automatically restarts the connections. The SERCOS ring also phases back up. Inhibit only certain types of axes.
Inhibit only these types of axes. • AXIS_SERVO • AXIS_SERVO_DRIVE
72
Rockwell Automation Publication MOTION-UM001H-EN-P - November 2018
Page 73
Commission and tune
Chapter 3
To inhibit all axes of a motion module, inhibit the module.
Inhibit all axes of a motion module? • YES, Inhibit the motion module. • NO, Inhibit the individual axes. Inhibit all axes of a module on an individual basis. However, inhibiting the module is more efficient than inhibiting each axis. Important: If inhibiting an axis on a drive, inhibit all action on the drive, including any half axes. Be aware of all action on a drive before inhibiting the axis. Example: If the motion module has two axes to inhibit, just inhibit the module.
If inhibiting all axes on a SERCOS ring, the drives phase up to phase 2. This happens whether inhibiting each axis individually or inhibiting the motion module.
Example: Inhibit an axis 1. Make sure all axes are off.
Rockwell Automation Publication MOTION-UM001H-EN-P - November 2018
73
Page 74
Chapter 3
Commission and tune
2. Use a one-shot instruction to trigger the inhibit.
3. Inhibit the axis.
4. Wait for the inhibit process to finish.
Example: Uninhibit an axis 1. Make sure all axes are off.
74
Rockwell Automation Publication MOTION-UM001H-EN-P - November 2018
Page 75
Commission and tune
Chapter 3
2. Use a one-shot instruction to trigger the uninhibit.
3. Uninhibit the axis.
4. Wait for the inhibit process to finish. All of these have happened: • The axis is uninhibited. •
All uninhibited axes are ready.
•
The connections to the motion module are running again.
•
For a SERCOS ring, the SERCOS ring has phased up again.
Test an axis with Motion Direct Commands
Motion Direct Commands allow issuing motion commands while online without writing or executing an application program. Motion Direct Commands are particularly useful when commissioning or debugging a motion application. During commissioning, configure an axis and monitor the behavior using Trends in the Controller Organizer. Use of Motion Direct Commands allows fine-tuning the system with or without load to optimize its performance. When in the testing and or debugging cycle, issue Motion Direct Commands to establish or reestablish conditions such as Home. Often during initial development or enhancement to mature applications testing the system in small manageable areas is necessary. The tasks include: •
Home to establish initial conditions
•
Incrementally Move to a physical position
•
Monitor system dynamics under certain conditions
Rockwell Automation Publication MOTION-UM001H-EN-P - November 2018
75
Page 76
Chapter 3
Commission and tune
Access the Motion Direct Commands for a motion group
Access the Motion Direct Commands for a motion group or motion axis. To access the Motion Direct Commands for a motion group •
In the Controller Organizer, right-click the group and select Motion Direct Commands.
See also Motion Direct Command dialog box on page 80
Access the Motion Direct Commands for an axis
76
Access the Motion Direct Commands from an axis in the motion group.
Rockwell Automation Publication MOTION-UM001H-EN-P - November 2018
Page 77
Commission and tune
Chapter 3
To access the Motion Direct Commands for an axis: •
In the Controller Organizer, right-click the axis and select Motion Direct Commands.
See also Motion Direct Command dialog box on page 80
Choose a command
Use the table to choose an instruction and check availability as a Motion Direct Command.
To
And
Use this instruction
Motion Direct Command
Change the state of an axis
Enable the servo drive and activate the axis servo loop.
MSO Motion Servo On
Yes
Turn off the servo drive and deactivate the axis servo loop.
MSF Motion Servo Off
Yes
Force an axis into the shutdown state and block any instructions that initiate axis motion.
MASD Motion Axis Shutdown
Yes
Transition an axis to the ready state. If all axes of a servo module MASR are removed from the shutdown state as a result of this Motion Axis Shutdown Reset instruction, the OK relay contacts for only an analog module close.
Yes
Enable the servo drive and set the servo output voltage of an axis. MDO Motion Direct Drive On
Yes
Rockwell Automation Publication MOTION-UM001H-EN-P - November 2018
77
Page 78
Chapter 3
Commission and tune
Turn off the servo drive and set the servo output voltage to the output offset voltage.
MDF Motion Direct Drive Off
Yes
Clear all motion faults for an axis.
MAFR Motion Axis Fault Reset
Yes
To
And
Use this instruction
Motion Direct Command
Control axis position
Stop any motion process on an axis.
MAS Motion Axis Stop
Yes
Home an axis.
MAH Motion Axis Home
Yes
Jog an axis.
MAJ Motion Axis Jog
Yes
Move an axis to a position.
MAM Motion Axis Move
Yes
Start electronic gearing between 2 axes.
MAG Motion Axis Gear
Yes
Initiate action on all axes
Change the speed, acceleration, or deceleration of a move or a jog MCD that is in progress. Motion Change Dynamics
Yes
Define a Master/Slave relationship between two motion axes and MDAC select which type of move instructions. Master Driven Axis Control
No
Change the command or actual position of an axis.
MRP Motion Redefine Position
Yes
Calculate a Cam Profile based on an array of cam points.
MCCP Motion Calculate Cam Profile
No
Start electronic camming between 2 axes.
MAPC Motion Axis Position Cam
No
Start electronic camming as a function of time.
MATC Motion Axis Time Cam
No
Calculate the slave value, slope, and derivative of the slope for a cam profile and master value.
MCSV Motion Calculate Slave Values
No
Stop motion of all axes.
MGS Motion Group Stop
Yes
Force all axes into the shutdown state.
MGSD Motion Group Shutdown
Yes
Transition all axes to the ready state.
MGSR Motion Group Shutdown Reset
Yes
Latch the current command and actual position of all axes.
MGSP Motion Group Strobe Position
Yes
MAW Motion Arm Watch Position
Yes
MDW Motion Disarm Watch Position
Yes
Arm the servo-module registration-event checking for an axis.
MAR Motion Arm Registration
Yes
Disarm the servo-module registration-event checking for an axis.
MDR Motion Disarm Registration
Yes
Arm and disarm special event checking Arm the watch-position event checking for an axis. functions such as registration and watch position Disarm the watch-position event checking for an axis.
78
Rockwell Automation Publication MOTION-UM001H-EN-P - November 2018
Page 79
Commission and tune
Tune an axis and run diagnostic tests for the control system. These tests include: • Motor/encoder hookup test
Chapter 3
Arm an output cam for an axis and output.
MAOC Motion Arm Output Cam
No
Disarm one or all output cams connected to an axis.
MDOC Motion Disarm Output Cam
No
Use the results of an MAAT instruction to calculate and update the MAAT servo gains and dynamic limits of an axis. Motion Apply Axis Tuning
No
Run a tuning motion profile for an axis.
MRAT Motion Run Axis Tuning
No
Use the results of an MRHD instruction to set encoder and servo polarities.
MAHD Motion Apply Hookup Diagnostic
No
Run one of the diagnostic tests on an axis.
MRHD Motion Run Hookup Diagnostic
No
Start a linear coordinated move for the axes of coordinate system. MCLM Motion Coordinated Linear Move
No
Start a circular move for the axes of coordinate system.
MCCM Motion Coordinated Circular Move
No
Change in path dynamics for the active motion on a coordinate system.
MCCD Motion Coordinated Change Dynamics
No
Stop the axes of a coordinate system.
MCS Motion Coordinated Stop
No
Shutdown the axes of a coordinate system.
MCSD Motion Coordinated Shutdown
No
Transition the axes of a coordinate system to the ready state and clear the axis faults.
MCSR No Motion Coordinated Shutdown Reset
Start a transform that links two coordinate systems together.
MCT 1 Motion Coordinated Transform
No
Calculate the position of one coordinate system with respect to another coordinate system.
MCTP 2 Motion Calculate Transform Position
No
Define a Master/Slave relationship between a Master Axis and a Coordinate System.
MDCC Master Driven Coordinated Control
No
• Encoder hookup test • Marker test
Control multi-axis coordinated motion
1 2
Use this instruction only with 1756-L6x controllers. Use this instruction only with 1756-L6x controllers.
Rockwell Automation Publication MOTION-UM001H-EN-P - November 2018
79
Page 80
Chapter 3
Commission and tune
Motion Direct Command dialog box
Must be online to execute a Motion Direct Command. The content of the Motion Direct Command dialog box varies depending on the command.
In the Command list, type the mnemonic and the list advances to the closest match, or scroll the list to select a command. Select the desired command and its dialog box opens. Select Execute to verify the operands and initiates the current Motion Direct Command.
Motion Group Shutdown
Motion Group Shutdown is located to the left of the screen. This placement helps avoid accidentally invoking this command.
If Motion Group Shutdown is selected and successfully executed, a Result message appears in the results window below the dialog box. Motion Group Shutdown is an abrupt means to stop motion, so an additional message appears in 80
Rockwell Automation Publication MOTION-UM001H-EN-P - November 2018