Page 11
Chapter
1
What Are ControlLogix Digital I/O Modules?
Topic
Page
Available Features
11
I/O Modules in the ControlLogix System
12
Module Identification and Status Information
15
ControlLogix® digital I/O modules are input and output modules that provide On/Off detection and actuation. By using the producer/consumer network model, digital I/O modules can produce information when needed while providing additional system functions.
Available Features
This table lists several features available on ControlLogix digital I/O modules. Feature
Description
Removal and Insertion Under Power (RIUP) You can remove and insert modules and removable terminal blocks (RTB) while power is applied. Producer/consumer communication
This communication method is an intelligent data exchange between modules and other system devices in which each module produces data without first being polled.
System time stamp of data
A 64-bit system clock places a time stamp on the transfer of data between the module and its owner-controller.
Module-level fault reporting and field-side diagnostic detection
Fault and diagnostic detection capabilities to help you effectively and efficiently use your module and troubleshoot your application.
Agency Certification
Class 1, Division 2 agency certification for any application that requires approval.
Rockwell Automation Publication 1756-UM058I-EN-P - December 2017
11
Page 12
Chapter 1
What Are ControlLogix Digital I/O Modules?
I/O Modules in the ControlLogix System
ControlLogix modules mount in a ControlLogix chassis and require either a removable terminal block (RTB) or a Bulletin 1492 wiring interface module (IFM)(1) to connect all field-side wiring. Before you install and use your module, you must do the following: • Install and ground a 1756 chassis and power supply. To install these products, refer to the publications listed in Additional Resources on page 10. • Order and receive an RTB or IFM and its components for your application. IMPORTANT
RTBs and IFMs are not included with your module purchase. See page 112 for RTBs and page 237 for IFMs.
Table 1 - ControlLogix Digital I/O Modules Cat. No.
Description
Page
1756-IA8D
79…132V AC 8-point diagnostic input module
135
1756-IA16
74…132V AC 16-point input module
135
1756-IA16I
79…132V AC 16-point isolated input module
136
1756-IA32
74…132V AC 32-point input module
137
1756-IB16
10…31.2V DC 16-point input module
138
1756-IB16D
10…30V DC diagnostic input module
139
1756-IB16I
10…30V DC 16-point, isolated input module
140
1756-IB16IF
10…30V DC,16-point, isolated, fast peer control input module
141
1756-IB32
10…31.2V DC 32-point input module
142
1756-IC16
30…60V DC 16-point input module
143
1756-IG16
Transitor-transitor logic (TTL) input module
144
1756-IH16I
90…146V DC 16-point isolated input module
145
1756-IM16I
159…265V AC 16-point isolated input module
146
1756-IN16
10…30V AC 16-point input module
146
1756-IV16
10…30V DC 16-point sourcing current input module
147
1756-IV32
10…30V DC 32-point sourcing current input module
148
1756-OA8
74…265V AC 8-point output module
149
1756-OA8D
74…132V AC 8-point diagnostic output module
150
1756-OA8E
74…132V AC 8-point electronically-fused output module
151
1756-OA16
74... 265V AC 16-point output module
152
1756-OA16I
74…265V AC 16-point isolated output module
153
1756-OB8
10…30V DC 8-point output module
154
1756-OB8EI
10…30V DC 8-point electronically-fused, isolated output module
155
1756-OB8I
10…30V DC 8-point isolated output module
156
1756-OB16D
19.2…30V DC 16-point diagnostic output module
157
(1) The ControlLogix system has been agency certified using only the ControlLogix RTB catalog numbers 1756-TBCH, 1756-TBNH, 1756-TBSH, and 1756-TBS6H. Any application that requires agency certification of the ControlLogix system using other wiring termination methods may require application-specific approval by the certifying agency.
12
Rockwell Automation Publication 1756-UM058I-EN-P - December 2017
Page 13
What Are ControlLogix Digital I/O Modules?
Chapter 1
Table 1 - ControlLogix Digital I/O Modules (continued) Cat. No.
Description
Page
1756-OB16E
10…31.2V DC 16-point electronically-fused output module
158
1756-OB16I
10…30V DC 16-point isolated output module
161
1756-OB16IEF
10…30V DC,16-point, isolated, fast peer control output module
162
1756-OB16IEFS
10…30V DC, 16-point, isolated, fast, scheduled per point output module
163
1756-OB16IS
10…30V DC scheduled, isolated output module
164
1756-OB32
10…31.2V DC 32-point output module
165
1756-OC8
30…60V DC 8-point output module
166
1756-OG16
Transitor-transitor logic (TTL) output module
167
1756-OH81
90…146V DC 8-point isolated output module
168
1756-ON8
10…30V AC 8-point output module
169
1756-OV16E
10…30V DC 16-point electronically-fused, sinking current output module
170
1756-OV32E
10…30V DC 32-point electronically-fused, sinking current output module
171
1756-OW16I
10…265V, 5-150V DC 16-point isolated contact module
172
1756-OX8I
10…265V, 5-150V DC 8-point isolated contact module
173
Rockwell Automation Publication 1756-UM058I-EN-P - December 2017
13
Page 14
Chapter 1
What Are ControlLogix Digital I/O Modules?
Figure 1 - Parts Illustration
DC OUTPUT
3
ST 0 1 2 3 4 5 6 7 O K
5 Removable Terminal Block
2
4
1
6
40200-M
14
Item
Description
1
Backplane Connector - Interface for the ControlLogix system that connects the module to the backplane.
2
Top and bottom guides - Guides provide assistance in seating the RTB or IFM onto the module.
3
Status indicators - Indicators display the status of communication, module health, and input/ output devices. Indicators help in troubleshooting anomalies.
4
Connector pins - Input/output, power, and grounding connections are made to the module through these pins with the use of an RTB or IFM.
5
Locking tab - The locking tab anchors the RTB or IFM on the module, maintaining wiring connections.
6
Slots for keying - Mechanically keys the RTB to prevent making the wrong wire connections to your module.
Rockwell Automation Publication 1756-UM058I-EN-P - December 2017
Page 15
What Are ControlLogix Digital I/O Modules?
Module Identification and Status Information
Chapter 1
Each ControlLogix I/O module maintains specific identification information that separates it from all other modules. This information assists you in tracking all the components of your system. For example, you can track module identification information to know which modules are in any ControlLogix chassis at any time. While retrieving module identity, you can also retrieve module status. Item
Description
Product type
Module product type, such as digital I/O or analog I/O
Product code
Module catalog number
Major revision
Module major revision number
Minor revision
Module minor revision number
Status
Module status, including these items: • Controller ownership • Whether the module has been configured • Device-specific status, such as the following: – Self-test – Update in progress – Communications fault – Not owned (outputs in Program mode) – Internal fault (needs update) – Run mode – Program mode (outputs only) • Minor recoverable fault • Minor unrecoverable fault • Major recoverable fault • Major unrecoverable fault
Vendor
Module manufacturer vendor, such as Allen-Bradley
Serial number
Module serial number
Length of ASCII text string
Number of characters in module text string
ASCII text string
Module ASCII text string description
IMPORTANT
You must perform a WHO service to retrieve this information. For more information, refer to page 226.
Rockwell Automation Publication 1756-UM058I-EN-P - December 2017
15
Page 16
Chapter 1
What Are ControlLogix Digital I/O Modules?
Notes:
16
Rockwell Automation Publication 1756-UM058I-EN-P - December 2017
Page 17
Chapter
2
Digital I/O Operation in the ControlLogix System
Topic
Page
Ownership
18
1756-OB16IEF Redundant Owner
18
Internal Module Operation
18
Connections
21
Input Module Operation
23
Input Modules in a Local Chassis
24
Input Modules in a Remote Chassis
25
Output Module Operation
28
Output Modules in a Local Chassis
28
Output Modules in a Remote Chassis
29
Listen-only Mode
31
Multiple Owner-Controllers of Input Modules
31
Configuration Changes in an Input Module with Multiple Owners
32
I/O modules are the interface between controllers and field devices in a ControlLogix® system. Digital I/O modules transfer data to devices that require just one bit to be represented (0 or 1). For example, a switch is open or closed, or a light is on or off.
Rockwell Automation Publication 1756-UM058I-EN-P - December 2017
17
Page 18
Chapter 2
Digital I/O Operation in the ControlLogix System
Ownership
I/O modules in a ControlLogix system can be owned by a Logix5000™ controller. An owner-controller fulfills these functions: • Stores configuration data for every module that it owns • Sends I/O modules configuration data to define module behavior and begin module operation with the control system • Resides in a local or remote chassis in regard to the I/O module position Each ControlLogix I/O module must continuously maintain communication with its owner-controller to operate normally. Typically, each module in the system has only one owner-controller. Input modules can have more than one owner-controller. Output modules, however, are limited to a single owner-controller. For more information about using multiple owner-controllers, see Configuration Changes in an Input Module with Multiple Owners on page 32.
1756-OB16IEF Redundant Owner Redundant ownership lets a single controller use redundant adapters to communicate with a single output or lets two separate controllers coordinate to control the output. See Redundant Owners on page 102.
Internal Module Operation
ControlLogix I/O modules experience signal propagation delays that must be accounted for during operation. Some of these delays are user-configurable, and some are inherent to the module hardware. For example, there is a small delay, typically less than 1 ms, between when a signal is applied at the RTB of a ControlLogix input module and when a signal is sent to the system over the backplane. This time reflects a filter time of 0 ms for a DC input. This section offers an explanation of the time limitations with ControlLogix I/O modules.
18
Rockwell Automation Publication 1756-UM058I-EN-P - December 2017
Page 19
Digital I/O Operation in the ControlLogix System
Chapter 2
Input Modules As shown in the illustration, ControlLogix input modules receive a signal at the RTB and process it internally through hardware, filters, and an ASIC scan before sending a signal to the backplane via the requested packet interval (RPI) or at a Change of State (COS) occurrence. The RPI is a configured interval of time that determines when module data is sent to the controller.
Hardware Delay
42701
Filter Delay
Signal Applied at the RTB
ASIC Delay
Signal Sent to the Backplane
The table defines some of the delay factors that affect the signal propagation on an I/O module. Delay
Description
Hardware
How the module is configured and the variance between the type of modules affects how the signal is processed.
Filter
User configuration varies between modules, thus affecting the signal propagation.
ASIC
ASIC scan = 200 μs.
EXAMPLE
A typical delay time can be estimated despite the number of factors that can contribute. For example, if you are turning on a 1756-IB16 module at 24V DC in 25 °C (77 °F) conditions, the signal propagation delay is affected by these factors: • Hardware delay to energize the input (typically 290 μs on the 1756-IB16 module) • User-configurable filter time of 0, 1, or 2 ms • ASIC scan of 200 μs In the worst case scenario with a filter time of 0 ms, the 1756-IB16 module has a 490 μs signal propagation delay. These times are not guaranteed. For nominal and maximum delay times for each module, see the 1756 ControlLogix I/O Modules Specifications Technical Data, publication 1756-TD002.
Rockwell Automation Publication 1756-UM058I-EN-P - December 2017
19
Page 20
Chapter 2
Digital I/O Operation in the ControlLogix System
Output Modules ControlLogix output modules receive a signal from the controller and process it internally via hardware and an ASIC scan before sending a signal to the output device via the RTB.
ASIC Delay
Hardware Delay
Signal Received from Controller
Signal Sent from RTB Output Point
42702
The table defines some of the delay factors that affect the signal propagation on an I/O module. Delay
Description
Hardware
How the module is configured and the variance between the type of modules affects how the signal is processed.
ASIC
ASIC scan = 200 μs.
EXAMPLE
20
A typical delay time can be estimated despite the number of factors that can contribute. For example, if you are turning on a 1756-OB16E module at 24V DC in 25 °C (77 °F) conditions, the signal propagation delay is affected by these factors: • Hardware delay to energize the input (typically 70 μs on the 1756-OB16E module) • ASIC scan of 200 μs In the worst case scenario with a filter time of 0 ms, the 1756-OB16E module has a 270 μs signal propagation delay. These times are not guaranteed. See Chapter 8 for nominal and maximum delay times for each module.
Rockwell Automation Publication 1756-UM058I-EN-P - December 2017