Browse
(440) 299-7778
Menu
(440) 299-7778
One-year parts and labor warranty30-day money-back guaranteeContact

The text of a manual · part 2 of 27

ControlLogix Digital I/O Modules User Manual: ControlLogix Digital I/O Modules User Manual, pages 11 to 20

Pages 11 to 20 of 258, from ControlLogix Digital I/O Modules User Manual

The original document is the PDF (7.2 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

For the Allen-Bradley 1756-OB16E

Page 11

Chapter

1

What Are ControlLogix Digital I/O Modules?

Topic

Page

Available Features

11

I/O Modules in the ControlLogix System

12

Module Identification and Status Information

15

ControlLogix® digital I/O modules are input and output modules that provide On/Off detection and actuation. By using the producer/consumer network model, digital I/O modules can produce information when needed while providing additional system functions.

Available Features

This table lists several features available on ControlLogix digital I/O modules. Feature

Description

Removal and Insertion Under Power (RIUP) You can remove and insert modules and removable terminal blocks (RTB) while power is applied. Producer/consumer communication

This communication method is an intelligent data exchange between modules and other system devices in which each module produces data without first being polled.

System time stamp of data

A 64-bit system clock places a time stamp on the transfer of data between the module and its owner-controller.

Module-level fault reporting and field-side diagnostic detection

Fault and diagnostic detection capabilities to help you effectively and efficiently use your module and troubleshoot your application.

Agency Certification

Class 1, Division 2 agency certification for any application that requires approval.

Rockwell Automation Publication 1756-UM058I-EN-P - December 2017

11

Page 12

Chapter 1

What Are ControlLogix Digital I/O Modules?

I/O Modules in the ControlLogix System

ControlLogix modules mount in a ControlLogix chassis and require either a removable terminal block (RTB) or a Bulletin 1492 wiring interface module (IFM)(1) to connect all field-side wiring. Before you install and use your module, you must do the following: • Install and ground a 1756 chassis and power supply. To install these products, refer to the publications listed in Additional Resources on page 10. • Order and receive an RTB or IFM and its components for your application. IMPORTANT

RTBs and IFMs are not included with your module purchase. See page 112 for RTBs and page 237 for IFMs.

Table 1 - ControlLogix Digital I/O Modules Cat. No.

Description

Page

1756-IA8D

79…132V AC 8-point diagnostic input module

135

1756-IA16

74…132V AC 16-point input module

135

1756-IA16I

79…132V AC 16-point isolated input module

136

1756-IA32

74…132V AC 32-point input module

137

1756-IB16

10…31.2V DC 16-point input module

138

1756-IB16D

10…30V DC diagnostic input module

139

1756-IB16I

10…30V DC 16-point, isolated input module

140

1756-IB16IF

10…30V DC,16-point, isolated, fast peer control input module

141

1756-IB32

10…31.2V DC 32-point input module

142

1756-IC16

30…60V DC 16-point input module

143

1756-IG16

Transitor-transitor logic (TTL) input module

144

1756-IH16I

90…146V DC 16-point isolated input module

145

1756-IM16I

159…265V AC 16-point isolated input module

146

1756-IN16

10…30V AC 16-point input module

146

1756-IV16

10…30V DC 16-point sourcing current input module

147

1756-IV32

10…30V DC 32-point sourcing current input module

148

1756-OA8

74…265V AC 8-point output module

149

1756-OA8D

74…132V AC 8-point diagnostic output module

150

1756-OA8E

74…132V AC 8-point electronically-fused output module

151

1756-OA16

74... 265V AC 16-point output module

152

1756-OA16I

74…265V AC 16-point isolated output module

153

1756-OB8

10…30V DC 8-point output module

154

1756-OB8EI

10…30V DC 8-point electronically-fused, isolated output module

155

1756-OB8I

10…30V DC 8-point isolated output module

156

1756-OB16D

19.2…30V DC 16-point diagnostic output module

157

(1) The ControlLogix system has been agency certified using only the ControlLogix RTB catalog numbers 1756-TBCH, 1756-TBNH, 1756-TBSH, and 1756-TBS6H. Any application that requires agency certification of the ControlLogix system using other wiring termination methods may require application-specific approval by the certifying agency.

12

Rockwell Automation Publication 1756-UM058I-EN-P - December 2017

Page 13

What Are ControlLogix Digital I/O Modules?

Chapter 1

Table 1 - ControlLogix Digital I/O Modules (continued) Cat. No.

Description

Page

1756-OB16E

10…31.2V DC 16-point electronically-fused output module

158

1756-OB16I

10…30V DC 16-point isolated output module

161

1756-OB16IEF

10…30V DC,16-point, isolated, fast peer control output module

162

1756-OB16IEFS

10…30V DC, 16-point, isolated, fast, scheduled per point output module

163

1756-OB16IS

10…30V DC scheduled, isolated output module

164

1756-OB32

10…31.2V DC 32-point output module

165

1756-OC8

30…60V DC 8-point output module

166

1756-OG16

Transitor-transitor logic (TTL) output module

167

1756-OH81

90…146V DC 8-point isolated output module

168

1756-ON8

10…30V AC 8-point output module

169

1756-OV16E

10…30V DC 16-point electronically-fused, sinking current output module

170

1756-OV32E

10…30V DC 32-point electronically-fused, sinking current output module

171

1756-OW16I

10…265V, 5-150V DC 16-point isolated contact module

172

1756-OX8I

10…265V, 5-150V DC 8-point isolated contact module

173

Rockwell Automation Publication 1756-UM058I-EN-P - December 2017

13

Page 14

Chapter 1

What Are ControlLogix Digital I/O Modules?

Figure 1 - Parts Illustration

DC OUTPUT

3

ST 0 1 2 3 4 5 6 7 O K

5 Removable Terminal Block

2

4

1

6

40200-M

14

Item

Description

1

Backplane Connector - Interface for the ControlLogix system that connects the module to the backplane.

2

Top and bottom guides - Guides provide assistance in seating the RTB or IFM onto the module.

3

Status indicators - Indicators display the status of communication, module health, and input/ output devices. Indicators help in troubleshooting anomalies.

4

Connector pins - Input/output, power, and grounding connections are made to the module through these pins with the use of an RTB or IFM.

5

Locking tab - The locking tab anchors the RTB or IFM on the module, maintaining wiring connections.

6

Slots for keying - Mechanically keys the RTB to prevent making the wrong wire connections to your module.

Rockwell Automation Publication 1756-UM058I-EN-P - December 2017

Page 15

What Are ControlLogix Digital I/O Modules?

Module Identification and Status Information

Chapter 1

Each ControlLogix I/O module maintains specific identification information that separates it from all other modules. This information assists you in tracking all the components of your system. For example, you can track module identification information to know which modules are in any ControlLogix chassis at any time. While retrieving module identity, you can also retrieve module status. Item

Description

Product type

Module product type, such as digital I/O or analog I/O

Product code

Module catalog number

Major revision

Module major revision number

Minor revision

Module minor revision number

Status

Module status, including these items: • Controller ownership • Whether the module has been configured • Device-specific status, such as the following: – Self-test – Update in progress – Communications fault – Not owned (outputs in Program mode) – Internal fault (needs update) – Run mode – Program mode (outputs only) • Minor recoverable fault • Minor unrecoverable fault • Major recoverable fault • Major unrecoverable fault

Vendor

Module manufacturer vendor, such as Allen-Bradley

Serial number

Module serial number

Length of ASCII text string

Number of characters in module text string

ASCII text string

Module ASCII text string description

IMPORTANT

You must perform a WHO service to retrieve this information. For more information, refer to page 226.

Rockwell Automation Publication 1756-UM058I-EN-P - December 2017

15

Page 16

Chapter 1

What Are ControlLogix Digital I/O Modules?

Notes:

16

Rockwell Automation Publication 1756-UM058I-EN-P - December 2017

Page 17

Chapter

2

Digital I/O Operation in the ControlLogix System

Topic

Page

Ownership

18

1756-OB16IEF Redundant Owner

18

Internal Module Operation

18

Connections

21

Input Module Operation

23

Input Modules in a Local Chassis

24

Input Modules in a Remote Chassis

25

Output Module Operation

28

Output Modules in a Local Chassis

28

Output Modules in a Remote Chassis

29

Listen-only Mode

31

Multiple Owner-Controllers of Input Modules

31

Configuration Changes in an Input Module with Multiple Owners

32

I/O modules are the interface between controllers and field devices in a ControlLogix® system. Digital I/O modules transfer data to devices that require just one bit to be represented (0 or 1). For example, a switch is open or closed, or a light is on or off.

Rockwell Automation Publication 1756-UM058I-EN-P - December 2017

17

Page 18

Chapter 2

Digital I/O Operation in the ControlLogix System

Ownership

I/O modules in a ControlLogix system can be owned by a Logix5000™ controller. An owner-controller fulfills these functions: • Stores configuration data for every module that it owns • Sends I/O modules configuration data to define module behavior and begin module operation with the control system • Resides in a local or remote chassis in regard to the I/O module position Each ControlLogix I/O module must continuously maintain communication with its owner-controller to operate normally. Typically, each module in the system has only one owner-controller. Input modules can have more than one owner-controller. Output modules, however, are limited to a single owner-controller. For more information about using multiple owner-controllers, see Configuration Changes in an Input Module with Multiple Owners on page 32.

1756-OB16IEF Redundant Owner Redundant ownership lets a single controller use redundant adapters to communicate with a single output or lets two separate controllers coordinate to control the output. See Redundant Owners on page 102.

Internal Module Operation

ControlLogix I/O modules experience signal propagation delays that must be accounted for during operation. Some of these delays are user-configurable, and some are inherent to the module hardware. For example, there is a small delay, typically less than 1 ms, between when a signal is applied at the RTB of a ControlLogix input module and when a signal is sent to the system over the backplane. This time reflects a filter time of 0 ms for a DC input. This section offers an explanation of the time limitations with ControlLogix I/O modules.

18

Rockwell Automation Publication 1756-UM058I-EN-P - December 2017

Page 19

Digital I/O Operation in the ControlLogix System

Chapter 2

Input Modules As shown in the illustration, ControlLogix input modules receive a signal at the RTB and process it internally through hardware, filters, and an ASIC scan before sending a signal to the backplane via the requested packet interval (RPI) or at a Change of State (COS) occurrence. The RPI is a configured interval of time that determines when module data is sent to the controller.

Hardware Delay

42701

Filter Delay

Signal Applied at the RTB

ASIC Delay

Signal Sent to the Backplane

The table defines some of the delay factors that affect the signal propagation on an I/O module. Delay

Description

Hardware

How the module is configured and the variance between the type of modules affects how the signal is processed.

Filter

User configuration varies between modules, thus affecting the signal propagation.

ASIC

ASIC scan = 200 μs.

EXAMPLE

A typical delay time can be estimated despite the number of factors that can contribute. For example, if you are turning on a 1756-IB16 module at 24V DC in 25 °C (77 °F) conditions, the signal propagation delay is affected by these factors: • Hardware delay to energize the input (typically 290 μs on the 1756-IB16 module) • User-configurable filter time of 0, 1, or 2 ms • ASIC scan of 200 μs In the worst case scenario with a filter time of 0 ms, the 1756-IB16 module has a 490 μs signal propagation delay. These times are not guaranteed. For nominal and maximum delay times for each module, see the 1756 ControlLogix I/O Modules Specifications Technical Data, publication 1756-TD002.

Rockwell Automation Publication 1756-UM058I-EN-P - December 2017

19

Page 20

Chapter 2

Digital I/O Operation in the ControlLogix System

Output Modules ControlLogix output modules receive a signal from the controller and process it internally via hardware and an ASIC scan before sending a signal to the output device via the RTB.

ASIC Delay

Hardware Delay

Signal Received from Controller

Signal Sent from RTB Output Point

42702

The table defines some of the delay factors that affect the signal propagation on an I/O module. Delay

Description

Hardware

How the module is configured and the variance between the type of modules affects how the signal is processed.

ASIC

ASIC scan = 200 μs.

EXAMPLE

20

A typical delay time can be estimated despite the number of factors that can contribute. For example, if you are turning on a 1756-OB16E module at 24V DC in 25 °C (77 °F) conditions, the signal propagation delay is affected by these factors: • Hardware delay to energize the input (typically 70 μs on the 1756-OB16E module) • ASIC scan of 200 μs In the worst case scenario with a filter time of 0 ms, the 1756-OB16E module has a 270 μs signal propagation delay. These times are not guaranteed. See Chapter 8 for nominal and maximum delay times for each module.

Rockwell Automation Publication 1756-UM058I-EN-P - December 2017