Browse
(440) 299-7778
Menu
(440) 299-7778
One-year parts and labor warranty30-day money-back guaranteeContact

The text of a manual · part 2 of 4

CompactLogix System Selection Guide, pages 11 to 20

Pages 11 to 20 of 40

The original document is the PDF (7.0 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

For the Allen-Bradley 1769-IQ6X0W4

Page 11

Select a CompactLogix System

CompactLogix 5370 L1 Controllers with Embedded I/O The CompactLogix 5370 L1 controller comes with: • A built-in, 24V DC isolated(1) Power Supply module.(2) • Dual EtherNet/IP ports for linear and ring topologies. • USB port for firmware updates and programming. • Embedded digital I/O (16 DC inputs, 16 DC outputs). • Support for 1734 POINT I/O. Characteristic

1769-L16ER-BB1B

1769-L18ER-BB1B

1769-L18ERM-BB1B

1769-L19ER-BB1B

Available user memory

384 KB

512 KB

512 KB

1 MB

Memory card

• 1784-SD1 (1 GB), shipped with controller • 1784-SD2 (2 GB)

Communication ports

• 2 EtherNet/IP • 1 USB

Embedded I/O

• 16 sinking 24V DC digital input points • 16 sourcing 24V DC digital output points

EtherNet/IP connections

• 256 EtherNet/IP • 120 TCP

• 256 EtherNet/IP • 120 TCP

EtherNet/IP nodes in one Studio 5000 Logix Designer® application, max

4

8

Integrated motion on an EtherNet/IP network, Module expansion capacity

6 POINT I/O modules

Battery

None

Embedded power supply

10…28.8V DC 24V DC nominal

Programming software support

• Version 20 - For controllers that use firmware revision 20. • Version 21 or later - For controllers that use firmware revision 21 or later.

• 256 EtherNet/IP • 120 TCP

Supports up to 2 axes 8 POINT I/O modules, 8 POINT I/O modules

Version 28 or later - For controllers that use firmware revision 28 or later.

(1) Only series B Power Supply modules are isolated. Series A Power supply modules are non-isolated. (2) For more information on how to connect a 24V DC power source to the 24V DC nonisolated power supply of the CompactLogix 5370 L1 controller, see the CompactLogix 5370 Controllers User Manual, publication 1769-UM021.

Rockwell Automation Publication 1769-SG001S-EN-P - December 2016

11

Page 12

Select a CompactLogix System

CompactLogix 5370 L2 Controllers with Embedded I/O The CompactLogix 5370 L2 controller comes with: • A built-in, 24V DC Power Supply module. • Dual EtherNet/IP ports for linear and ring topologies. • USB port for firmware updates and programming. • A combination of embedded digital, analog, and high-speed counter I/O. • A 1769-ECR right-end cap. • Support for 1769 Compact I/O. Characteristic

1769-L24ER-QB1B

1769-L24ER-QBFC1B

1769-L27ERM-QBFC1B

Available user memory

0.75 MB

0.75 MB

1 MB

Memory card

• 1784-SD1 (1 GB), shipped with controller • 1784-SD2 (2 GB)

Communication ports

• 2 EtherNet/IP • 1 USB

Embedded I/O

• 16 sinking/sourcing 24V DC digital input points • 16 sourcing 24V DC digital output points

• • • • •

EtherNet/IP connections

• 256 EtherNet/IP • 120 TCP

• 256 EtherNet/IP • 120 TCP

EtherNet/IP nodes in one Logix Designer application, max

8

Integrated motion on an EtherNet/IP network, Module expansion capacity

4 1769 modules

Battery

None

Embedded power supply

24V DC

Programming software support

• Version 20 - For controllers that use firmware revision 20. • Version 21 or later - For controllers that use firmware revision 21 or later.

16 sinking/sourcing 24V DC digital input points 16 sourcing 24V DC digital output points 4 universal analog input points 2 analog output points 4 high-speed counters • 256 EtherNet/IP • 120 TCP 16, Supports up to 4 axes

These controllers replace previous catalog numbers. New Controller

Replaces Previous Controller

Differences

1769-L24ER-QBFC1B

1769-L23-QBFC1B 1769-L23E-QBFC1B

1769-L24ER-QB1B

1769-L23E-QB1B

1769-L27ERM-QBFC1B

1769-L23E-QBFC1B

• • • • • •

12

Rockwell Automation Publication 1769-SG001S-EN-P - December 2016

Additional memory Integrated motion on EtherNet/IP support (1769-L27ERM-QBFC1B) USB port instead of RS-232 port Dual-port EtherNet/IP support SD card support addition Support for additional expansion I/O modules

Page 13

Select a CompactLogix System

CompactLogix 5370 L3 Controllers In a CompactLogix 5370 L3 controller system, the 1769 I/O modules can be placed to the left and the right of the power supply. As many as eight modules can be placed on each side of the power supply. The CompactLogix 5370 L3 controller comes with: • Dual EtherNet/IP ports for linear and ring topologies. • USB port for firmware updates and programming. • Support for 1769 Compact I/O. Use the 1769-L30ER-NSE controller for mining applications. You can deplete the residual stored energy of the 1769-L30ER-NSE controller to 200 µJ or less before you transport it into or out of a mine. The 1769-L30ER-NSE controller does not maintain the real-time clock on power cycle. Characteristic

1769-L30ER

1769-L30ERM

1769-L30ER-NSE

1769-L33ER

1769-L33ERM

1769-L36ERM

Available user memory

1 MB

1 MB

1 MB No capacitor

2 MB

2 MB

3 MB

Memory card

1784-SD1 (1 GB), shipped with controller 1784-SD2 (2 GB)

Communication ports

• 2 EtherNet/IP • 1 USB

EtherNet/IP connections

• 256 EtherNet/IP • 120 TCP

• 256 EtherNet/IP • 120 TCP

• 256 EtherNet/IP • 120 TCP

• 256 EtherNet/IP • 120 TCP

• 256 EtherNet/IP • 120 TCP

EtherNet/IP nodes in one Logix Designer application, max

16

Integrated motion on an EtherNet/IP network, Module expansion capacity

8 1769 modules 1 bank of modules

Battery

None

Power supply distance rating

4 modules

Programming software support

• Version 20 - For controllers that use firmware revision 20.

• 256 EtherNet/IP • 120 TCP

32 Supports up to 4 axes, - 48 Supports up to 8 axes

Supports up to 16 axes

16 1769 modules 2 banks of modules

30 1769 modules 3 banks of modules

4 modules

4 modules

• Version 21 or later - For controllers that use firmware revision 21 or later.

These controllers replace previous catalog numbers. New Controller(1)

Replaces Previous Controller

Differences

1769-L30ER 1769-L30ERM 1769-L30ER-NSE

1769-L31 1769-L32C(2) 1769-L32E

1769-L33ER 1769-L33ERM

1769-L35CR(2) 1769-L35E

• Additional memory • Integrated motion on EtherNet/IP support (1769-L30ERM, 1769-L33ERM, 1769-L36ERM) • USB port instead of RS-232 port • Dual-port EtherNet/IP support • SD card instead of CompactFlash card

1769-L36ERM

Any previous 1769-L3x controller

(1) IMPORTANT: Typically, you can use any of the new controllers that are listed in each row as replacements for any of the previous controllers that are listed in the corresponding cell to the right. For example, you can replace a 1769-L32E with a 1769-L30ER, 1769-L30ERM, or 1769-L30ER-NSE controller. In some rare cases, system configuration helps to prevent controller replacement as shown in the previous table. For example, if your system uses a 1769-L32E controller with 12 expansion modules, you cannot replace that controller with a 1769-L30ER, 1769-L30ERM, or 1769-L30ER-NSE controller. Those controllers support no more than 8 expansion modules. You must replace the 1769-L32E controller with a 1769-L33ER, 1769-L33ERM, or 1769-L36ERM controller. We recommend that before you upgrade your controllers, consider your application requirements to verify that the replacements that are listed previously apply. (2) Requires converting from ControlNet connections to EtherNet/IP connections.

Rockwell Automation Publication 1769-SG001S-EN-P - December 2016

13

Page 14

Select a CompactLogix System

CompactLogix 5380 Controllers In a CompactLogix 5380 controller system, 5069 Compact I/O modules are installed to the right of the controller as local I/O modules. As many as 31 modules can be installed in the system. The CompactLogix 5380 controllers come with: • Dual embedded EtherNet/IP ports for use in star, linear, and DLR EtherNet/IP network topologies • USB port for firmware updates and programming • Support for Dual-IP mode. Energy Depletion characteristics for the 5069-L310ER-NSE controller. The residual stored energy of the 5069-L310ER-NSE controller depletes to 20 µJ or less in two minutes with 0…32V DC of SA power applied. The 5069-L310ER-NSE controller does not maintain the real-time clock on power cycle. IMPORTANT

You can use the 5069-L310ER-NSE controller with DC Sensor Actuator (SA) power only.

Characteristic

5069-L306ER, 5069-L306ERM

5069-L310ER, 5069-L320ER, 5069-L310ER-NSE, 5069-L320ERM 5069-L310ERM

5069-L330ER, 5069-L330ERM

5069-L340ER, 5069-L340ERM

5069-L350ERM

5069-L380ERM

5069-L3100ERM

Available user memory

0.6 MB

1 MB

3 MB

4 MB

5 MB

8 MB

10 MB

Memory card

• 1784-SD1 (1 GB) • 1784-SD2 (2 GB), ships with controller

Communication ports

• 2 - EtherNet/IP ports, 10 Mbps/100 Mbps/1 Gbps • 1 port USB client 50

55

60

70

80

EtherNet/IP nodes in 16 one Logix Designer application, max

2 MB

24

40

Integrated motion on an EtherNet/IP network

As many as 2 axes As many as 4 axes (5069-L306ERM (5069-L310ERM) only)

As many as 8 axes As many as 16 axes As many as 20 axes As many as 24 axes As many as 28 axes As many as 32 axes (5069-L320ERM) (5069-L330ERM) (5069-L340ERM)

Local I/O modules, max

8

16

Battery

None

Power supply terminals (sold separately)

• 5069-RTB64-SCREW kit - Includes RTB catalog numbers 5069-RTB6-SCREW and 5069-RTB4-SCREW • 5069-RTB64-SPRING - Includes RTB catalog numbers 5069-RTB6-SPRING and 5069-RTB4-SPRING

Programming software support

• Version 28 or later - 5069-L320ER, 5069-L340ERM only • Version 29 or later - 5069-L306ER, 5069-L306ERM, 5069-L310ER, 5069-L310ER-NSE, 5069-L310ERM, 5069-L320ERM, 5069-L330ER, 5069-L330ERM, 5069-L340ER • Version 30 or later - 5069-L350ERM, 5069-L380ERM, 5069-L3100ERM

31(1)

(1) When you use a 5069-L330ER or 5069-L330ERM controller with the Logix Designer application, version 29.00.00, the application limits the number of local I/O modules in the project to 16. For more information, see the Rockwell Automation® Knowledgebase article #942580, ‘5380 CompactLogix controllers limited to 16 local 5069 modules in V29 of Studio 5000.’ The document is available at http:// www.rockwellautomation.com/knowledgebase. With the Logix Designer application, version 30.00.00 or later, the controller supports as many as 31 local I/O modules.

14

Rockwell Automation Publication 1769-SG001S-EN-P - December 2016

Page 15

Select a CompactLogix System

Compact GuardLogix 5370 Controllers In a Compact GuardLogix 5370 controller system, the 1769 I/O modules can be placed to the left and the right of the power supply. As many as eight modules can be placed on each side of the power supply. The CompactLogix 5370 L3S controller comes with: • Dual EtherNet/IP ports for ring and linear topologies. • USB port for firmware updates and programming. • Safety control to achieve SIL 3/PLe according to ISO 13849. • Support for1769 Compact I/O. Characteristic

1769-L30ERMS

1769-L33ERMS

1769-L36ERMS

Available user memory

• 1 MB (standard) • 0.5 MB (safety)

• 2 MB (standard) • 1 MB (safety)

• 3 MB (standard) • 1.5 MB (safety)

Memory card

• 1784-SD1 (1 GB), shipped with controller • 1784-SD2 (2 GB)

Communication ports

• 2 EtherNet/IP • 1 USB

EtherNet/IP connections

• 256 EtherNet/IP • 120 TCP

EtherNet/IP nodes in one Logix Designer application, max

16

32

48

Integrated motion on an EtherNet/IP network

Supports up to 4 axes

Supports up to 8 axes

Supports up to 16 axes

Module expansion capacity

8 1769 modules 1 bank of modules

16 1769 modules 2 banks of modules

30 1769 modules 3 banks of modules

Battery

None

Power supply distance rating

4 modules

Programming software support

Version 28 or later - For controllers that use firmware revision 28 or later.

Rockwell Automation Publication 1769-SG001S-EN-P - December 2016

15

Page 16

Select a CompactLogix System

Armor CompactLogix and Armor Compact GuardLogix Controllers You can connect 1732 ArmorBlock or 1738 ArmorPoint I/O modules to the controller via EtherNet/IP in an Armor CompactLogix or Armor Compact GuardLogix controller system.The controller comes with: • An IP67-rated enclosure • A built-in, 24V DC Power Supply module • An SD card slot • Connection to On-Machine I/O • Dual EtherNet/IP ports for ring topologies • USB port for firmware updates and programming • Safety control to achieve SIL 3/PLe according to ISO 13849 • Support for1769 Compact I/O via EtherNet/IP Characteristic

1769-L33ERMO

1769-L36ERMO

Available user memory

2 MB

3 MB

Memory card

• 1784-SD1 (1 GB), shipped with controller • 1784-SD2 (2 GB)

Communication ports

• 2 EtherNet/IP • 1 USB

EtherNet/IP connections

• 256 EtherNet/IP • 120 TCP

EtherNet/IP nodes in one Logix Designer application, max

32

48

Integrated motion on an EtherNet/IP network

Supports up to 8 axes

Supports up to 16 axes

Programming software support

Version 28 or later - For controllers that use firmware revision 28 or later.

16

1769-L37ERMO

64

1769-L33ERMOS

1769-L36ERMOS

• 2 MB (standard) • 1 MB (safety)

• 3 MB (standard) • 1.5 MB (safety)

32

48

Supports up to 8 axes

Supports up to 16 axes

Rockwell Automation Publication 1769-SG001S-EN-P - December 2016

1769-L37ERMOS

64

Page 17

Select a CompactLogix System

Controller Memory Use IMPORTANT This section does not apply to CompactLogix 5380 controllers. These equations provide an estimate of the memory that is needed for a CompactLogix controller. These numbers are rough estimates. Controller Tasks

_____ * 4000

=

_____ bytes (minimum 1 task)

Digital I/O points

_____ * 400

=

_____ bytes

_____ * 2600

=

_____ bytes

_____ * 7400

=

_____ bytes

Other communication modules

_____ * 2000

=

_____ bytes

Motion axes

_____ * 8000

=

_____ bytes

FactoryTalk® alarm instruction

_____ * 1000

=

_____ bytes (per alarm)

FactoryTalk subscriber

_____ * 10000

=

_____ bytes

Analog I/O points (1)

DeviceNet modules

(2)

(1) The first DeviceNet module is 7400 bytes. Additional DeviceNet modules are 5800 bytes each. (2) Count the communication modules in the system, not just those modules in the local chassis. This total includes device connection modules, adapters, and ports on PanelView terminals.

Reserve 20…30% of the controller memory for future expansion.(1)

(1) This requirement does not apply to CompactLogix 5380 controllers.

Rockwell Automation Publication 1769-SG001S-EN-P - December 2016

17

Page 18

Select a CompactLogix System

CompactLogix Communication Options You can configure your system for information exchange between a range of devices and computing platforms and operating systems. Select a CompactLogix controller with integrated communication or the appropriate communication module. For detailed specifications, see: • CompactLogix Controllers Specifications Technical Data, publication 1769-TD005. • CompactLogix Communication Modules Specifications Technical Data, publication 1769-TD007. • CompactLogix 5380 Controllers Specifications Technical Data, publication 5069-TD002

EtherNet/IP Communication Options The Ethernet Industrial network protocol (EtherNet/IP) is an open industrial-networking standard that supports real time I/O messaging and message exchange. The EtherNet/IP network uses off-the-shelf Ethernet communication chips and physical media. Dual-port EtherNet/IP support embeds switch technology directly in the controller to so the controller can operate on star, linear, or ring EtherNet/IP topologies. CompactLogix Controller EtherNet/IP Communication Options Cat. No.

Description

Communication Rate

Logix Resources(2)

TCP/IP Connections

1769-L16ER-BB1B,

CompactLogix 5370 L1 controller with embedded dual EtherNet/IP ports, POINT I/O form factor

10/100 Mbps

4 nodes 256 EtherNet/IP connections

120

1769-L18ER-BB1B, 1769-L18ERM-BB1B

8 nodes 256 EtherNet/IP connections

1769-L19ER-BB1B 1769-L24ER-BB1B, 1769-L24ER-QBFC1B

CompactLogix 5370 L2 controller with embedded dual EtherNet/IP ports, Compact I/O form factor

1769-L27ERM-QBFC1B 1769-L30ER, 1769-L30ERM, 1769-L30ERMS

CompactLogix 5370 L3 controller with embedded dual EtherNet/IP ports

10/100 Mbps

8 nodes 256 EtherNet/IP connections

10/100 Mbps

16 nodes 256 EtherNet/IP connections

10/100 Mbps

16 nodes 256 EtherNet/IP connections

1769-L33ER, 1769-L33ERM, 1769-L33ERMO, 1769-L33ERMOS, 1769-L33ERMS

32 nodes 256 EtherNet/IP connections

1769-L36ERM, 1769-L33ERMO, 1769-L36ERMOS, 1769-L36ERMS

48 nodes 256 EtherNet/IP connections

1769-L37ERMO, 1769-L37ERMOS

64 nodes 256 EtherNet/IP connections

18

Rockwell Automation Publication 1769-SG001S-EN-P - December 2016

120

120

Page 19

Select a CompactLogix System

CompactLogix Controller EtherNet/IP Communication Options Cat. No.

Description

Communication Rate

5069-L306ER, 5069-L306ERM CompactLogix 5380 controller with embedded dual EtherNet/IP ports 10/100 Mbps, 1 Gbps

(1)

Logix Resources(2)

TCP/IP Connections

16, 5069-L310ER, 5069-L310ERNSE, 5069-L310ERM

24

5069-L320ER, 5069-L320ERM

40

5069-L330ER, 5069-L330ERM

50

5069-L340ER, 5069-L340ERM

55

5069-L350ERM

60

5069-L380ERM

70

5069-L3100ERM

80

(1) Network performance in a CompactLogix 5380 system is optimal if the 1 Gbps network communication rate is used. However, many Ethernet devices do not support the 1 Gbps network communication rate. You must consider how the different maximum network communication rates impact your CompactLogix 5380 control system when you design the system. (2) The number of nodes that are listed for CompactLogix 5370 and CompactLogix 5380 controllers represents the maximum number of EtherNet/IP nodes you can include in a controller project for those controllers. For example, in a controller project that uses a 1769-L18ERM-BB1B controller, you can add as many as eight EtherNet/IP nodes to the project.

CompactLogix 5380 Controllers EtherNet/IP Modes The CompactLogix 5380 controllers are the first Logix controllers to offer multiple EtherNet/IP modes. With CompactLogix 5380 controller firmware revision 29.011 or later, you can use Dual-IP mode or Linear/DLR mode.

Dual-IP Mode Dual-IP mode lets you configure the controller embedded Ethernet ports to connect to separate EtherNet/IP networks, that is, an enterprise-level network and a device-level network. In this mode, each port requires its own network configurations that include some restrictions. For example, when you set IP addresses in Dual-IP mode, you cannot overlap IP addresses between the ports. CompactLogix 5380 Controller 5069 Compact I/O Modules Enterprise-level Network PanelView Plus 7 Terminal F1

F9

F2

F10

F3

F11

F4

F12

F5

F13

F6

F14

F7

F15

F8

F16

Device-level Network Stratix 5700 Switch

PowerFlex 527 Drive 527

Rockwell Automation Publication 1769-SG001S-EN-P - December 2016

5069-AEN2TR Adapter 5069 Compact I/O Modules

19

Page 20

Select a CompactLogix System

Linear/DLR Mode When CompactLogix 5380 controllers operate in Linear/DLR mode, they connect to only one network. That is, there is only one network configuration. When used in Linear/DLR mode, CompactLogix 5380 controllers can connect to any EtherNet/IP network topology–linear, DLR, or star. CompactLogix 5380 Controller 5069 Compact I/O Modules

PanelView Plus 7 Terminal

F1

F9

F2

F10

F3

F11

F4

F12

F5

F13

F6

F14

F7

F15

F8

F16

Device-level Network

527

5069-AEN2TR Adapter 5069 Compact I/O Modules

PowerFlex 527 Drive

For more information on EtherNet/IP modes with a CompactLogix 5380 controller, see the following: • CompactLogix 5380 Controllers User Manual, publication 5069-UM001 • CompactLogix 5380 Controllers Specifications Technical Data, publication 5069-TD002

20

Rockwell Automation Publication 1769-SG001S-EN-P - December 2016