Page 11
Select a CompactLogix System
CompactLogix 5370 L1 Controllers with Embedded I/O The CompactLogix 5370 L1 controller comes with: • A built-in, 24V DC isolated(1) Power Supply module.(2) • Dual EtherNet/IP ports for linear and ring topologies. • USB port for firmware updates and programming. • Embedded digital I/O (16 DC inputs, 16 DC outputs). • Support for 1734 POINT I/O. Characteristic
1769-L16ER-BB1B
1769-L18ER-BB1B
1769-L18ERM-BB1B
1769-L19ER-BB1B
Available user memory
384 KB
512 KB
512 KB
1 MB
Memory card
• 1784-SD1 (1 GB), shipped with controller • 1784-SD2 (2 GB)
Communication ports
• 2 EtherNet/IP • 1 USB
Embedded I/O
• 16 sinking 24V DC digital input points • 16 sourcing 24V DC digital output points
EtherNet/IP connections
• 256 EtherNet/IP • 120 TCP
• 256 EtherNet/IP • 120 TCP
EtherNet/IP nodes in one Studio 5000 Logix Designer® application, max
4
8
Integrated motion on an EtherNet/IP network, Module expansion capacity
6 POINT I/O modules
Battery
None
Embedded power supply
10…28.8V DC 24V DC nominal
Programming software support
• Version 20 - For controllers that use firmware revision 20. • Version 21 or later - For controllers that use firmware revision 21 or later.
• 256 EtherNet/IP • 120 TCP
Supports up to 2 axes 8 POINT I/O modules, 8 POINT I/O modules
Version 28 or later - For controllers that use firmware revision 28 or later.
(1) Only series B Power Supply modules are isolated. Series A Power supply modules are non-isolated. (2) For more information on how to connect a 24V DC power source to the 24V DC nonisolated power supply of the CompactLogix 5370 L1 controller, see the CompactLogix 5370 Controllers User Manual, publication 1769-UM021.
Rockwell Automation Publication 1769-SG001S-EN-P - December 2016
11
Page 12
Select a CompactLogix System
CompactLogix 5370 L2 Controllers with Embedded I/O The CompactLogix 5370 L2 controller comes with: • A built-in, 24V DC Power Supply module. • Dual EtherNet/IP ports for linear and ring topologies. • USB port for firmware updates and programming. • A combination of embedded digital, analog, and high-speed counter I/O. • A 1769-ECR right-end cap. • Support for 1769 Compact I/O. Characteristic
1769-L24ER-QB1B
1769-L24ER-QBFC1B
1769-L27ERM-QBFC1B
Available user memory
0.75 MB
0.75 MB
1 MB
Memory card
• 1784-SD1 (1 GB), shipped with controller • 1784-SD2 (2 GB)
Communication ports
• 2 EtherNet/IP • 1 USB
Embedded I/O
• 16 sinking/sourcing 24V DC digital input points • 16 sourcing 24V DC digital output points
• • • • •
EtherNet/IP connections
• 256 EtherNet/IP • 120 TCP
• 256 EtherNet/IP • 120 TCP
EtherNet/IP nodes in one Logix Designer application, max
8
Integrated motion on an EtherNet/IP network, Module expansion capacity
4 1769 modules
Battery
None
Embedded power supply
24V DC
Programming software support
• Version 20 - For controllers that use firmware revision 20. • Version 21 or later - For controllers that use firmware revision 21 or later.
16 sinking/sourcing 24V DC digital input points 16 sourcing 24V DC digital output points 4 universal analog input points 2 analog output points 4 high-speed counters • 256 EtherNet/IP • 120 TCP 16, Supports up to 4 axes
These controllers replace previous catalog numbers. New Controller
Replaces Previous Controller
Differences
1769-L24ER-QBFC1B
1769-L23-QBFC1B 1769-L23E-QBFC1B
1769-L24ER-QB1B
1769-L23E-QB1B
1769-L27ERM-QBFC1B
1769-L23E-QBFC1B
• • • • • •
12
Rockwell Automation Publication 1769-SG001S-EN-P - December 2016
Additional memory Integrated motion on EtherNet/IP support (1769-L27ERM-QBFC1B) USB port instead of RS-232 port Dual-port EtherNet/IP support SD card support addition Support for additional expansion I/O modules
Page 13
Select a CompactLogix System
CompactLogix 5370 L3 Controllers In a CompactLogix 5370 L3 controller system, the 1769 I/O modules can be placed to the left and the right of the power supply. As many as eight modules can be placed on each side of the power supply. The CompactLogix 5370 L3 controller comes with: • Dual EtherNet/IP ports for linear and ring topologies. • USB port for firmware updates and programming. • Support for 1769 Compact I/O. Use the 1769-L30ER-NSE controller for mining applications. You can deplete the residual stored energy of the 1769-L30ER-NSE controller to 200 µJ or less before you transport it into or out of a mine. The 1769-L30ER-NSE controller does not maintain the real-time clock on power cycle. Characteristic
1769-L30ER
1769-L30ERM
1769-L30ER-NSE
1769-L33ER
1769-L33ERM
1769-L36ERM
Available user memory
1 MB
1 MB
1 MB No capacitor
2 MB
2 MB
3 MB
Memory card
1784-SD1 (1 GB), shipped with controller 1784-SD2 (2 GB)
Communication ports
• 2 EtherNet/IP • 1 USB
EtherNet/IP connections
• 256 EtherNet/IP • 120 TCP
• 256 EtherNet/IP • 120 TCP
• 256 EtherNet/IP • 120 TCP
• 256 EtherNet/IP • 120 TCP
• 256 EtherNet/IP • 120 TCP
EtherNet/IP nodes in one Logix Designer application, max
16
Integrated motion on an EtherNet/IP network, Module expansion capacity
8 1769 modules 1 bank of modules
Battery
None
Power supply distance rating
4 modules
Programming software support
• Version 20 - For controllers that use firmware revision 20.
• 256 EtherNet/IP • 120 TCP
32 Supports up to 4 axes, - 48 Supports up to 8 axes
Supports up to 16 axes
16 1769 modules 2 banks of modules
30 1769 modules 3 banks of modules
4 modules
4 modules
• Version 21 or later - For controllers that use firmware revision 21 or later.
These controllers replace previous catalog numbers. New Controller(1)
Replaces Previous Controller
Differences
1769-L30ER 1769-L30ERM 1769-L30ER-NSE
1769-L31 1769-L32C(2) 1769-L32E
1769-L33ER 1769-L33ERM
1769-L35CR(2) 1769-L35E
• Additional memory • Integrated motion on EtherNet/IP support (1769-L30ERM, 1769-L33ERM, 1769-L36ERM) • USB port instead of RS-232 port • Dual-port EtherNet/IP support • SD card instead of CompactFlash card
1769-L36ERM
Any previous 1769-L3x controller
(1) IMPORTANT: Typically, you can use any of the new controllers that are listed in each row as replacements for any of the previous controllers that are listed in the corresponding cell to the right. For example, you can replace a 1769-L32E with a 1769-L30ER, 1769-L30ERM, or 1769-L30ER-NSE controller. In some rare cases, system configuration helps to prevent controller replacement as shown in the previous table. For example, if your system uses a 1769-L32E controller with 12 expansion modules, you cannot replace that controller with a 1769-L30ER, 1769-L30ERM, or 1769-L30ER-NSE controller. Those controllers support no more than 8 expansion modules. You must replace the 1769-L32E controller with a 1769-L33ER, 1769-L33ERM, or 1769-L36ERM controller. We recommend that before you upgrade your controllers, consider your application requirements to verify that the replacements that are listed previously apply. (2) Requires converting from ControlNet connections to EtherNet/IP connections.
Rockwell Automation Publication 1769-SG001S-EN-P - December 2016
13
Page 14
Select a CompactLogix System
CompactLogix 5380 Controllers In a CompactLogix 5380 controller system, 5069 Compact I/O modules are installed to the right of the controller as local I/O modules. As many as 31 modules can be installed in the system. The CompactLogix 5380 controllers come with: • Dual embedded EtherNet/IP ports for use in star, linear, and DLR EtherNet/IP network topologies • USB port for firmware updates and programming • Support for Dual-IP mode. Energy Depletion characteristics for the 5069-L310ER-NSE controller. The residual stored energy of the 5069-L310ER-NSE controller depletes to 20 µJ or less in two minutes with 0…32V DC of SA power applied. The 5069-L310ER-NSE controller does not maintain the real-time clock on power cycle. IMPORTANT
You can use the 5069-L310ER-NSE controller with DC Sensor Actuator (SA) power only.
Characteristic
5069-L306ER, 5069-L306ERM
5069-L310ER, 5069-L320ER, 5069-L310ER-NSE, 5069-L320ERM 5069-L310ERM
5069-L330ER, 5069-L330ERM
5069-L340ER, 5069-L340ERM
5069-L350ERM
5069-L380ERM
5069-L3100ERM
Available user memory
0.6 MB
1 MB
3 MB
4 MB
5 MB
8 MB
10 MB
Memory card
• 1784-SD1 (1 GB) • 1784-SD2 (2 GB), ships with controller
Communication ports
• 2 - EtherNet/IP ports, 10 Mbps/100 Mbps/1 Gbps • 1 port USB client 50
55
60
70
80
EtherNet/IP nodes in 16 one Logix Designer application, max
2 MB
24
40
Integrated motion on an EtherNet/IP network
As many as 2 axes As many as 4 axes (5069-L306ERM (5069-L310ERM) only)
As many as 8 axes As many as 16 axes As many as 20 axes As many as 24 axes As many as 28 axes As many as 32 axes (5069-L320ERM) (5069-L330ERM) (5069-L340ERM)
Local I/O modules, max
8
16
Battery
None
Power supply terminals (sold separately)
• 5069-RTB64-SCREW kit - Includes RTB catalog numbers 5069-RTB6-SCREW and 5069-RTB4-SCREW • 5069-RTB64-SPRING - Includes RTB catalog numbers 5069-RTB6-SPRING and 5069-RTB4-SPRING
Programming software support
• Version 28 or later - 5069-L320ER, 5069-L340ERM only • Version 29 or later - 5069-L306ER, 5069-L306ERM, 5069-L310ER, 5069-L310ER-NSE, 5069-L310ERM, 5069-L320ERM, 5069-L330ER, 5069-L330ERM, 5069-L340ER • Version 30 or later - 5069-L350ERM, 5069-L380ERM, 5069-L3100ERM
31(1)
(1) When you use a 5069-L330ER or 5069-L330ERM controller with the Logix Designer application, version 29.00.00, the application limits the number of local I/O modules in the project to 16. For more information, see the Rockwell Automation® Knowledgebase article #942580, ‘5380 CompactLogix controllers limited to 16 local 5069 modules in V29 of Studio 5000.’ The document is available at http:// www.rockwellautomation.com/knowledgebase. With the Logix Designer application, version 30.00.00 or later, the controller supports as many as 31 local I/O modules.
14
Rockwell Automation Publication 1769-SG001S-EN-P - December 2016
Page 15
Select a CompactLogix System
Compact GuardLogix 5370 Controllers In a Compact GuardLogix 5370 controller system, the 1769 I/O modules can be placed to the left and the right of the power supply. As many as eight modules can be placed on each side of the power supply. The CompactLogix 5370 L3S controller comes with: • Dual EtherNet/IP ports for ring and linear topologies. • USB port for firmware updates and programming. • Safety control to achieve SIL 3/PLe according to ISO 13849. • Support for1769 Compact I/O. Characteristic
1769-L30ERMS
1769-L33ERMS
1769-L36ERMS
Available user memory
• 1 MB (standard) • 0.5 MB (safety)
• 2 MB (standard) • 1 MB (safety)
• 3 MB (standard) • 1.5 MB (safety)
Memory card
• 1784-SD1 (1 GB), shipped with controller • 1784-SD2 (2 GB)
Communication ports
• 2 EtherNet/IP • 1 USB
EtherNet/IP connections
• 256 EtherNet/IP • 120 TCP
EtherNet/IP nodes in one Logix Designer application, max
16
32
48
Integrated motion on an EtherNet/IP network
Supports up to 4 axes
Supports up to 8 axes
Supports up to 16 axes
Module expansion capacity
8 1769 modules 1 bank of modules
16 1769 modules 2 banks of modules
30 1769 modules 3 banks of modules
Battery
None
Power supply distance rating
4 modules
Programming software support
Version 28 or later - For controllers that use firmware revision 28 or later.
Rockwell Automation Publication 1769-SG001S-EN-P - December 2016
15
Page 16
Select a CompactLogix System
Armor CompactLogix and Armor Compact GuardLogix Controllers You can connect 1732 ArmorBlock or 1738 ArmorPoint I/O modules to the controller via EtherNet/IP in an Armor CompactLogix or Armor Compact GuardLogix controller system.The controller comes with: • An IP67-rated enclosure • A built-in, 24V DC Power Supply module • An SD card slot • Connection to On-Machine I/O • Dual EtherNet/IP ports for ring topologies • USB port for firmware updates and programming • Safety control to achieve SIL 3/PLe according to ISO 13849 • Support for1769 Compact I/O via EtherNet/IP Characteristic
1769-L33ERMO
1769-L36ERMO
Available user memory
2 MB
3 MB
Memory card
• 1784-SD1 (1 GB), shipped with controller • 1784-SD2 (2 GB)
Communication ports
• 2 EtherNet/IP • 1 USB
EtherNet/IP connections
• 256 EtherNet/IP • 120 TCP
EtherNet/IP nodes in one Logix Designer application, max
32
48
Integrated motion on an EtherNet/IP network
Supports up to 8 axes
Supports up to 16 axes
Programming software support
Version 28 or later - For controllers that use firmware revision 28 or later.
16
1769-L37ERMO
64
1769-L33ERMOS
1769-L36ERMOS
• 2 MB (standard) • 1 MB (safety)
• 3 MB (standard) • 1.5 MB (safety)
32
48
Supports up to 8 axes
Supports up to 16 axes
Rockwell Automation Publication 1769-SG001S-EN-P - December 2016
1769-L37ERMOS
64
Page 17
Select a CompactLogix System
Controller Memory Use IMPORTANT This section does not apply to CompactLogix 5380 controllers. These equations provide an estimate of the memory that is needed for a CompactLogix controller. These numbers are rough estimates. Controller Tasks
_____ * 4000
=
_____ bytes (minimum 1 task)
Digital I/O points
_____ * 400
=
_____ bytes
_____ * 2600
=
_____ bytes
_____ * 7400
=
_____ bytes
Other communication modules
_____ * 2000
=
_____ bytes
Motion axes
_____ * 8000
=
_____ bytes
FactoryTalk® alarm instruction
_____ * 1000
=
_____ bytes (per alarm)
FactoryTalk subscriber
_____ * 10000
=
_____ bytes
Analog I/O points (1)
DeviceNet modules
(2)
(1) The first DeviceNet module is 7400 bytes. Additional DeviceNet modules are 5800 bytes each. (2) Count the communication modules in the system, not just those modules in the local chassis. This total includes device connection modules, adapters, and ports on PanelView terminals.
Reserve 20…30% of the controller memory for future expansion.(1)
(1) This requirement does not apply to CompactLogix 5380 controllers.
Rockwell Automation Publication 1769-SG001S-EN-P - December 2016
17
Page 18
Select a CompactLogix System
CompactLogix Communication Options You can configure your system for information exchange between a range of devices and computing platforms and operating systems. Select a CompactLogix controller with integrated communication or the appropriate communication module. For detailed specifications, see: • CompactLogix Controllers Specifications Technical Data, publication 1769-TD005. • CompactLogix Communication Modules Specifications Technical Data, publication 1769-TD007. • CompactLogix 5380 Controllers Specifications Technical Data, publication 5069-TD002
EtherNet/IP Communication Options The Ethernet Industrial network protocol (EtherNet/IP) is an open industrial-networking standard that supports real time I/O messaging and message exchange. The EtherNet/IP network uses off-the-shelf Ethernet communication chips and physical media. Dual-port EtherNet/IP support embeds switch technology directly in the controller to so the controller can operate on star, linear, or ring EtherNet/IP topologies. CompactLogix Controller EtherNet/IP Communication Options Cat. No.
Description
Communication Rate
Logix Resources(2)
TCP/IP Connections
1769-L16ER-BB1B,
CompactLogix 5370 L1 controller with embedded dual EtherNet/IP ports, POINT I/O form factor
10/100 Mbps
4 nodes 256 EtherNet/IP connections
120
1769-L18ER-BB1B, 1769-L18ERM-BB1B
8 nodes 256 EtherNet/IP connections
1769-L19ER-BB1B 1769-L24ER-BB1B, 1769-L24ER-QBFC1B
CompactLogix 5370 L2 controller with embedded dual EtherNet/IP ports, Compact I/O form factor
1769-L27ERM-QBFC1B 1769-L30ER, 1769-L30ERM, 1769-L30ERMS
CompactLogix 5370 L3 controller with embedded dual EtherNet/IP ports
10/100 Mbps
8 nodes 256 EtherNet/IP connections
10/100 Mbps
16 nodes 256 EtherNet/IP connections
10/100 Mbps
16 nodes 256 EtherNet/IP connections
1769-L33ER, 1769-L33ERM, 1769-L33ERMO, 1769-L33ERMOS, 1769-L33ERMS
32 nodes 256 EtherNet/IP connections
1769-L36ERM, 1769-L33ERMO, 1769-L36ERMOS, 1769-L36ERMS
48 nodes 256 EtherNet/IP connections
1769-L37ERMO, 1769-L37ERMOS
64 nodes 256 EtherNet/IP connections
18
Rockwell Automation Publication 1769-SG001S-EN-P - December 2016
120
120
Page 19
Select a CompactLogix System
CompactLogix Controller EtherNet/IP Communication Options Cat. No.
Description
Communication Rate
5069-L306ER, 5069-L306ERM CompactLogix 5380 controller with embedded dual EtherNet/IP ports 10/100 Mbps, 1 Gbps
(1)
Logix Resources(2)
TCP/IP Connections
16, 5069-L310ER, 5069-L310ERNSE, 5069-L310ERM
24
5069-L320ER, 5069-L320ERM
40
5069-L330ER, 5069-L330ERM
50
5069-L340ER, 5069-L340ERM
55
5069-L350ERM
60
5069-L380ERM
70
5069-L3100ERM
80
(1) Network performance in a CompactLogix 5380 system is optimal if the 1 Gbps network communication rate is used. However, many Ethernet devices do not support the 1 Gbps network communication rate. You must consider how the different maximum network communication rates impact your CompactLogix 5380 control system when you design the system. (2) The number of nodes that are listed for CompactLogix 5370 and CompactLogix 5380 controllers represents the maximum number of EtherNet/IP nodes you can include in a controller project for those controllers. For example, in a controller project that uses a 1769-L18ERM-BB1B controller, you can add as many as eight EtherNet/IP nodes to the project.
CompactLogix 5380 Controllers EtherNet/IP Modes The CompactLogix 5380 controllers are the first Logix controllers to offer multiple EtherNet/IP modes. With CompactLogix 5380 controller firmware revision 29.011 or later, you can use Dual-IP mode or Linear/DLR mode.
Dual-IP Mode Dual-IP mode lets you configure the controller embedded Ethernet ports to connect to separate EtherNet/IP networks, that is, an enterprise-level network and a device-level network. In this mode, each port requires its own network configurations that include some restrictions. For example, when you set IP addresses in Dual-IP mode, you cannot overlap IP addresses between the ports. CompactLogix 5380 Controller 5069 Compact I/O Modules Enterprise-level Network PanelView Plus 7 Terminal F1
F9
F2
F10
F3
F11
F4
F12
F5
F13
F6
F14
F7
F15
F8
F16
Device-level Network Stratix 5700 Switch
PowerFlex 527 Drive 527
Rockwell Automation Publication 1769-SG001S-EN-P - December 2016
5069-AEN2TR Adapter 5069 Compact I/O Modules
19
Page 20
Select a CompactLogix System
Linear/DLR Mode When CompactLogix 5380 controllers operate in Linear/DLR mode, they connect to only one network. That is, there is only one network configuration. When used in Linear/DLR mode, CompactLogix 5380 controllers can connect to any EtherNet/IP network topology–linear, DLR, or star. CompactLogix 5380 Controller 5069 Compact I/O Modules
PanelView Plus 7 Terminal
F1
F9
F2
F10
F3
F11
F4
F12
F5
F13
F6
F14
F7
F15
F8
F16
Device-level Network
527
5069-AEN2TR Adapter 5069 Compact I/O Modules
PowerFlex 527 Drive
For more information on EtherNet/IP modes with a CompactLogix 5380 controller, see the following: • CompactLogix 5380 Controllers User Manual, publication 5069-UM001 • CompactLogix 5380 Controllers Specifications Technical Data, publication 5069-TD002
20
Rockwell Automation Publication 1769-SG001S-EN-P - December 2016