CompactLogix System Selection Guide, pages 21 to 30

Pages 21 to 30 of 40

The original document is the PDF (7.0 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

For the Allen-Bradley 1769-IQ6X0W4

Page 21

Select a CompactLogix System

DeviceNet Communication Options The DeviceNet network is an open, low-level network that provides connections between simple industrial devices (such as sensors and actuators) and higher-level devices (such as controllers and computers). Cat. No.

Description

Communication Rate

Number of Nodes

1769-SDN

Compact I/O DeviceNet scanner

64

1769-ADN

Compact I/O DeviceNet adapter

125 Kbps (500 m, max) 250 Kbps (250 m, max) 500 Kbps (100 m, max)

Serial Communication Options These CompactLogix controllers support serial communication. Cat. No.

Serial Options

1769-L16ER-BB1B, 1769-L18ER-BB1B, 1769-L18ERM-BB1B, 1769-L19ERM-BB1B

1734-232ASC module for an RS-232 serial interface 1734-485 ASC module for an RS-422 and RS-485 serial device

1769-L24ER-BB1B, 1769-L24ER-QBFC1B

1769-ASCII module for an ASCII interface to RS-232, RS-422, and RS-485 devices 1769-SM2 module for a Modbus RTU interface

1769-L27ERM-QBFC1B 1769-L30ER, 1769-L30ERM, 1769-L30ERMS 1769-L33ER, 1769-L33ERM, 1769-L33ERMO, 1769-L33ERMOS, 1769-L33ERMS 1769-L36ERM, 1769-L36ERMO, 1769-L36ERMOS, 1769-L36ERMS, 1769-L37ERMO, 1769-L37ERMOS

Modbus Support To access a Modbus TCP network, connect through the embedded Ethernet port of the CompactLogix 5370 or CompactLogix 5380 controllers and execute a ladder-logic routine. For more information, see Knowledgebase document 470365 at http://www.rockwellautomation.com/knowledgebase/. To access a Modbus RTU network, connect through a 1769-SM2 module, or Encompass partner, Prosoft ModuBus module, or Gateway and execute a ladder-logic routine. For more information, see Using Logix5000 Controllers as Masters or Slaves on Modbus Application Solution, publication CIG-AP129.

Rockwell Automation Publication 1769-SG001S-EN-P - December 2016

21

Page 22

Select a CompactLogix System

CompactLogix Integrated Motion The Logix architecture supports motion control components that work in a wide variety of machine architectures. • Integrated motion on EtherNet/IP supports a connection to Ethernet drives. • The Kinetix integrated-motion solution uses a SERCOS interface module to perform multi-axis, synchronized motion. • Logix integrated motion supports the analog family of servo modules for controlling drives/actuators. • Networked motion lets you connect via the DeviceNet network to one axis drive to perform point-to-point indexing. • Not all CompactLogix 5370 and CompactLogix 5380 controllers support Integration motion on EtherNet/IP. • All CompactLogix 5380 controllers support single-axis motor control with PowerFlex variable frequency drives over an EtherNet/IP network. This functionality is available on CompactLogix 5380 controllers that do not support other aspects of Integrated Motion over an EtherNet/IP network. Motion Feature

1769-L18ERM-BB1B

EtherNet/IP sequence of events for software registration

Yes

Kinematics

Yes

Integrated motion on an EtherNet/IP network

Yes

Indexing

Yes with one of these pulsetrain output modules: • AMCI 1734-3401 • AMCI 1734-3401L

Load observer (with only Kinetix 6500 drives)

Yes

Total axis count

100

Virtual axis, max

100

Position-loop axis, max

2

Axis/ms, max

2

EtherNet/IP feedback, VHz, torque, or velocity axis, max

8

1769-L27ERM-QBFC1B

1769-L30ERM, 1769-L30ERMS, 1769-L33ERM, 1769-L33ERMO, 1769-L33ERMOS, 1769-L33ERMS, 1769-L36ERM, 1769-L36ERMO, 1769-L36ERMOS, 1769-L36ERMS, 1769-L37ERMO, 1769-L37ERMOS

5069-L306ERM, 5069-L310ERM, 5069-L320ERM, 5069-L330ERM, 5069-L340ERM 5069-L350ERM 5069-L380ERM 5069-L3100ERM

Yes with AMCI 1769-3602 pulse-train output module

Yes

4

• • • • • • • •

16

5069-L306ERM: 2 5069-L310ERM: 4 5069-L320ERM: 8 5069-L330ERM: 16 5069-L340ERM: 20 5069-L350ERM: 24 5069-L380ERM: 28 5069-L3100ERM: 32

32 16

48

80

For more information, see the: • CompactLogix 5380 Controllers User Manual, publication 5069-UM001. • Integrated Motion on the EtherNet/IP network Configuration and Startup User Manual, publication MOTION-UM003. • Integrated Motion on the EtherNet/IP network Reference Manual, Publication MOTION-RM003. • Motion Analyzer CD to size your motion application and to make final component selection. Download the software from http://www.ab.com/motion/software/analyzer.html. • Kinetix Motion Control Selection Guide, publication GMC-SG001, to verify drive, motor, and accessory specifications.

22

Rockwell Automation Publication 1769-SG001S-EN-P - December 2016

Page 23

Select a CompactLogix System

Compact GuardLogix Integrated Safety The Compact GuardLogix controller provides safety control to achieve SIL 3/PLe according to ISO 13849. A major benefit of this system is that it is still one project, safety and standard together. Application

Description

SIL 1, 2, 3

The Compact GuardLogix controller system is type-approved and certified for use in safety applications up to and including SIL 3 according to IEC 61508, and applications up to and including PLe/Cat.4 according to ISO 13849-1. For more information, see: • GuardLogix Controllers User Manual, publication 1769-UM022. • GuardLogix 5570 and Compact GuardLogix 5370 Controller Safety Systems Safety Reference Manual, publication 1756-RM099. • Compact GuardLogix Controllers User Manual, publication 1768-UM002. • GuardLogix Safety Application Instruction Set Reference Manual, publication 1756-RM095.

During development, safety and standard have the same rules, multiple programmers, online editing, and forcing are all possible. Once the project is tested and ready for final validation, you apply the safety application signature and safety-lock the application to set the safety task to a SIL 3 integrity level. The GuardLogix controller enforces the SIL 3 integrity level. When safety memory is locked and protected, the safety logic cannot be modified and all safety functions operate with SIL 3 integrity. On the standard side of the GuardLogix controller, all functions operate like a regular Logix controller. Thus online editing, forcing, and other activities are all possible. With this level of integration, standard logic and external devices, like HMIs or other controllers, can read safety memory, avoiding the need to condition safety memory for use elsewhere. The result is easy system-wide integration and the ability to display safety status on displays or marquees. Use Guard I/O™ modules for field device connectivity. For safety interlocking between GuardLogix controllers use Ethernet or ControlNet networks. Multiple GuardLogix controllers can share safety data for zone to zone interlocking, or one GuardLogix controller can use remote distributed safety I/O between cells/areas. The Compact GuardLogix controller has these safety-related features and the standard features of a CompactLogix controller. Characteristic

1769-L30ERMS

1769-L33ERMS

1769-L36ERMS

1768-L43S

1768-L45S

Available user memory

1 MB standard 0.5 MB safety

2 MB standard 1 MB safety

3 MB standard 1.5 MB safety

2 MB standard 0.5 MB safety

3 MB standard 1 MB safety

Communication options

• Dual-port EtherNet/IP (standard and safety) • DeviceNet (standard)

• EtherNet/IP (standard and safety) • ControlNet (standard and safety) • DeviceNet (standard)

• EtherNet/IP (standard and safety) • ControlNet (standard and safety) • DeviceNet (standard)

Programming languages

• Standard task: all languages • Safety task: relay ladder, safety application instructions

Rockwell Automation Publication 1769-SG001S-EN-P - December 2016

23

Page 24

Select a CompactLogix System

Armor CompactLogix and Armor Compact GuardLogix Integrated Safety The Armor CompactLogix and Armor Compact GuardLogix controllers extend the features of the CompactLogix 5370 and Compact GuardLogix 5370 controllers to On-Machine space. The Armor Compact GuardLogix controllers deliver integrated safety control up to and including SIL 3, according to IEC 61508 and Ple/CAT. 4, according to ISO 13849-1. Application

Description

SIL 1, 2, 3

The Compact GuardLogix controller system is type-approved and certified for use in safety applications up to and including SIL 3 according to IEC 61508, and applications up to and including PLe/Cat.4 according to ISO 13849-1. For more information, see: • GuardLogix Controllers User Manual, publication 1769-UM022. • GuardLogix 5570 and Compact GuardLogix 5370 Controller Safety Systems Safety Reference Manual, publication 1756-RM099. • Compact GuardLogix Controllers User Manual, publication 1768-UM002. • GuardLogix Safety Application Instruction Set Reference Manual, publication 1756-RM095.

During development, safety and standard have the same rules, multiple programmers, online editing, and forcing are all possible. Once the project is tested and ready for final validation, you apply the safety application signature and safety-lock the application to set the safety task to a SIL 3 integrity level. The Armor Compact GuardLogix controller enforces the SIL 3 integrity level. When safety memory is locked and protected, the safety logic cannot be modified and all safety functions operate with SIL 3 integrity. On the standard side of the Armor Compact GuardLogix controller, all functions operate like a regular Logix controller. Thus online editing, forcing, and other activities are all possible. With this level of integration, standard logic and external devices, like HMIs or other controllers, can read safety memory, avoiding the need to condition safety memory for use elsewhere. The result is easy system-wide integration and the ability to display safety status on displays or marquees. Use Guard I/O modules for field device connectivity. For safety interlocking between Armor Compact GuardLogix controllers use Ethernet or ControlNet networks. Multiple Armor Compact GuardLogix controllers can share safety data for zone to zone interlocking, or one GuardLogix controller can use remote distributed safety I/O between cells/areas. The Armor CompactLogix and Armor Compact GuardLogix controllers have these safety-related features and the standard features of a CompactLogix controller. Characteristic

1769-L33ERMO

1769-L33ERMOS

1769-L36ERMO, 1769-L37ERMO

1769-L36ERMOS, 1769-L37ERMOS

Available user memory

2 MB

• 2 MB standard • 1 MB safety

3 MB

• 3 MB standard • 1.5 MB safety

Communication options

• Dual-port EtherNet/IP (standard and safety) • DLR

Programming languages

• Standard task: all languages • Safety task: relay ladder

24

Rockwell Automation Publication 1769-SG001S-EN-P - December 2016

Page 25

Select a CompactLogix System

Additional Local I/O Modules 1734 POINT I/O Modules Additional 1734 POINT I/O modules can be installed on a CompactLogix 5370 L1 controller. The POINT I/O family is ideal for applications where flexibility and low cost of ownership are key for successful control system design and operation. The base (A) mounts onto the DIN rail and provides the backplane. The POINT I/O module (B) snaps into the base. The removable terminal block (C) also snaps into the base and provides the wiring and terminations for field-side connections, and system power for the backplane.

1734 AC Digital Modules Cat. No.

Inputs/Outputs

Voltage Category

Wiring Base

POINTBus™ Current @ 5V DC

1734-IA2

2 inputs, nonisolated, sink

120V AC

1734-TB, 1734-TBS, 1734-TOP, 1734-TOPS

75 mA

1734-IA4

4 inputs, nonisolated, sink

1734-IM2

2 inputs, nonisolated, sink

220V AC

1734-TB, 1734-TBS, 1734-TOP, 1734-TOPS

75 mA

1734-IM4

4 inputs, nonisolated, sink

1734-OA2

2 outputs, nonisolated, source

120/220V AC

1734-TB, 1734-TBS, 1734-TOP, 1734-TOPS

75 mA

1734-OA4

4 outputs, nonisolated, source

1734 DC Digital Modules Cat. No.

Inputs/Outputs

Voltage Category

Wiring Base

POINTBus Current @ 5V DC

1743-IB2

2 inputs, sink

24V DC

1734-TB, 1734-TBS

75 mA

1734-IB4

4 inputs, sink

1734-IB4D

4 inputs, sink, diagnostic

24V DC

1734-TB, 1734-TBS, 1734-TOP, 1734-TOPS

50 mA

1734-IB8

8 inputs, sink

24V DC

1734-TB, 1734-TBS

75 mA

1734-IB8S

8 inputs, sink, safety

24V DC

1734-TB,1734-TOP

175 mA

1734-IV2

2 inputs, source

24V DC

1734-TB,1734-TBS

75 mA

1734-IV4

4 inputs, source

1734-IV8

8 inputs, source

Rockwell Automation Publication 1769-SG001S-EN-P - December 2016

25

Page 26

Select a CompactLogix System

Cat. No.

Inputs/Outputs

Voltage Category

Wiring Base

POINTBus Current @ 5V DC

1734-OB2

2 outputs, nonisolated, source

12/24V DC

1734-TB, 1734-TBS

75 mA

1734-OB2E

2 outputs, nonisolated protected, source

1734-OB4

4 outputs, nonisolated, source

1734-OB4E

4 outputs, nonisolated protected, source

1734-OB8

8 outputs, nonisolated, source

1734-OB8E

8 outputs, nonisolated protected, source

1734-OB8S

8 outputs, safety

24V DC

1734-TB,1734-TOP

190 mA

1734-OV2E

2 outputs, nonisolated protected, sink

12/24V DC

1734-TB, 1734-TBS

75 mA

1734-OV4E

4 outputs, nonisolated protected, sink

1734-OV8E

8 outputs, nonisolated protected, sink

1734 Relay Contact Output Modules Cat. No.

Inputs/Outputs

Voltage Range

Wiring Base

POINTBus Current @ 5V DC

1734-OW2

2 Form A (normally open) relays

1734-TB,1734-TBS

80 mA

1734-OW4

4 Form A (normally open) relays

1734-OX2

2 Form C isolated (normally open; normally closed) electromechanical relays

5…28.8V DC @ 2.0 A 48V DC @ 0.5 A 125V DC @ 0.25 A 125V DC @ 2.0 A 240V AC @ 2.0 A

100 mA

1734 Analog and Temperature Modules Cat. No.

Inputs/Outputs

Range

Resolution

Wiring Base

POINTBus Current @ 5V DC

1734-IE2C

2 single-ended, nonisolated, current

4…20 mA 0…20 mA

16 bits over 0…21 mA 0.32 A/cnt

1734-TB, 1734-TBS

75 mA

1734-IE2V

2 single-ended, nonisolated, voltage

15 bits plus sign 0…10V (-0.0V under, +0.5V over) 320 V/cnt in unipolar or ±10V (-0.5V under, +0.5V over) bipolar mode

1734-IE4C

4 single-ended, nonisolated, current

4…20 mA 0…20 mA

16 bits - over 0…21 mA 0.32 A/cnt

1734-IE4S

4 inputs, single-ended, safety rated

0…20 mA, 4…20 mA ±5V, 0…5V, ±10V, 0…10V

12 bits

1734-TB, 1734-TBS, 1734-TOP, 1734-TOPS, 1734-TOP3, 1734-TOP3S

110 mA

1734-IE8C

8 single-ended, nonisolated, current

4…20 mA 0…20 mA

16 bits - over 0…21 mA 0.32 A/cnt

1734-TB, 1734-TBS

75 mA

1734-IR2

2 single-ended, nonisolated

0…600

16 bits 9.5 m/cnt 0.03 °C/cnt (Pt385 @ 25 °C) [0.05 °F/cnt (Pt385 @ 77 °F)]

1734-TB, 1734-TBS, 1734-TOP, 1734-TOPS

220 mA

1734-IR2E

2 single-ended, nonisolated, protected

0…220

16 bits 2.4 m/cnt 0.006 °C/cnt (Pt385 @ 25 °C) [0.0114 °F/cnt (Pt385 @ 77 °F)]

26

Rockwell Automation Publication 1769-SG001S-EN-P - December 2016

Page 27

Select a CompactLogix System

Cat. No.

Inputs/Outputs

Range

Resolution

Wiring Base

POINTBus Current @ 5V DC

1734-IT2I

2 differential, individually isolated

Sensors B, C, E, J, K, N, R, S, T

15 bits plus sign 2.5 V/cnt

1734-TBCJC

175 mA

1734-OE2C

2 single-ended, nonisolated, current

4…20 mA 0…20 mA

13 bits over 0…21mA 2.5 A/cnt (average) 3…2.7 A/cnt (typical range)

1734-TB, 1734-TBS, 1734-TB3, 1734-TB3S

75 mA

1734-OE2V

2 single-ended, nonisolated, voltage

0…10V (-0.0V under, +0.5V 14 bits (13 plus sign) over) 1.28 mV/cnt in unipolar or ±10V (-0.5V under, +0.5V over) bipolar mode

1734-OE4C

4 single-ended, nonisolated, current

4…20 mA 0…20 mA

16 bits over 0…21 mA 0.32 A/cnt)

1734 Counter Modules Cat. No.

Inputs/Outputs

Range

Frequency

Wiring Base

POINTBus Current @ 5V DC

1734-IJ

1 - 1 group of A/Areturn, B/Breturn and Z/Zreturn

5V DC

1734-TB, 1734-TBS, 1734-TB3, 1734-TB3S

160 mA

1734-IK

1 - 1 group of A/Areturn, B/Breturn and Z/Zreturn

15…24V DC

1.0 MHz counter and encoder X1 500 kHz encoder X2 (no filter 250 kHz encoder X4 (no filter)

1734-VHSC24

1 - 1 group of A/Areturn, B/Breturn and Z/Zreturn

15…24V DC

180 mA

1734-VHSC5

1 - 1 group of A/Areturn, B/Breturn and Z/Zreturn

5V DC

180 mA

160 mA

1734 Self-configurable Modules Cat. No.

Inputs/Outputs

Voltage Category

Wiring Base

POINTBus Current @ 5V DC

1734-8CFG

8 self-configurable

24V DC

1734-TB, 1734-TBS, 1734-TOP, 1734-TOPS

100 mA

1734 Communication and Specialty Modules Cat. No.

Description

Wiring Base

1734-AENT

The single port adapter connects POINT I/O modules to the Ethernet network.

–

1734-AENTR

The adapter connects POINT I/O modules to a linear or DLR network and uses two copper network ports to connect to the network.

–

1734-232ASC

The 1734-232ASC and 1734-485ASC serial interface modules offer a serial-link communication interface solution for peripheral products with RS-232 (only 1734-232ASC), RS-485, and RS-422 ports (only 1734-485ASC.)

1734-TB, 1734-TBS

75 mA

1734-ARM

The 1734-ARM address reserve module reserves address and slot numbers to maintain a numbering scheme of a system. The 1734-ARM has no module configuration and does not communicate I/O data.

1734-TB, 1734-TBS

75 mA

1734-CTM

The common terminal module (1734-CTM) and voltage terminal module (1734-VTM) expand the termination capabilities of POINT I/O modules. Install the modules to support higher density (8 channel) POINT I/O modules.

1734-TB, 1734-TBS, 1734-TOP, 1734-TOPS

75 mA

The 1734-SSI module collects serial data from absolute-position, encoding sensors that use standard serial synchronous interface (SSI) protocol.

1734-TB, 1734-TBS

110 mA

1734-485ASC

1734-VTM 1734-SSI

Rockwell Automation Publication 1769-SG001S-EN-P - December 2016

POINTBus Current

27

Page 28

Select a CompactLogix System

1769 Compact I/O Modules The 1769 Compact I/O modules can be used with the CompactLogix 5370 L2 and L3 controllers and 1768 CompactLogix controllers as follows:

Local I/O modules with CompactLogix 5370 L3 Controller

Remote I/O modules accessible by using a 1769-AENTR EtherNet/IP Adapter

• Local I/O modules • Remote I/O modules accessible by using a 1769-AENTR EtherNet/IP adapter

The modules mechanically lock together with a tongueand-groove design and have an integrated communication bus that is connected from module to module by a moveable bus connector. Each I/O module includes a built-in removable terminal block with fingersafe cover for connections to I/O sensors and actuators. The terminal block is behind a door at the front of the module. I/O wiring can be routed from beneath the module to the I/O terminals. For detailed specifications, see 1769 Compact I/O Modules Specifications Technical Data, publication 1769-TD006.

Power Supply Distance Ratings Check the specification table of each module for the power supply distance rating. This rating indicates how many slot positions the module can be from the power supply.

1769 AC Digital Modules Cat. No.

Inputs/Outputs

Voltage Category

Operating Voltage Range

Backplane Current

Power Supply Distance Rating

1769-IA8I

8 inputs, individually isolated

100/120V AC

79…132V AC, 47…63 Hz

90 mA @ 5.1V(1)

8

1769-IA16

16 inputs

100/120V AC

79…132V AC, 47…63 Hz

115 mA @ 5.1V

8

1769-IM12

12 inputs

200/240V AC

159…265V AC, 47…63 Hz

100 mA @ 5.1V

8

1769-OA8

8 outputs

100/240V AC

85…265V AC 47…63 Hz

145 mA @ 5.1V

8

1769-OA16

16 outputs

100/240V AC

85…265V AC 47…63 Hz

225 mA @ 5.1V

8

(1) Maximum is 190 mA.

28

Rockwell Automation Publication 1769-SG001S-EN-P - December 2016

Page 29

Select a CompactLogix System

1769 DC Digital Modules Cat. No.

Inputs/Outputs

Voltage Category

Operating Voltage Range

Backplane Current

Power Supply Distance Rating

1769-IG16

16 inputs

5V DC TTL

4.5…5.5V DC

120 mA @ 5.1V

8

1769-IQ16

16 inputs

24V DC sink/source

10…30V DC @ 30 °C (86 °F) 10…26.4V DC @ 60 °C (140 °F)

115 mA @ 5.1V

8

1769-IQ16F

16 inputs, high speed

24V DC sink/source

10…30V DC @ 30 °C (86 °F) 10…26.4V DC @ 60 °C (140 °F)

100 mA @ 5.1V

8

1769-IQ32

32 inputs

24V DC sink/source

10…30V DC @ 30 °C (86 °F) 10…26.4V DC @ 60 °C (140 °F)

170 mA @ 5.1V

8

1769-IQ32T

32 inputs

24V DC sink/source

20.4…26.4V DC @ 60 °C (140 °F)

170 mA @ 5.1V

8

1769-IQ6XOW4

6 inputs 4 outputs

24V DC sink/source input AC/DC normally open relay contact outputs

10…30V DC @ 30 °C (86 °F) 10…26.4V DC @ 60 °C (140 °F)

105 mA @ 5.1V 50 mA @ 24V

8

1769-OB8

8 outputs

24V DC source

20.4…26.4V DC

145 mA @ 5.1V

8

1769-OB16

16 outputs

24V DC source

20.4…26.4V DC

200 mA @ 5.1V

8

1769-OB16P

16 outputs, protected

24V DC source

20.4…26.4V DC

160 mA @ 5.1V

8

1769-OB32

32 outputs

24V DC source

20.4…26.4V DC

300 mA @ 5.1V

6

1769-OB32T

32 outputs

24V DC source

10.2…26.4V DC

220 mA @ 5.1V

8

1769-OG16

16 outputs

5V DC TTL

4.5…5.5V DC

200 mA @ 5.1V

8

1769-OV16

16 outputs

24V DC sink

20.4…26.4V DC

200 mA @ 5.1V

8

1769-OV32T

32 outputs

24V DC sink

10.2…26.4V DC

300 mA @ 5.1V

8

1769 Contact Output Modules Cat. No.

Inputs/Outputs

Operating Voltage Range

Backplane Current

Power Supply Distance Rating

1769-OW8

8 outputs

5…265V AC 5…125V DC

125 mA @ 5.1V 100 mA @ 24V

8

1769-OW8I

8 outputs, individually isolated

5…265V AC 5…125V DC

125 mA @ 5.1V 100 mA @ 24V

8

1769-OW16

16 outputs

5…265V AC 5…125V DC

205 mA @ 5.1V 180 mA @ 24V

8

Rockwell Automation Publication 1769-SG001S-EN-P - December 2016

29

Page 30

Select a CompactLogix System

1769 Analog Modules Cat. No.

Inputs/Outputs

Range

Resolution

Backplane Current

Power Supply Distance Rating

1769-IF4

4 inputs, differential or single-ended

±10V 0…10V 0…5V 1…5V 0…20 mA 4…20 mA

14 bits (unipolar) 14 bits plus sign (bipolar)

120 mA @ 5.1V 60 mA @ 24V

8

1769-IF4I

4 inputs, differential or single-ended, individually isolated

±10V 0…10V 0…5V 1…5V 0…20 mA 4…20 mA

16 bits (unipolar) 15 bits plus sign (bipolar)

145 mA @ 5.1V 125 mA @ 24V

8

1769-IF8

8 inputs, differential or single-ended

±10V 0…10V 0…5V 1…5V 0…20 mA 4…20 mA

16 bits (unipolar) 15 bits plus sign (bipolar)

120 mA @ 5.1V 70 mA @ 24V

8

1769-IF16C

16 inputs, single-ended

0…20 mA 4…20 mA

16 bits (unipolar) 15 bits plus sign (bipolar)

190 mA @ 5.1V 70 mA @ 24V

8

1769-IF16V

16 inputs, single-ended

±10V 0…10V 0…5V 1…5V

16 bits (unipolar) 15 bits plus sign (bipolar)

190 mA @ 5.1V 70 mA @ 24V

8

1769-IF4XOF2

4 inputs, differential or single-ended 2 outputs, single-ended

0…10V 0…20 mA

Input: 8 bits plus sign Output: 8 bits plus sign

120 mA @ 5.1V 160 mA @ 24V

8

1769-IF4FXOF2F

4 inputs, fast differential or single-ended 2 outputs, fast single-ended

±10V 0…10V 0…5V 1…5V 0…20 mA 4…20 mA

Input: 14 bits (unipolar) 14 bits plus sign (bipolar) Output: 13 bits (unipolar) 13 bits plus sign (bipolar)

220 mA @ 5.1V 120 mA @ 24V

8

1769-OF2

2 outputs, single-ended

±10V 0…10V 0…5V 1…5V 0…20 mA 4…20 mA

14 bits (unipolar) 14 bits plus sign (bipolar)

120 mA @ 5.1V 120 mA @ 24V

8

1769-OF4

4 outputs, single-ended

±10V 0…10V 0…5V 1…5V 0…20 mA 4…20 mA

15 bits plus sign unipolar and bipolar

120 mA @ 5.1V 170 mA @ 24V

8

1769-OF4CI

4 outputs, differential, individually isolated

0…20 mA 4…20 mA

16 bits (unipolar)

165 mA @ 5V 110 mA @ 24V

8

30

Rockwell Automation Publication 1769-SG001S-EN-P - December 2016