The text of a manual · part 4 of 4
CompactLogix System Selection Guide, pages 31 to 40
Pages 31 to 40 of 40
The original document is the PDF (7.0 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
For the Allen-Bradley 1769-IQ6X0W4
Page 31
Select a CompactLogix System
Cat. No.
Inputs/Outputs
Range
Resolution
Backplane Current
Power Supply Distance Rating
1769-OF4VI
4 outputs, differential, individually isolated
±10V 0…10V 0…5V 1…5V
15 bits plus sign (bipolar)
145 mA @ 5.1V 75 mA @ 24V
8
1769-OF8C
8 outputs, single-ended
0…20 mA 4…20 mA
16 bits (unipolar)
140 mA @ 5.1V 145 mA @ 24V
8
1769-OF8V
8 outputs, single-ended
±10V 0…10V 0…5V 1…5V
16 bits plus sign (bipolar)
145 mA @ 5.1V 125 mA @ 24V
8
1769 Analog RTD and Thermocouple Modules Cat. No.
Inputs/Outputs
Sensors Supported
Backplane Current
Power Supply Distance Rating
1769-IR6
6 RTD inputs
100, 200, 500, 1000 Platinum 385 100, 200, 500, 1000 Platinum 3916 120 Nickel 618 120 Nickel 672 10 Nickel-iron 518 0…150 0…500 0…1000 0…3000
100 mA @ 5.1V 45 mA @ 24V
8
1769-IT6
6 thermocouple inputs
Thermocouple types B, C, E, J, K, N, R, S, T ±50V ±100V
100 mA @ 5.1V 45 mA @ 24V
8(1)
(1) To reduce the effects of electrical noise, install the 1769-IT6 module at least two slots away from the AC power supplies.
1769 Communication and Specialty Modules Cat. No.
Description
Backplane Current
Power Supply Distance Rating
1769-AENTR
The adapter connects 1769 I/O modules to a linear or DLR network and uses two copper network ports to connect to the network.
500 mA @ 5V
5
1769-ARM
Use a 1769-ARM address reserve module to reserve module slots. After creating an I/O configuration and user program, you can remove and replace any I/O module in the system with a 1769-ARM module. You must first inhibit the removed module in the Logix Designer application.
60 mA @ 5.1V
8
1769-ASCII
The 1769-ASCII module, a general-purpose two-channel ASCII interface, provides a flexible network interface to a wide variety of RS-232, RS-485, and RS-422 ASCII devices. The module provides the communication connections to the ASCII device.
425 mA @ 5.1V
4
1769-BOOLEAN
Use the 1769-BOOLEAN module in applications that require repeatability, such as material handling and 220 mA @ 5.1V packaging, when there is a requirement to activate an output that is based on the transition of an input. If the Boolean expression is true, the output is directed to the ON state. If the Boolean expression is false, the output channel is directed to the OFF state. There are four operators that you can configure as OR, AND, XOR, or none.
8
Rockwell Automation Publication 1769-SG001S-EN-P - December 2016
31
Page 32
Select a CompactLogix System
Cat. No.
Description
Backplane Current
Power Supply Distance Rating
1769-HSC
Use the 1769-HSC when you need: • A counter module that can react to high-speed input signals. • To generate rate and time-between-pulses (pulse interval) data. • As many as two channels of quadrature or four channels of pulse/count inputs.
245 mA @ 5.1V
4
1769-SM1
The Compact I/O to DPI™ or SCANport™ module connects to PowerFlex 7-class drives, other DPI-based host devices, and SCANport-based host devices such as 1305 and 1336 PLUS™ II drives.
280 mA @ 5.1V
6
1769-SM2
The Compact I/O to DSI/Modbus module connects to PowerFlex 4-class drives and to other Modbus RTU slave devices, such as PowerFlex 7-class drives with 20-COMM-H RS-485 HVAC adapters.
350 mA @ 5.1V
4
1769 Expansion Cables If you divide 1769 modules into multiple banks, make sure: • Each bank needs its own power supply. • To use expansion cables to connect the banks. • The last I/O bank requires an end cap. Vertical
Horizontal
How you orient I/O banks determines the expansion cables that you must connect the I/O banks. If you add a
And connect the chassis
Use this cable(1)
Second bank
Right to left
1769-CRLx
Right to right
1769-CRRx
Right to left
1769-CRLx
Right to right
1769-CRRx
Left to left
1769-CLLx
Third bank
(1) Where x = 1 for 1 ft (305 mm) or 3 for 3.28 ft (1 m).
1769 End Caps The final 1769 Compact I/O bank requires an end cap on the end without the expansion cable. The CompactLogix 5370 L2 controller comes with a right-end cap, so you do not need to order one separately. • Right end cap, catalog number 1769-ECR • Left end cap, catalog number 1769-ECL
32
Rockwell Automation Publication 1769-SG001S-EN-P - December 2016
Page 33
Select a CompactLogix System
1769 Wiring Systems As an alternative to buying removable terminal blocks (RTBs) and connecting the wires yourself, you can buy a wiring system of: • Interface modules (IFMs) that provide the output terminal blocks for digital I/O modules. Use the pre-wired cables that match the I/O module to the IFM. • Analog interface modules (AIFMs) that provide the output terminal blocks for analog I/O modules. Use the pre-wired cables that match the I/O module to the AIFM. • I/O module-ready cables. One end of the cable assembly is an RTB that plugs into the front of the I/O module. The other end has individually color-coded conductors that connect to a standard terminal block.
Removable Terminal Kits You can order removable terminal kits with the CompactLogix 5370 L1 and L2 controllers separately. The kits are used to connect wiring to the controllers. The following table describes the kits. Cat. Nos.
Controllers Supported
Description
1769-RTB45
CompactLogix 5370 L1
• Four 10-pin connectors that are used to connect wiring to the embedded digital I/O module of the controller. • One 5-pin connector that is used to connect an external 24V DC power source to the controller.
1769-RTB40DIO
CompactLogix 5370 L2
Four 10-pin connectors that are used to connect wiring to the embedded digital I/O module of the controller.
1769-RTB40AIO
1769-L24ER-QBFC1B and 1769-L27ERM-QBFC1B
Four 10-pin connectors that are used to connect wiring to the embedded analog I/O module of the controller.
Rockwell Automation Publication 1769-SG001S-EN-P - December 2016
33
Page 34
Select a CompactLogix System
5069 Compact I/O Modules You can install 5069 Compact I/O modules as local I/O modules in a CompactLogix 5380 control system. The 5069 Compact I/O architecture provides a wide range of input and output modules to span many applications, from high-speed digital to process control. The architecture uses Producer/Consumer technology that allows input information and output status to be shared among multiple Logix5000 controllers. The 5069 Compact I/O modules are installed to the right of a CompactLogix 5380 controller and require a separately sold removable terminal block (RTB) to connect field-side wiring. The modules draw system-side power, which is known as Module (MOD) power, and field-side power, which is known as Sensor Actuator (SA) power from the system backplane as needed. The modules then pass the remaining power to the next module in the system.
5069 Compact I/O DC Digital Modules Cat. No.
Inputs/Outputs
Voltage Category
MOD Current, Max
SA Power Current, Max
5069-IB16
16 inputs, sink
24V DC
75 mA
200 mA
5069-IB16F 5069-IB6F-3W
6 inputs, sink
150 mA per channel 900 mA module
5069-OB16
16 outputs, source
Local Actuator Power Current(1) 0.5 A per channel 8 A module
8 outputs (2 groups of 4)
Local Actuator Power Current(1) 2 A per channel 8 A per group 16 A per module
5069-OB16F 5069-OB8
(1) The module does not draw current from the SA power bus that is internal to the system. Local Actuator (LA+ and LA-) connections are used to supply field-side power to the module.
5069 Compact I/O AC Digital Modules Cat. No.
Inputs/Outputs
Voltage Category
MOD Current, Max
SA Power Current, Max
5069-IA16
16 inputs
120/240V AC
75 mA
240 mA
5069-OA16
16 outputs
120/240V AC
100 mA
4A
34
Rockwell Automation Publication 1769-SG001S-EN-P - December 2016
Page 35
Select a CompactLogix System
5069 Compact I/O Relay Output Modules Cat. No.
Outputs
Voltage Range
Module Power Current, Max
Sensor Actuator Power Current, Max
5069-OW4I
4 - Form A (normally open)
5…125V DC 5…264V AC
75 mA
–
5069-OW16
2 groups of 8 - Form A (normally open)
5…125V DC 5…264V AC
150 mA
5069-OX4I
4 - Form C (SPDT)
5…125V DC 5…264V AC
–
5069 Compact I/O Analog, Resistance, and Temperature Modules Cat. No.
Inputs/Outputs
Range
Resolution
5069-IF8
8 differential
Voltage ±10V 0…10V 0…5V
±10.5V: <320 μV/count (15 bits plus sign bipolar) 0…10.5V: <160 μV/count (16 bits unipolar) 0…5.25V: <80 μV/count (16 bits unipolar)
Current 0…20 mA 4…20 mA
0…21 mA: <0.32 μA/count (16 bits) 3.6…21 mA: <0.27 μA/count (16 bits)
Voltage ±10V 0…10V 0…5V
±10.5V: <320 μV/count (15 bits plus sign bipolar) 0…10.5V: <160 μV/count (16 bits unipolar) 0…5.25V: <80 μV/count (16 bits unipolar)
Current 0…20 mA 4…20 mA
0…21 mA: <0.32 μA/count (16 bits) 3.6…21 mA: <0.27 μA/count (16 bits)
RTD(1) (Input types PT 385, PT 3916, CU 427, NI 618, NI 672 available) 1…500 Ω 2…1000 Ω 4…2000 Ω 8…4000 Ω
< 7.9 mΩ/cnt in 1…500 Ω mode < 15.8 mΩ/cnt in 2…1000 Ω mode < 31.7 mΩ/cnt in 4…2000 Ω mode < 63.4 mΩ/cnt in 8…4000 Ω mode
5069-IY4
4 differential
Thermocouple (Input types B, C, D, E, J, K, N, R, S, T, TXK/XK (L) available) ±100 mV
Module Power Current, Max
Sensor Actuator Power Current, Max
75 mA
100 mA
< 3.1 μV/cnt in ±100 mV mode
Rockwell Automation Publication 1769-SG001S-EN-P - December 2016
35
Page 36
Select a CompactLogix System
Cat. No.
Inputs/Outputs
Range
Resolution
5069-OF4
4 current or voltage
Voltage ± 10V 0…10V 0…5V
16 bits across ± 10.5V - 320 μV/bit 16 bits across 10.5V - 160 μV/bit 16 bits across 5.25V - 80 μV/bit
Current 0…20 mA 4…20 mA 5069-OF8
8 current or voltage
Voltage ± 10V 0…10V 0…5V Current 0…20 mA 4…20 mA
Module Power Current, Max
Sensor Actuator Power Current, Max
75 mA
150 mA
16 bits across 21 mA - 320 nA/bit
250 mA 16 bits across ± 10.5V - 320 μV/bit 16 bits across 10.5V - 160 μV/bit 16 bits across 5.25V - 80 μV/bit 16 bits across 21 mA - 320 nA/bit
(1) Operating in 3-wire mode.
5069 Compact I/O Counter Module Cat. No.
Inputs/Outputs
Range
Frequency
Module Power Current, Max
Sensor Actuator Power Current, Max
5069-HSC2xOB4
2 quadrature (ABZ) differential inputs 4 channels (1 group of 4), sourcing outputs
18…32V DC
1 MHz, 125 ns pulse width min
50 mA
3 A(1)
(1) SA power current is drawn only when the embedded output channels are used.
5069 Compact I/O EtherNet/IP Adapter Cat. No.
Description
Module Power Current, Max
Sensor Actuator Power Current, Max
5069-AENTR
The adapter connects remote 5069 Compact I/O systems, to star, linear, and DLR EtherNet/IP network topologies.
220 mA
5 mA (DC power) 2 mA (AC power)
450 mA
10 mA (DC power) 25 mA (AC power)
5069-AEN2TR
36
Rockwell Automation Publication 1769-SG001S-EN-P - December 2016
Page 37
Select a CompactLogix System
5069 Compact I/O Specialty Modules Cat. No.
Description
Module Power Current, Max
Sensor Actuator Power Current, Max
5069-ARM
5069 Compact I/O address reserve module
45 mA
–
5069-FPD
5069 Compact I/O field potential distributor
–
10 mA (DC power) 25 mA (AC power)
For more information on how to use local 5069 Compact I/O modules, see the following: • 5000 Series Digital I/O Modules in Logix5000 Control Systems User Manual, publication 5000-UM004 • 5000 Series High-speed Counter Modules in Logix5000 Control Systems User Manual, publication 5000-UM005 • 5000 Series High-speed Counter Modules in Logix5000 Control Systems User Manual, publication 5000-UM006
5069 End Caps The right-most 5069 Compact I/O module in a CompactLogix 5380 control system requires an end cap. The end cap catalog number is 5069-ECR. An end cap ships with the CompactLogix 5380 controllers. You do not need to order one separately. However, you can order replacement 5069-ECR end caps.
Removable Terminal Kits You can order removable terminal kits with the CompactLogix 5380 controllers and 5069-FPD module separately. The kits are used to connect wiring to the controllers. The following table describes the kits. Cat. Nos.(1)
Device Supported
Description
5069-RTB14CJC-SCREW
5069 Compact I/O module
14-pin screw type terminal block with embedded CJC thermistors
5069-RTB14CJC-SPRING
14-pin spring type terminal block with embedded CJC thermistors
5069-RTB18-SCREW
18-pin screw type terminal block
5069-RTB18-SPRING
18-pin spring type terminal block
5069-RTB6-SCREW
5069-FPD module
5069-RTB6-SPRING
6-pin spring type terminal block
5069-RTB64-SCREW
(2)
5069-RTB64-SPRING 5069-RTB5-SCREW
(2)
(3)
5069-RTB5-SPRING
6-pin screw type terminal block
CompactLogix 5380 controllers 5069-AEN2TR EtherNet/IP adapter
4 and 6-pin screw type terminal block
5069-AENTR EtherNet/IP adapter
5-pin screw type terminal block
(3)
4 and 6-pin spring type terminal block
5-pin spring type terminal block
(1) All RTBs except for the 5069-RTB64-SCREW and 5069-RTB64-SPRING RTBs are sold in packs of 5 pieces. (2) Sold in packs of 1 piece. (3) Sold in packs of 2 pieces.
Rockwell Automation Publication 1769-SG001S-EN-P - December 2016
37
Page 38
Select a CompactLogix System
CompactLogix Power Supplies Select power supplies based on the controller and the number of additional I/O banks. For a
Select
CompactLogix 5370 L3 controller
• One 1769 power supply for the controller and local I/O modules. • One 1769 power supply for each additional bank of I/O modules.
CompactLogix 5370 L2 controller
No power supply as it is integrated to the controller package.
CompactLogix 5370 L1 controller
No power supply as it is integrated to the controller package.
CompactLogix 5380 controller
External power supplies to transfer MOD power and SA power to the system. The external power supplies are connected to a MOD power RTB and an SA power RTB that is installed on the controller.
Power Supplies Cat. No.
Description
Voltage Category
Operating Voltage Range
1769-PA2
1769 Compact I/O expansion power supply
120V/220V AC
85…265V AC
1769-PB2
24V DC
19.2…31.2V DC
1769-PA4
120V/220V AC
85…265V AC or 170…265V AC (switch selectable) 47…63 Hz
1769-PB4
24V DC
19.2…31.2V DC
For detailed specifications, see Compact Power Supplies Specifications Technical Data, publication 1769-TD008.
38
Rockwell Automation Publication 1769-SG001S-EN-P - December 2016
Page 39
CompactLogix System
Notes:
Page 40
Rockwell Automation Support Use the following resources to access support information. Technical Support Center
Knowledgebase Articles, How-to Videos, FAQs, Chat, User Forums, and Product Notification Updates.
www.rockwellautomation.com/knowledgebase
Local Technical Support Phone Numbers
Locate the phone number for your country.
www.rockwellautomation.com/global/support/get-supportnow.page
Direct Dial Codes
Find the Direct Dial Code for your product. Use the code to route your call directly to a technical support engineer.
www.rockwellautomation.com/global/support/direct-dial.page
Literature Library
Installation Instructions, Manuals, Brochures, and Technical Data.
www.rockwellautomation.com/literature
Product Compatibility and Download Center (PCDC)
Get help determining how products interact, check features and capabilities, and find associated firmware.
www.rockwellautomation.com/global/support/pcdc.page
Documentation Feedback Your comments will help us serve your documentation needs better. If you have any suggestions on how to improve this document, complete the How Are We Doing? form at http://literature.rockwellautomation.com/idc/groups/literature/documents/du/ra-du002_-en-e.pdf.
Rockwell Automation maintains current product environmental information on its website at http://www.rockwellautomation.com/rockwellautomation/about-us/sustainabilityethics/product-environmental-compliance.page. 1336 PLUS, Allen-Bradley, Armor, ArmorBlock, ArmorPOINT, ArmorStart, ArmorStratix, Compact I/O, CompactLogix, ControlLogix, Data Highway Plus, DPI, FactoryTalk, Guard I/O, GuardLogix, Integrated Architecture, Kinetix, LISTEN. THINK. SOLVE., Logix5000, On-Machine, PanelView, POINT Guard I/O, POINT I/O, POINTBus, PowerFlex, Rockwell Automation, Rockwell Software, SCANport, Stratix, Studio 5000 Logix Designer, and SynchLink are trademarks of Rockwell Automation, Inc. ControlNet, DeviceNet and EtherNet/IP are trademarks of ODVA, Inc. Trademarks not belonging to Rockwell Automation are property of their respective companies.
Publication 1769-SG001S-EN-P - December 2016 Supersedes Publication 1769-SG001R-EN-P - October 2015
Copyright © 2016 Rockwell Automation, Inc. All rights reserved. Printed in the U.S.A.