Troubleshooting Your Input Module Chapter Objective

In this chapter, we describe how to troubleshoot your module by:

• • • • •

Diagnostics Reported by the Module observing the indicators monitoring status bits reported to the processor. checking module operation checking for common mode voltages isolating a bad input

At power-up, the module momentarily turns on the red indicator as a lamp test, then checks for:

• correct RAM operation • firmware errors Thereafter, the module lights the green RUN indicator when operating without fault, or lights the red FAULT indicator when it detects fault conditions. The module also reports status and specific faults (if they occur) in every transfer of data (BTR) to the PC processor. Monitor the green and red indicators and status bits in word 1 of the BTR file when troubleshooting your module.

&

Diagnostic Bits Reported By the Analog Input Module Diagnostic bits in the read block transfer status words provide diagnostic capabilities. Word 1 provides power-up and valid data status. Words 2, 3 and 4 provide channel data status. If a module on-board self test fault occurs, block transfers will be inhibited, the red fault (FLT) will light, and the green run (RUN) light will go out. Word 1 Diagnostics word 1 is the first data word in the read block transfer file for transfer to the central processor. It contains a power-up bit (bit 00) that is set (1) when the module is first powered up. It is reset (0) after a write block transfer. It also contains an under-range or over-range bit (bit 01) that is set when any input is under or over-range.

Page 52

7–2

Troubleshooting Your Input Module

An invalid scaling data bit (bit 02) is set if invalid scaling data is entered into any of the minimum/maximum scaling value words. Note that minimum equal to maximum is an invalid value. If invalid values are entered into the minimum or maximum scaling words the corresponding read block transfer input channel word will be set to 0000. Bit 02 is set if an invalid digital filter value is entered (e.g., 1F). If an invalid digital filter value is entered, the module will not perform digital filtering. The real time sample (RTS) fault bit (bit 03) is set if the module is configured for RTS and a block transfer read has not occurred within the user-programmed period. Bit 04 is the calibration status bit. This bit is reset (0) when a successful calibration is completed. If the bit is set (1), an incorrect voltage/current was applied, or offset and gain calibrations were attempted together. The EEPROM status bit (05) is set when an error occurs when saving calibration data to nonvolatile memory. If this bit is set at powerup, the EEPROM data did not pass checksum and calibration values are being used. The hardware failure bit (06) is set when a blown fuse is detected, or when the EEPROM can’t recover from a fault. Word 2 Word 2 provides for under-range conditions. When a particular channel input is under-range, the associated bit will be set. As long as inputs are under range the associated bit remains set. Bit 00 corresponds to channel 1, bit 01 to channel 2, etc. Word 3 Word 3 provides for over-range conditions. When a particular channel input is over-range, the associated bit will be set. As long as inputs are in range the associated bit remains reset. Bit 00 corresponds to channel 1, bit 01 to channel 2, etc. Word 4 Word 4 provides an indication of a particular channel’s input polarity (set, or 1 = negative; reset, or 0 = positive). Bit 00 corresponds to channel 1, bit 01 to channel 2, etc.

-

Page 53

Troubleshooting Your Input Module

7–3

The following table lists the probable cause and recommended actions for some common trouble indications. Troubleshooting Chart for Analog Input Module (1771-IFE/C) Legend -!! -( &$(%$("

Indicators

Probable Cause

Recommended Action

)*

)(

+

$(

-.+( !)+ +

) *)0 +

)!! *)0 +- ')/ + $(, $(-) -.+( *)0 +- ! ' ,-$&& 1$,-, *)0 + ,.**&2 $, *+)* +&2 + -.+( -# !)+ +

$-# + , )(

Page 54 read from a scan by OCR; it may hold reading errors

7-4 Troubleshooting Your Input Module

Checking Module The following allows you to run a check on module operation, and Operation isolate a fault either to the module or external to the module.

Connect the Module in a Simple Test System

Set up a 1771 I/O chassis with a PLC-5 processor in the leftmost slot.

Set the chassis backplane switch 5 to ON. All other backplane switches to Off.

1 This sets the chassis to 1-slot addressing.

Note: Check the processor screen to verify that the processor is set for 1-slot addressing.

l , m7no 20 Off [I= Switches ae Oe Nl of i 5 Addressing ways Ct OFF OFF | 2:slot ae 1-slot tl oe oF esa N FF slo {| ie |}. Off cris OFF OFF Al Off cot ue processor. These slots guide the 1771-IFE/C module into position.

2. Place the module in the card guides on the top and bottom of the first slot next to the

Important: Apply firm even pressure on the module to seat it into its backplane connector.

[ 1771-A1B, -A2B, -A3B, -A3B1, -A4B I/O chassis | locking tab card guides cn aod

PLC-5 Processor

IFE module

Snap the chassis latch over the top of the module to secure it.

Pressed in on right ON (closed)

Pressed in on left OFF (open)

[ 1771-A1B, -A2B, -A3B1, -A4B Series B I/O chassis | locking bar pin card guides atl

PLC-5 Processor locking bar

IFE module

Swing the chassis locking bar down into place to secure the modules. Make sure the locking pins engage., _19809

After inserting the module into the slot, apply power to the chassis.

Publication 1771-6.5.115 - February 1999

Page 55 read from a scan by OCR; it may hold reading errors

Troubleshooting Your Input Module

7-5

3 | Enter the following ladder logic into the processor.

ae A i BLOCK TRANSFER WRITE A: yt RACK: oo | EN) Note: This programming is only to test EN EN GROUP: 0 We Plow ree ane read functions. MODULE: 0 {DN} is not intended for regular use. CONTROL BLOCK: BT9:0 (eR DATA FILE: N7:0 ) LENGTH: 0 CONTINUOUS: N UE UE i BLOCK TRANSFER READ VE VE EN AN RACK: 09 [AEN, GROUP: 0 MODULE: 0 |(0N) CONTROL BLOCK: BT9:1 DATA FILE: n740 | AER}, LENGTH: 0 CONTINUOUS: N The module lights the green RUN indicator when operating without fault, or lights the red FAULT indicator when it detects fault conditions. If the module is operating correctly, the module will be receiving BTRs and sending BTWs. The indicator light will indicate green/flashing green. If the indicator is blinking green, the module RUN has not received a configuration block transfer write. FLT Cc 5 This configuration sets the IFE module for: 1-5V range Block Transfer Write Single-ended inputs BCD data format ia a No digital filter Data Table Report PLC-5/11 Addr 4. FE Data Table File N7:0 No real time sampling 0-4095 scaling . a ADDRESS 0 1 2 3 4 5 6 7 8 Monitor the status bits in word 1 of the BTR file when troubleshooting your module. en troubleshooting y N7:0 0 0 0 0 0 0 16533 0 16533 Write block transfer N7:10 16533 0 16533 0 16533 0 16533 0 16533 configuration data N7:20 16533 0 16533 0 16533 0 16533 0 16533 N7:30 16533 0 16533 0 16533 0 16533 0 0 N7:40 2 -1 0 0 oOo 60 0 0 0 N7:50 0 0 0 0 0 0 0 oO 0 Read block N7:60 0 0 0 0 0 0 0 0 0 transfer data N7:70 0 0 0 0 0 0 0 0 0 N7:80 0 0 0 0 0 0 0 0 0 N7:90 0 0 0 0 0 0 0 0 0 N7:100 0 0 0 0 0 0 0 0 0

Note: 1653349 = 409546 (BCD)

Ne

\ Oo SS SSS eo

Note: If all input terminals are shorted together and tied to module common, the input data for all channels will read zero.

Publication 1771-6.5.115 - February 1999

Page 56 read from a scan by OCR; it may hold reading errors

7-6 Troubleshooting Your Input Module the PC processor. Monitor the green and red indicators and the status bits in word 1 of the BTR

6 The module also reports status and specific faults (if they occur) in every transfer of data (BTR) to file when troubleshooting your module.

Block transfer control files

Attach the wiring arm (1771-WG) to the horizontal bar at the bottom of the I/O chassis.

The wiring arm pivots upward and connects with the module so you can install or remove the module without disconnecting the wires.

(vate Report PLC-5/11 Addr 4 IFE Data Table File N7:0 ADDRESSEN ST DN ERCO EWNR TO RWRLENDLEN FILE ELEM R G M

BT9:0 01100111 00 0 37 7 0000 BT9:1 11000 11 0 1 0 20 7 +400 00 BT9:2 00000 000 0 0 0 0000

7

Memory Map Report PLC-5/11 Addr 4 IFE Data Table File N7:0

FILE TYPE LASTADDRESS _ SIZE (elements) SIZE (words)

output 0:037 32 38 input 1:037 32 38 status $:127 128 134 binary or bit © B3/15 1 7 timer T4:0 1 9 counter C5:0 1 9 control R6:0 1 9 integer N7:103 104 110 floating point + F8:0 1 8

BT block transfer BT9:2 3 24

T1™2Z2DVDO7AWN - "O

[ oeisHssunue horizontal bar ae install

After connecting the field wiring arm to the module, proceed to check the module operation when receiving inputs.

Publication 1771-6.5.115 - February 1999

Page 57

Troubleshooting Your Input Module

Checking for Common Mode Voltages

7–7

Common mode voltage on any input must not exceed +14.25V as referenced to module common (terminals 20 and 21). Common mode voltages occur when the ground potentials of current transmitter and/or voltage device power sources are at differential potentials (as referenced to module common). The resulting ground currents can cause voltage potentials at the input terminals. Observe the following guidelines whenever possible to prevent common mode voltages:

• use single-ended mode • use 2-wire transmitters with a common power supply • separate 2-wire and 4-wire transmitters between different modules • tie 4-wire transmitter and/or separate power supply grounds together

Affect of Common Mode Voltage on Inputs If common mode voltage exceeds +14.25V on any input, channel to channel crosstalk can occur. All channel input data in the programmable controller data table could be invalid. Incorrect overrange and underrange bits could also occur (#

--

""-

-

(#

-

-

-

-

-

-

-

- -

- -

- -

- -

-

- -

-

(#

(+!' 1&/% !+**#!/#" /+ )+"0(# !+))+*

(+!' 1&/% - &*,0/ !+**#!/#" /+ !+))+*

--

""-

-

(#

-

-

- -

- -

- -

- -

-

-

-

-

-

(+!' 1&/% - &*,0/ !+**#!/#" /+ )+"0(# !+))+* (#

--

-

""-

(#

-

-

-

- -

- -

- -

- -

- -

- -

-

-

-

- -4

Page 58

7–8

Troubleshooting Your Input Module

Troubleshooting a Bad Input

A noise spike which exceeds +14.25V on an input will also cause crosstalk to occur. This transient condition will affect all inputs. Refer to publication 1770-4.1, “Wiring and Grounding Guidelines for Noise Immunity.”

After determining that the module is operating correctly, troubleshoot any faulty inputs by:

• measuring each input with respect to module common • disconnecting inputs from the field wiring arm one at a time while observing module action • testing for input channel functionality

Measuring Each Input with Respect to Module Common During this procedure, monitor the input data table of the programmable controller and observe any changes which occur. 1. Make sure the field wiring arm is in position on the module. 2. Apply power to the 1771 I/O chassis. 3. Check each input (either single-ended or differential) for common mode voltages exceeding +14.25V with respect to module common. A. Hold the positive probe of the voltmeter on the first input terminal. B. Hold the negative probe of the voltmeter on a module common terminal (terminals 20 or 21). 4. If any voltage is seen that exceeds +14.25V, remove that channel’s input wiring and observe the affect on the input data table of the programmable controller.

!

ATTENTION: Remove power from the 1771 I/O chassis backplane and field wiring arm before removing or installing input wiring.

• Failure to remove power from the backplane or wiring arm could cause module damage, degradation of performance, or injury. • Failure to remove power from the backplane could cause injury or equipment damage due to possible unexpected operation.

If no other common mode voltages are present, the input data for all other channels should stabilize to some predictable value.

-

Page 59

Troubleshooting Your Input Module

7–9

5. Attempt to equalize all grounds at the offending channel before reconnecting the input wiring.

!

ATTENTION: Remove power from the 1771 I/O chassis backplane and field wiring arm before removing or installing input wiring.

• Failure to remove power from the backplane or wiring arm could cause module damage, degradation of performance, or injury. • Failure to remove power from the backplane could cause injury or equipment damage due to possible unexpected operation.

6. If the common mode voltage cannot be removed on the input, an isolation device may be required on that channel.

Disconnecting Inputs from the Field Wiring Arm One at a Time While Observing Module Action During this procedure, monitor the input data table of the programmable controller and observe any changes which occur. 1. Make sure the field wiring arm is in position on the module. 2. Apply power to the 1771 I/O chassis. 3. While observing the input data table, remove one input at a time.

!

ATTENTION: Remove power from the 1771 I/O chassis backplane and field wiring arm before removing or installing input wiring.

• Failure to remove power from the backplane or wiring arm could cause module damage, degradation of performance, or injury. • Failure to remove power from the backplane could cause injury or equipment damage due to possible unexpected operation.

4. When the offending input channel is disconnected, the input data table will stabilize to some predictable values.

-

Page 60

7–10

Troubleshooting Your Input Module

Testing for Input Channel Functionality To test the functionality of an input channel: 1. Remove the input wiring from the field wiring arm.

!

ATTENTION: Remove power from the 1771 I/O chassis backplane and field wiring arm before removing or installing input wiring.

• Failure to remove power from the backplane or wiring arm could cause module damage, degradation of performance, or injury. • Failure to remove power from the backplane could cause injury or equipment damage due to possible unexpected operation.

2. Connect a battery (or other voltage source) across the input terminals. When the 4-20mA range is selected, the voltage source must not exceed 1-5V.

!

ATTENTION: The voltage source must be within the selected voltage range. If the source voltage is greater than the selected voltage range of the input, module damage will result.

3. Monitor the input data table for predictable values.(values relative to the input source voltage).

Chapter Summary

-

In this chapter you learned how to interpret the indicator lights, and troubleshoot your input module.