Manual · Allen-Bradley
Analog Input Module (Cat. No. 1771-IFE Series C) User Manual
Manual82 pagesPDF 727 KB
User manual for the Allen-Bradley 1771-IFE Series C analog input module: installing, programming, configuring, calibrating and troubleshooting.
What this file really is
The old site listed this file as a manual for the Allen-Bradley 1771-AL. Filed as a 1771-AL manual, but it is the user manual for the 1771-IFE Series C Analog Input Module; the 1771-AL local adapter is mentioned only as one not to use with it.
Filed with · 1 model
Also filed with these models on the old site
Summary
What is in it
Allen-Bradley user manual for the 1771-IFE Series C Analog Input Module, an intelligent block transfer module for 1771 I/O chassis. It helps you install, program, calibrate and troubleshoot the module, with block transfer programming for PLC-2, PLC-3 and PLC-5 processors, configuration of input ranges, data format, digital filtering, real time sampling and scaling, the block transfer read format, specifications and the differences between Series A, B and C modules. The 1771-AL is named only as a local adapter not to use with this module.
Its parts
- Overview of the Analog Input Module
- Installing the Input Module
- Module Programming
- Configuring Your Module
- Module Status and Input Data
- Calibrating Your Module
- Troubleshooting Your Input Module
From the manual
Key facts from this manual
Some pages are scans or cannot be read; this says only what the readable text supports. Each line names its page in the PDF.
Allen-Bradley user manual for the 1771-IFE series C analog input module (publication 1771-6.5.115, February 1999), not a manual for the 1771-AL. It covers installing, programming, configuring, calibrating and troubleshooting the module, and names the 1771-AL only to say the module must not be used with it. Several pages have a scrambled text layer.
- Module
- 1771-IFE series C analog input module, a single-slot block transfer module for any 1771 I/O chassis p. 9, 10
- Inputs
- 16 single-ended or 8 differential p. 61
- Voltage ranges
- +1 to +5V, 0 to +5V, -5 to +5V, -10 to +10V, 0 to +10V dc p. 61
- Current ranges
- +4 to +20mA, 0 to +20mA, -20 to +20mA p. 61
- Resolution
- 12-bit binary; 12 bits plus sign on bipolar ranges p. 61
- Accuracy
- 0.1% of full scale range at 25 C p. 61
- Backplane current
- 500mA at +5V from the I/O chassis backplane p. 14, 61
- Input impedance
- Over 10 megohms on voltage ranges; 250 ohms on current ranges p. 61
- Internal scan rate
- 13.7ms for 8 differential or 27.4ms for 16 single-ended inputs, plus 0.3ms with filtering p. 61
- Overvoltage protection
- 200V in voltage mode; 8V in current mode p. 61
- Operating temperature
- 0 to 60 C (32 to 140 F) p. 62
- Wiring arm
- 1771-WG field wiring arm; conductors up to 14 gauge (2mm2) stranded p. 62
- Power dissipation
- 2.5 Watts maximum (8.52 BTU/hr) p. 61
- Factory setting
- Shipped set for voltage mode and Series C applications p. 14
What this manual walks you through
- How block transfers move data between processor and module p. 11, 12
- Checking chassis power and choosing a slot p. 14, 15
- Setting the configuration plugs for voltage or current inputs p. 15
- Reading the RUN and FAULT indicators p. 51
- Interpreting the diagnostic bits in the read block transfer words p. 51, 52
- Checking for common mode voltages p. 57
- Isolating a bad input one channel at a time p. 58, 59
- Testing an input channel with a voltage source p. 60
Good to know
- The manual says not to use this module with the 1771-AL PLC-2/20, 2/30 local adapter. p. 9
- Single-ended and differential inputs must not be mixed on the module. p. 15
- With 2-slot addressing, the module must not share an I/O group with a discrete high-density module. p. 15
- Common mode voltage above +14.25V on any input can cause crosstalk and invalid data for all channels. p. 57
- Passive transducers need loop power supplied by the user. p. 10
Questions this manual answers
Can the 1771-IFE be used with a 1771-AL adapter?
No. The manual says not to use the 1771-IFE series C with the 1771-AL PLC-2/20, 2/30 local adapter. p. 9
How much backplane current does the 1771-IFE series C draw?
It needs 500mA at +5V from the I/O chassis backplane. p. 61
What input ranges does the 1771-IFE series C support?
Voltage ranges +1 to +5V, 0 to +5V, -5 to +5V, -10 to +10V and 0 to +10V dc; current ranges +4 to +20mA, 0 to +20mA and -20 to +20mA. p. 61
What does the red FAULT light on the 1771-IFE mean?
The module has detected a fault. On a self-test fault, block transfers are inhibited and the green RUN light goes out. p. 51
Contents
Chapters and sections
Each line opens the PDF at its page.
- 1771-6.5.115, Analog Input Module, User Manual1
- Important User Information2
- Summary of Changes3
- Preface - Using This Manual7
- 1 - Overview of the Analog Input Module10
- 2 - Installing the Input Module13
- 3 - Module Programming27
- 4 - Configuring Your Module33
- 5 - Module Status and Input Data43
- 6 - Calibrating Your Module46
- 7 - Troubleshooting Your Input Module51
- A - Specifications61
- B - Differences Between Series A and B Modules and Series C Modules63
- C - Programming Examples64
- D - Data Table Formats68
- E - Block Transfer (Mini-PLC-2 and PLC-2/20 Processors)71
- F - Forms74
- Index77
- Allen-Bradley Publication Problem Report79
- Business Reply Card80
- Support Services81
- Back Cover82