For the Allen-Bradley 1771-ASB
Page 79
Appendix Cc
Differences Between 1771-ASB Series A, B, C, D and E Remote I/O Adapter Modules
Major differences between series are noted in the table below.
Table C.A Major Differences Between 1771-ASB Series Adapters 1771-ASB Series A Series B Series C Series D Series E Functional Initial release Firmware change Hardware and Firmware change Hardware change Changes 9 firmware change | Added CE certification Added C-Tick certification Restrictions or Supports only 1 or 2 . limitations slot addressing Supports 1/2, 1 or 2 slot addressing Hardware Does not support 32 eis Does support 32 bit digital I/O Compatibility bit digital 1/0 Does support 32 bit digital /O Can emulate series B adapter Communication 57.6kbits/s 57.6kbits/s Rate 115.2kbits/s 115.2kbits/s . 230.4kbits/s Certifications CSA Hazardous Class I, Div 2 oe Hazardous Class |, Div 2 Backplane Current 1.2A @ 5V de 1.0A @ 5V de _ 5,000ft @ 115.2kbits/s 5,000 @ 115.2kbitsis Chassis Distance 10,0008 @ 57.6kbits/s 10,000ft @ 57.6kbits/s , . 2,500ft @ 230.4kbits/s Thermal 20.47 BTU/hr 17.06 BTU/hr Dissipation Power Dissipation 6W 5W
Publication 1771-UM001A-US-P - February 2000
Page 80
C-2 Differences Between 1771-ASB Series A, B, C, D and E Remote I/O Adapter Modules
Publication 1771-UM001A-US-P - February 2000
Page 81
Appendix
-
D
This appendix presents some of the most commonly asked questions about application and operation of the Remote I/O Adapter Module.
Questions and Answers
The following questions and answers do not cover all possible questions, but are representative of the more common ones. Q. What happens to my inputs and outputs when an adapter communication failure occurs? A. On a communication failure, inputs in this rack will appear in the processor input image table in the last state they were reported to be in before the failure. Outputs in this rack will either remain in their last state or be turned off, depending on the I/O chassis backplane switch setting for output last state. Q. Is there a way to monitor my remote rack status and take appropriate action if there is a rack fault or a communication failure? A. Yes. Processor rack fault bits can be monitored. Communication failure can be detected by monitoring the program’s block transfer error bit. A diagnostic step array and timer can be programmed to monitor the status of changing digital inputs. In all cases, the appropriate action can be taken, i.e. program a fault routine. Q. I just replaced my series B adapter with a series E adapter, and now my block transfers are timing out (block transfer error code –9). What’s wrong? A. Certain scanner modules require series B emulation which includes a delay to provide the scanner sufficient time to service all of its communication ports. If you are using a 1772-SD2, 1775-S4, 1775-S4A, 1775-S5, 1775-SR5 or 1775-SR scanner, set the link response for unrestricted or series B emulation (switch S2, position 5 on).
Page 82
D–2
Questions and Answers
Q. I just added a rack to my remote I/O network and my PLC-5 scanner channel autoconfiguration does not recognize it. Why not? A. This is typically the result of installation and configuration problems. Anything from adapter power, wiring and connections, terminations, improper setting of adapter and chassis module switches. Use the scanner and adapter status indicators as a troubleshooting tool. Easy checks include 1.) installing a known to be good adapter into this chassis, or 2.) start from scratch by saving the program, clearing the processor memory by removing the battery, creating an I/O status file, configuring the scanner channel and autoconfigure. Sometimes just creating a new I/O status file works. You could also check this adapter alone with the scanner without a program in the processor, and without a module in the chassis. Also, insure that the processor and its I/O image table suppport the rack address you are adding and that the rack inhibit bit is not set. Expand the image table and remove the rack inhibit as necessary. Q. I am adding a new remote rack to my RIO network. Do I have to shut my process down to install it? A. Yes, the processor must be in Program mode to either manually add or autoconfigure remote I/O devices on the network. Q. I just added a rack to my RIO network and my block transfer data throughput has slowed down considerably. Why? A. Block transfer throughput is determined by a number of things, including how many adapters are on the network, how many block transfer modules are in each chassis, communication rate and number of block transfer words being transferred. Refer to your processor user manual to determine the worst case throughput and recommendations on how to optimize throughput. Q. I am adding a new remote rack to my RIO network. Since this rack is in close proximity to one of my adapters in the middle of my link, can I wire it directly to that adapter? A. No, you can’t. Star connections are not allowed on remote I/O. Daisy-chain or trunkline-dropline configurations are the only ones permitted.
Page 83
Questions and Answers
D–3
Q. My remote I/O is working fine without termination resistors. Are they really required? A. Yes, termination resistors are required. Any change in the RIO network installation (i.e. cable length, baud rate) can cause a remote I/O communication failure without proper termination. Installing termination resistors reduces the chance of this occurring. Q. I have an existing PLC remote I/O system that I’m replacing with 1771. Are the new adapters compatible with the older processors? A. Any remote I/O adapter is compatible with any processor. Any and all series/revisions of remote I/O adapter devices can be mixed on the blue hose. Make sure you set the adapter switches correctly, since switch positions may have changed on later adapters. Also, older racks and adapters only support 2 slot addressing and 8 pt. modules, while newer racks and adapters and racks have no such restrictions. Q. I’m replacing an existing PLC-2 remote I/O system with new PLC-5 processors. Will the new processors work with the older 1771-ASB adapters? A. Again, any processor will work with any series/revision remote I/O adapter. Watch your switch settings. Old power supplies can be used to power your adapters, but cannot be used to power the rack containing a PLC-5 processor. PLC-5 processors must be powered by slot power supplies or by a 1771-P7 supply. Q. Specifications for my processor state that it can support 24 logical racks, but it won’t accept any rack addresses over rack 17 (16 physical racks). A. This is a processor limitation. Each RIO channel is limited to 16 logical racks which can be scanned by the channel. The additional racks can be scanned on another RIO channel, if practical. Q. How do I add a 1771-ASB adapter module to my ControlLogix remote I/O network? A. Simply add the adapter under the 1756-DHRIO scanner in the Logix5550 Controller Organizer I/O configuration tree. With the scanner, adapter and chassis switches set correctly, download the program to the Logix5550 processor and switch to Run mode. Communication to the adapter will commence.
Page 84
D–4
Questions and Answers
Q. How do I add a 1771-ASB adapter module to my SLC 1747-SN scanner remote I/O network? A. Enter the correct rack number, rack size and starting group in the SLC500 program I/O configuration G-file data screen. With the correct communication rate set on the scanner, download the program to the SLC processor and switch to Run mode. Communication to the adapter will commence. Q. Ever since I installed fiber optics on my remote I/O network, the adapters won’t communicate. A. This is probably an installation issue. Check your installation for the correct application, connection and termination of fiber optic cable, and the correct setup of the fiber optic module (1771-AF, -AF1). Make sure that no length of blue hose on this network is less than 10ft long, including the blue hose connections from the processor, scanner or adapter to the fiber optic module in the same chassis. Q. I have a 12-slot chassis but only the modules in the first 8 slots are recognized by my program. A. Check the scan switch (switch S2, position 4) for correct setting. It probably is set ON “scan all but the last 4 slots.” Set it to OFF. Q. I just installed a 1771-IL series B analog input module in my remote I/O chassis which already has a 1771-ASB series A adapter. Now my block transfers to this module are erroring. A. Adapter modules prior to series C, firmware revision D, are not compatible with the following modules:
-
Page 85
Questions and Answers D-5
1771-QD Series A and B 1771-QDC Series A
1771-QH Series A
1771-TCM Series A 1771-VHSC, VHSCK Series A 1771-WS Series A
Publication 1771-UM001A-US-P - February 2000
Page 86
D-6 Questions and Answers
Publication 1771-UM001A-US-P - February 2000