The Allen-Bradley user manual for the 1771-ASB Series E Remote I/O Adapter Module, which links 1771 I/O chassis to a programmable controller over remote I/O. It covers the module's features and indicators, installation (power, keying, configuration plugs, module and chassis switches, field wiring arm, terminator), the 2-slot, 1-slot and 1/2-slot addressing modes with complementary I/O, and troubleshooting with the indicator lights. Appendices give specifications, switch settings for earlier series A to D adapters and the differences between series.
Its parts
- Introducing the Remote I/O Adapter Module
- Installing Your Module
- Addressing Modes for Your Remote I/O
- Troubleshooting
From the manual
Key facts from this manual
Some pages are scans or cannot be read; this says only what the readable text supports. Each line names its page in the PDF.
User manual (publication 1771-UM001A-US-P, February 2000) for the Allen-Bradley 1771-ASB Series E remote I/O adapter module. It walks through setting the configuration plugs and switches, wiring and terminating the remote I/O link, installing the module and troubleshooting with the indicator lights. Appendices give the specifications and answers to common questions.
- Device
- Series E remote I/O adapter, the interface between remote 1771 I/O modules and programmable controllers p. 11
- Chassis distance
- 2500 ft at 230.4K baud; 5000 ft at 115.2K baud; 10000 ft at 57.6K baud p. 61
- Backplane current
- 1.0A at 5V dc p. 15
- Location
- Leftmost slot of the I/O chassis p. 15
- Keying
- Upper connector between 54 and 56; lower connector between 16 and 18 p. 15
- I/O support
- Any mix of 4, 6, 8, 16 or 32-point I/O; 1/2-slot, 1-slot and 2-slot addressing p. 11
- Indicators
- ACTIVE (green), ADAPTER FAULT (red), I/O RACK FAULT (red) p. 12
- Field wiring arm
- 1771-WB, with connections for the I/O communication cables and a user-supplied chassis restart pushbutton p. 13
- Interconnect cable
- 1770-CD p. 61
- Terminator
- 150 ohm at both ends of the link, or 82 ohm where supported (allows up to 32 physical devices) p. 28
- Power dissipation
- 5 Watts p. 61
- Compatible processors
- PLC-2/20, PLC-2/30, PLC-3, PLC-5 family, PLC-5/250, ControlLogix 5550 family, SLC family p. 6
- Compatible chassis
- 1771-A1, -A1B, 1771-A2, -A2B, 1771-A3B, -A3B1, 1771-A4, -A4B p. 6
- Scan options
- Scans all slots or all but the last four; can emulate a series B adapter for 1771-S4A and -S4B scanners p. 11
What this manual walks you through
- Setting the configuration plugs for 32-point or 1771-IX and -IY modules p. 16
- Setting switch assemblies S1 and S2: rack number, first I/O group, baud rate, scan and link response p. 16, 17, 18
- Wiring the field wiring arm p. 26, 27
- Installing the terminator resistor on the last adapter p. 28
- Installing the module in the I/O chassis p. 29
- Troubleshooting with the indicator lights p. 57, 58, 59
- Getting PLC-5 autoconfigure, 1747-SN and 1756-DHRIO scanners to recognize the adapter p. 60
- Answers to common application and operation questions p. 81, 82, 83, 84
Good to know
- 32-point I/O modules and 1771-IX or 1771-IY thermocouple modules cannot be used together; the 1771-IXE works with 32-point modules. p. 16
- Do not remove or insert the adapter while system power is on. p. 27
- Devices running at 230.4K baud need 82 ohm terminators. p. 28
- Star connections are not allowed on remote I/O; only daisy-chain or trunkline-dropline layouts. p. 82
- Mixing 1771-ASB and 1771-AS adapters in one remote system limits it to 115.2k baud or less. p. 6
Questions this manual answers
Block transfers time out after replacing a series B 1771-ASB with series E. Why?
Some scanners need series B emulation. With a 1772-SD2, 1775-S4, 1775-S4A, 1775-S5, 1775-SR5 or 1775-SR scanner, turn on switch S2, position 5. p. 81
Why are only the first 8 slots of a 12-slot chassis recognized?
The scan switch (S2, position 4) is probably ON, scanning all but the last 4 slots. Set it to OFF. p. 84
How far can a 1771-ASB be from the scanner?
2500 ft at 230.4K baud, 5000 ft at 115.2K baud and 10000 ft at 57.6K baud. p. 61
What does it mean when all three 1771-ASB indicators are on?
The module is not communicating because of an incorrect baud rate setting; check the switch setting. p. 58
Does the process have to stop to add a remote rack?
Yes. The processor must be in Program mode to add or autoconfigure remote I/O devices. p. 82
Contents
Chapters and sections
Each line opens the PDF at its page.
- 1771-UM001A-UM, Remote I/O Adapter Module, User Manual1
- Important User Information2
- Preface - Using This Manual3
- 1 - Introducing the Remote I/O Adapter Module11
- 2 - Installing Your Module15
- Chapter Objectives15
- Power Requirements15
- Module Location and Keying15
- Setting the Module Configuration Plugs16
- Setting the Module Switches16
- Setting the I/O Chassis Switches23
- Setting the I/O Chassis Power Supply Configuration Plug26
- Wiring the Field Wiring Arm26
- Installing the Terminator28
- Compatibility of 1771 Remote I/O Products with Extended Node Numbers28
- Module Installation29
- Summary29
- 3 - Addressing Modes for Your Remote I/O31
17 more lines, from page 54 on
- Acceptable Chassis Combinations54
- 4 - Troubleshooting57
- A - Specifications61
- B - Settings for 1771-AS and 1771-ASB Series A, B, C and D Remote I/O Adapters63
- C - Differences Between 1771-ASB Series A, B, C, D and E Remote I/O Adapter Modules79
- D - Questions and Answers81
- E - CSA Hazardous Location Approval87
- Index89
- Publication Problem Report91
- Business Reply Mail92
- Back Cover94
The whole text · 13 parts
Read the manual here as text
Its text as extracted from the PDF, unedited, in parts; each page opens the PDF at that page.
- Pages 1 to 81-8
- Pages 9 to 149-14
- 2 - Installing Your Module, pages 15 to 2215-22
- 2 - Installing Your Module, pages 23 to 3023-30
- 3 - Addressing Modes for Your Remote I/O, pages 31 to 3931-39
- 3 - Addressing Modes for Your Remote I/O, pages 40 to 4840-48
- 3 - Addressing Modes for Your Remote I/O, pages 49 to 5649-56
- 4 - Troubleshooting57-60
- Pages 61 to 6961-69
- Pages 70 to 7870-78
- Pages 79 to 8679-86
- Pages 87 to 9087-90
- Pages 91 to 9491-94
The file