For the Allen-Bradley 1771-ASB
Page 40
3–10
Addressing Modes for Your Remote I/O
Follow these guidelines when configuring your remote system with complementary I/O chassis:
• Assign the complementary I/O rack number to a chassis of equal or smaller size than the primary chassis. • If the complementary chassis is smaller than the primary one, set the last chassis switch on the complementary chassis to the ON position, unless the adapter is in the faulted I/O search mode. • For PLC-2 family processors: • Connect the complementary chassis to the same scanner channel as the primary chassis. • Connect the complementary chassis to the remote trunkline as though they were additional primary chassis. • For PLC-3 processors, connect the complementary chassis to a different scanner channel as the primary chassis. • Assign the same beginning I/O group number to both I/O racks. • You cannot configure complementary I/O in a chassis that uses a combination of 2-slot addressing and 16-point I/O. • You cannot use 32-point I/O modules in a complementary I/O configuration when you select 2-slot or 1-slot addressing. • You can place an output module opposite another output module; they reflect the same bits in the output image table. • Do not place an input module opposite an input module. You can use the following modules in either primary or complementary I/O chassis opposite any type of module:
Catalog Number
Description
*,0/
+0,(" *,0/
+!"-
.
"
Page 41
Addressing Modes for Your Remote I/O
3–11
Module Placement with 2Ćslot Addressing Figure 3.9 shows possible module placement when configuring complementary I/O with 2-slot addressing. Figure 3.9 Complementary I/O Configurations with 2Ćslot Addressing / (+ / 5 - *- 1 ' 0 0 (0
/ - 2 . !$/ - + . *$ + $ , 1 / 5 - *- 1 ' 0 0 (0
-
-2! 1
-
-
4 + . *$ / (+ / 5 - *- 1 ' 0 0 (0
/ - 2 . !$/ - + . *$ + $ , 1 / 5 ' 0 0 (0 - 1 **- 3 $ # 4 " $ . 1 %- / 2 1. 2 1
-
2 1. 2 10 (, 1' $ " - + . *$ + $ , 1 / 5 " ' 0 0 (0 2 0 $ 1' $ 0 + $ ! (10 (, 1' $ - 2 1. 2 1 (+ & $ 1 ! *$ 1' $ - 2 1. 2 10 (, 1' $ . / (+ / 5 " ' 0 0 (0
0
4 + . *$
1 -#2*$ 21.21 -#2*$ *-") 1/ ,0%$/ -#2*$
- 2 1.21 + - #2*$0 20$ 1'$ 0 + $ -2 1.21 (+ &$ 1 ! *$ !(10 , !$ (,.21 -/ -21.21 + -#2*$ -/ !*- ") 1/ ,0%$/ + -# 2*$ 201 !$ $ + .15 (% "-//$0.-,#(, & ./(+ /5 0*-1 (0 ! *-") 1/ , 0%$/ + -#
Follow these guidelines when you select 2-slot addressing:
• Place an 8-point output module opposite a 16-point input module. • An I/O group having a 16-point input and output module cannot have a corresponding I/O group in the complementary chassis. • You can place an output module opposite another output module; they reflect the same bits in the output image table. You can use block-transfer modules in a complementary I/O system, with these restrictions:
1(-, - -$!/2 /5
Page 42
3–12
Addressing Modes for Your Remote I/O
• When using double-slot block-transfer modules: • The left slot of the complementary I/O group must be empty. • You can only place an 8-point output module (if any) in the right slot of the complementary I/O group.
• When using single-slot block-transfer modules: • The right slot of the primary I/O group can be another single-slot block-transfer module, or an 8-point input or output module. • The left slot of the complementary I/O group must be empty. • You can place an 8-point output module in the right slot of the complementary I/O group; this slot must be empty if the corresponding slot in the primary I/O group is a single-slot block-transfer module. When you select 2-slot addressing, each pair of slots (one I/O group) is assigned to the corresponding pair of words in the input and output image tables. You assign one I/O rack number to eight I/O groups (Figure 3.10). Figure 3.10 I/O Image Table and Corresponding Hardware for One Assigned Rack Number with 2Ćslot Addressing )+
. -* . - ' " ! &!
-
-
0
1
2
3
4
5
6
7 - 0*)$(- ') .&!, - ) .&!, &$%!
)+
( * . - ' " ! &!
-
-
-
Page 43
Addressing Modes for Your Remote I/O
1-Slot Addressing
3–13
Definition: The processor addresses one I/O module slot as one I/O group. Concept: The physical address of each I/O group corresponds to an input and output image table word. The type of module you install (8, 16, or 32-point) determines the number of bits in these words that are used. You select 1-slot addressing by setting switches 5 and 6 of the I/O chassis backplane switch assembly:
• switch 5 to the ON position • switch 6 to the OFF position With 1-slot addressing, because 16 input AND 16 output bits are available in the processor’s image table for each I/O slot, you can use any mix of 8 or 16-point I/O modules in the I/O chassis. To use 32-point I/O modules with 1-slot addressing, you must install, as a pair, an input module and an output module in 2 adjacent slots of the I/O chassis beginning with I/O slot 0 (Figure 3.11). If you cannot pair the modules in this way, one of the two slots of the pair must be empty. For example, if I/O slot 0 holds a 32-point input module, I/O slot 1 can hold an 8, 16, or 32-point output module (or a module that uses the backplane for power only); otherwise, it must be empty. Figure 3.11 Using 32Ćpoint I/O Modules with 1Ćslot Addressing &%"&%
-
-
-
Page 44
3–14
Addressing Modes for Your Remote I/O
Thirty-two-point I/O modules need 32 input or 32 output bits in the processor’s image table. Because only 16 input and 16 output bits are available for each I/O group, to address a 32-point I/O module, the remote I/O adapter module uses the unused input or output word associated with the adjacent I/O slot. Refer to Figure 3.12. When the 1771-ASB remote adapter module addresses a 1-slot I/O group containing a 32-point I/O module, the adapter module uses the unused word assigned to the adjacent I/O module slot. For example, the adapter module uses the unused input word associated with I/O slot 1 (because that slot must hold an output module and does not use its input word). Figure 3.13 illustrates the concept of 1-slot addressing with two 32-point I/O modules. Figure 3.12 1Ćslot I/O Group Concept With 32Ćpoint I/O Modules
$"'#
'&#'&
$"'#
'&#'&
$"'#
-
'&#'& $"' #
-
Page 45
Addressing Modes for Your Remote I/O
3–15
Identifying I/O Groups You identify your I/O groups in one of three ways, depending on the addressing method and I/O chassis you use. Refer to Figure 3.13 for 1-slot addressing when using series B I/O chassis. Figure 3.13 Identifying 1Ćslot I/O Groups with Series B I/O Chassis
I/O Rack Number I/O Group Number
R 1 G 0
G 1
00-07
00-07
10-17
10-17
Example: Using I/O Group 0 and 16Ćpoint modules, a sample physical address (with its corresponding data table address) is:
Physical Address
2 -s lo t I/O G r o u p
1
1
0
12
I/O Group 0
1
1
1
12
I/O Group 1
Type of I/O module 1 = Input 0 = Output I/O Rack Number In p u t T e r m in a ls 00 01 02 03 04 05 06 07 10 11 12 13 14 15 16 17
In p u t T e r m in a ls 00 01 02 03 04 05 06 07 10 11 12 13 14 15 16 17
Module Terminal Number I/O Group Number
In p u t im a g e ta b le w o r d c o r r e s p o n d in g to th e I/O g r o u p . 17 16 15 14 13 12 11 10 07 06 05 04 03 02 01 00
1
1
0
I/O Group 0
17 16 15 14 13 12 11 10 07 06 05 04 03 02 01 00
1
1
1
I/O Group 1
Module Terminal Number
Type of I/O module 1 = Input 0 = Output I/O Rack Number I/O Group Number
Rules for module terminal point assignments are:
Standard density discrete I/O module in the left slot has terminals numbered 00-07. (Mark top only.) High density (16Ćpoint) discrete I/O module in either slot has terminals numbered 00-07 and 10-17.
10810-I
Publication 1771-UM001A-US-P - February 2000
Page 46
3–16
Addressing Modes for Your Remote I/O
Module Placement with 1Ćslot Addressing Figure 3.14 shows possible module placement for complementary I/O with 1-slot addressing. Figure 3.14 Complementary I/O Configurations with 1Ćslot Addressing 0 ), ! 0 5 1 +. 2 ( ! 1 1 )1
.3"+%1+.2
-
-
0 . 3 / "%0 . , / +% , % - 2! 0 5 1 +. 2 ( ! 1 1 )1
- 4 ! , / +%
0 ), ! 0 5 1 +. 2 ( ! 1 1 )1
0 . 3 / "%0
. , / +% , % - 2! 0 5 1 +. 2 ( ! 1 1 )1
- 4 ! , / +% .$3+% .0 32/32 .$3+% .0 /.)- +.#* 20! -1&%0 .$3+%
32/32 , .$3+%1 3 1% 2(% 1!, % .32/32 ), !'% 2!"+% ")21 !- "% )- /32 .0 . 32/32 , . $3+% . 0 /.)- 1)-' +%1+.2 "+.#* 20!- 1 &%0 , .$3+% 312 " % %, /25 )& #.00%1/.- $)-' / 0), !05 1+.2 )1 "+. #* 20!-1&%0 , . $3+%
Follow these guidelines when you select 1-slot addressing:
• Place input modules opposite output modules; place output modules opposite input modules. • You can use 8-point or 16-point I/O modules. • Output modules placed opposite output modules reflect the same bits in the output image table. You can use block-transfer modules in a complementary I/O configuration with 1-slot addressing. Remember that when you select 1-slot addressing, an I/O group is one module slot. Use block-transfer modules with these restrictions:
Page 47
Addressing Modes for Your Remote I/O
3–17
• When using double-slot block-transfer modules: – The left slot of the two corresponding I/O groups must be empty. – You can place any single-slot I/O module in the right slot of the two corresponding I/O groups. When using single-slot block-transfer modules, the corresponding I/O group must be empty.
Assigning I/O Rack Numbers with 1-Slot Addressing
The following rules apply when you assign I/O rack numbers: When you select 1-slot addressing, set switches of switch assembly S1 to assign the first I/O rack number of the chassis. The remote I/O adapter module automatically assigns the next higher I/O rack number to the remaining I/O groups of the chassis. For example, if you want a 16-slot chassis that you set for 1-slot addressing to begin with I/O rack number 0, set switches of switch assembly S1 for I/O rack number 0. The adapter module automatically assigns I/O rack number 1 to the remaining I/O groups of the chassis (Figure 3.15). Figure 3.15 Assigning I/O Rack Numbers with 1Ćslot Addressing
01
23
45
-
67
01
23
45
67
&% *
%+$. - *& * *
- -.
-.)#&*
You assign one I/O rack number to eight I/O groups, regardless of which addressing method you select.
- -
Page 48
3–18
Addressing Modes for Your Remote I/O
When you select 1-slot addressing, each individual slot (one I/O group) is assigned to the corresponding word in the input or output image tables. You assign one I/O rack number to eight I/O groups (Figure 3.16). Figure 3.16 I/O Image Table and Corresponding Hardware for One Assigned Rack Number with 1Ćslot Addressing - +*'+* $
-
-
&*
- (&+'
- ,"*! -.)#&*
I
I
I
I
O O
O O
%'+*-+*'+*
-
%'+* $
#,
-
-