Remote I/O Adapter Module (Cat. No. 1771-ASB Series E) User Manual: 4 - Troubleshooting
Pages 57 to 60 of 94, from Remote I/O Adapter Module (Cat. No. 1771-ASB Series E) User Manual
The original document is the PDF (847 KB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
For the Allen-Bradley 1771-ASB
Page 57
Chapter
Chapter Objectives Troubleshooting With the Indicator Lights
4
In this chapter, you will learn how to use the indicators on the module frontplate for troubleshooting the module.
The module has three indicators on the front plate, as shown below. Use these indicators for troubleshooting the module.
-
-
-
-
- -
The following table describes problems that may occur, probable causes, and recommended courses of action.
-
Page 58
4–2
Troubleshooting
Table 4.A Remote I/O System Troubleshooting Guide Indicators Active Adapter I/O Fault Rack
Description
Probable Cause
Recommended Action
On
Off
Off
Normal indication; remote adapter is fully operational; processor is in Run mode
Off
On
Off
Adapter crash.
RAM memory fault. Watchdog timeout
Cycle power. Replace module if problem reoccurs.
On
Blink
Off
Module placement error
I/O module in incorrect slot.
Place module in correct slot in chassis.
Blink in unison Off
Incorrect starting I/O group number
Error in starting I/O group number or I/O rack address
Check dipswitch settings. Refer to table 3.B to verify acceptable beginning I/O group number; set switches correctly
On
On
On
Module not communicating
Incorrect baud rate setting
Check dipswitch setting
Off
On
On
Module not communicating
Scan switch set for "all but last 4 slots" in 1/4 rack
Reset scan switch setting
Blink
Off
Off
Remote adapter not actively controlling I/O (scanner to adapter communication link is normal)4; scanner manual or autoconfiguration 8 was successful
Processor is in program or test mode Scanner is holding adapter module in fault mode; Configuration mismatch
Place processor in Run mode. Fault should be cleared by I/O scanner Correct the configuration mismatch, i.e. incorrect rack size, rack number
LEDs sequence on/off from top to bottom
Module not communicating
Another remote I/O adapter with the same address is on the link.
Correct the address.
Blink alternately
Adapter module not actively controlling I/O2
Processor restart lockout switch on chassis backplane switch assembly on1
Depress reset button to clear lockout feature or cycle power; if after repeated attempts indicators are still blinking, check: • pushbutton not wired properly to field wiring arm • wiring arm not connected to adapter module • adapter module was reset by processor/scanner, then immediately faulted
Off
Adapter module in processor restart lockout mode (adapter to scanner link is normal)5
Off
Off
On
I/O chassis fault.2 No communication Problem exists between: on link. • adapter and module in chassis; the module will stay in fault mode until fault is corrected • shorted printed circuit board runs on backplane or I/O module
Cycle power to the chassis to clear a problem resulting from high noise3 • remove and replace all I/O modules one at a time • if problem does not clear, something is wrong in chassis or I/O module
Blink
Off
On
Communication on link. Chassis violation.
Identify source of noise. Suppress output module inductive loads or noise sources in proximity to output module wiring. Target the problem by splitting the rack into smaller racks. Check chassis, Replace chassis as necessary.
Publication 1771-UM001A-US-P - February 2000
Possible shorted backplane in chassis. Excessive noise on backplane.6
Page 59
Troubleshooting
Indicators Active Adapter I/O Fault Rack
Description
Probable Cause
4–3
Recommended Action
Blink
On
Off
Module identification line fault
Excessive noise on backplane
Identify source of noise. Check power supply incoming ac power with a line disturbance analyzer. Monitor scanner channel for retries to determine if noise is entering the RIO cable. Possible problem with block transfer module. Remove to isolate.
Off
Off
Off
Module not communicating7
Autoconfiguration 8 unsuccessful Scanner not configured properly
Check scanner COM indicator; Steady green - normal; Blinking green - at least one node on the link is faulted or failed; Red - scanner may have a hardware problem, replace. Blinking red - all adapters on link have faulted or duplicate node address detected Off - scanner channel has not been configured to be active on the RIO link (not online) Refer to Autoconfigure below.
Power supply fault
Check power supply, cable connections, and make sure adapter module is fully seated in chassis.
Wiring from scanner to adapter module disrupted
Correct cable and wiring defects
One faulted chassis within a rack group address causing scanner/distribution panel to fault all chassis in rack group address (when in disable search mode)
Check sequentially from the first module to the last module to pinpoint fault; correct any faults and proceed to the next chassis
1. You must select the operating mode of the remote I/O adapter module as outlined in the publication furnished with the remote I/O scanner/distribution panel, remote I/O scanner-program interface module, or I/O scanner-message handling module. Pay close attention to the disable search mode in the 1771-SD, -SD2. 2. The I/O chassis is in faulted mode as selected by the last state switch on the chassis backplane. 3. Cycling power clears the block-transfer request queue. All pending block transfers are lost. Your program must repeat the request for block transfers from the chassis. 4. If a fault occurs and the processor is in the run mode but is actually operating in the dependent mode, the chassis fault response mode is selected by the last state switch on the chassis backplane. 5. The I/O chassis is in faulted mode as selected by the last state switch on the chassis backplane. 6. If excessive chassis faults occur, check switch SW-2, position 6 for the OFF position. 7. The adapter considers loss of communication if it sees no transmissions on the RIO network for 100ms or sees 255 transmissions on the RIO with none to the adapter. 8. Autoconfigure is a feature of the PLC-5 processor family.
Publication 1771-UM001A-US-P - February 2000
Page 60
4–4
Troubleshooting
For a successful autoconfigure, insure that a processor I/O status file exists, all rack and reset and inhibit bits are zeroed, and the channel is set up for scanner, and the baud rate is correct. Make sure that:
• the input and output image tables are large enough to accommodate the rack address you are attempting to assign • the adapter and chassis switches are set correctly, especially communication rate, rack and group. • the wiring is correct and properly terminated • the remote I/O racks are not split across scanner channels or the local chassis If autoconfigure is still not successful, save the program, clear processor memory by disconnecting the battery, create an I/O status file, reconfigure the scanner channel, and try again. 1747-SN Scanner For the adapter to recognized by the 1747-SN scanner module, the G-files must be properly constructed for rack and starting group and scanner switches must be set for the correct communication rate. 1756-DHRIO Scanner For the adapter to be recognized by the scanner module, the adapter must be added for each logical rack under the scanner module and be properly configured in the Logix5550 Controller Organizer configuration tree, and the scanner switches must be set correctly for remote I/O and node number.
In this chapter you learned how to use the indicators on the front of the module to troubleshoot your module.