Remote I/O Adapter Module (Cat. No. 1771-ASB Series E) User Manual, pages 61 to 69

Pages 61 to 69 of 94: A - Specifications; B - Settings for 1771-AS and 1771-ASB Series A, B, C and D Remote I/O Adapters

The original document is the PDF (847 KB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

For the Allen-Bradley 1771-ASB

Page 61

Appendix

A

Module Location

1771 I/O chassis, leftmost slot

Chassis Distance

2500 ft @ 230.4K Baud 5000 ft @ 115.2K Baud 10000 ft @ 57.6K Baud

Interconnect Cable

Power Dissipation

5 Watts

Thermal Dissipation

17.06 BTU/hr

Backplane Current

1.0A @ 5V

Keying

Upper connector: between 54 and 56 Lower connector: between 16 and 18

Environmental Conditions Operational Temperature Storage Temperature Relative Humidity

0o to 60oC (32o to 140oF) -40o to 85oC (-40o to 185oF) 5% to 95% (without condensation)

Field Wiring Arm

Cat. No. 1771-WB

Field Wiring Arm Screw Torque

7-9 poundĆinches

Conductor Size Remote I/O blue cable User supplied I/O rack restart switch Category Termination Resistor Agency Certification (when product is marked)

20 AWG (0.5mm2) stranded copper with 1 wire per terminal1 20 AWG (0.5mm2) with 3/64 (1.2mm) insulation maximum 22 82Ω - A-B part number 740018-23 150Ω - A-B cat. no. 1770-XT • CSA Certified • CSA Class I, Division 2 Groups A, B, C, D certified • UL listed • CE marked for all applicable directives • C-Tick marked for all applicable acts.

1. Connect only 1 stranded wire to a terminal. Use stranded copper wire only. 2. Use this conductor category information for planning conductor routing. Refer to publication 1770-4.1, Automation Wiring and Grounding Guidelines for Noise Immunity."

Publication 1771-UM001A-US-P - February 2000

Page 62 read from a scan by OCR; it may hold reading errors

A-2 Specifications

Publication 1771-UM001A-US-P - February 2000

Page 63 read from a scan by OCR; it may hold reading errors

Appendix B

General Information

Settings for 1771-AS and

1771-ASB Series A,

B, C and D

Remote I/O Adapters

This appendix provides information on previous remote I/O adapters supplied by Allen-Bradley. The following table lists the adapter and respective figure reference.

Figure Description Applies to: B.1 Keying Diagram for 1771-ASB series A, B and C 1771-ASB series A, B and C B.2 | Keying Diagram for 1771-AS 1771-AS B.3 Field Wiring Arm Connection for 1771-AS, -ASB series A, B and C 171-AS ° , , 1771-ASB series A, B and C B4 Module Switch Assembly Settings for 1771-AS, -ASB series AandB | 1771-AS , Adapter for PLC-2 Family Processors 1771-ASB series A, B B5 Module Switch Assembly Settings for 1771-ASB series C Adapter for 1771-ASB series C and D PLC-2 Family Processors B6 Module Switch Assembly Settings for 1771-AS and 1771-ASB series | 1771-AS , A and B Adapters for PLC-3 Family Processors 1771-ASB series A, B B7 Module Switch Assembly Settings for 1771-ASB series C Adapters for 1771-ASB series C and D PLC-3 Family Processors Module Switch Assembly Settings for 1771-AS and 1771-ASB series 1771-AS B.8 | AandB Adapters for PLC-5 Family, SLC and ControlLogix Processor 1771-ASB series A. B Systems Processors without Complementary I/O , Module Switch Assembly Settings for 1771-ASB series C Adapters for B.9 | PLC-5 Family, SLC and ControlLogix Processor Systems Processors | 1771-ASB series C and D without Complementary I/O Module Switch Assembly Settings for 1771-AS, -ASB series A and B 1771-AS B.10 | Adapters for PLC-5 Family, SLC and ControlLogix Processor Systems 1771-ASB series A. B Processors with Complementary I/O , Module Switch Assembly Settings for 1771-ASB series C Adapters for B.11_ | PLC-5 Family, SLC and ControlLogix Processor Systems Processors | 1771-ASB series C and D with Complementary I/O I/O Chassis Backplane Switch Assembly Settings for 1771-AS B.12 | Remote Adapter Module in PLC-2, SLC and ControlLogix Processor | 1771-AS Systems Family Processor System I/O Chassis Backplane Switch Assembly Settings for 1771-AS B.13 | Remote Adapter Module in PLC-3 Family, SLC and ControlLogix 1771-AS Processor Systems Processor System I/O Chassis Backplane Switch Assembly Settings for Remote Adapter B.14 | Module in PLC-2, SLC and ControlLogix Processor Systems Family 1771-ASB series C and D Processor System B15 I/O Chassis Backplane Switch Assembly Settings for Remote Adapter 1771-ASB series C and D

Module in PLC-3 Family Processor System

Publication 1771-UM001A-US-P - February 2000

Page 64

B–2

Settings for 1771–AS and 1771–ASB Series A, B, C and D Remote I/O Adapters

Figure

Description

Applies to:

"*, /'! %)

-!,%!-

"*, /'! %) %)

-!,%!-

"*, /'! %) -

-!,%!-

Figure B.1 Keying Diagram for 1771-ASB series A, B, C and D

-

-

-

-)-!,. &!2%)# - /++!, '*0!,

Figure B.2 Keying Diagram for 1771-AS Remote I/O Adapter

-

-

-

-)-!,. &!2%)# - /++!, '*0!,

Page 65 read from a scan by OCR; it may hold reading errors

Settings for 1771-AS and 1771-ASB Series A, B, C and D Remote I/O Adapters B-3

1 Line 1 2 Shield Cable

Figure B.3 Field Wiring Arm Connection Diagram for 1771-AS, -ASB series A, B, C and D Blue Shield ~~ Clear

3 Line 2

Allen-Bradley Cable (cat. no. 1770-CD)

WARNING: Do not make connections to terminals

4 through 10. These terminals are connected internally (1 to 4, 2 to 5 and 3 to 6) and cannot be used for any other purpose.

User supplied

4 No connection 5 No connection 6 No connection 7 No connection 8 No connection 9 No connection

10 No connection

I/O rack restart pushbutton

"In = Reset 12 Ret, 17343

Publication 1771-UM001A-US-P - February 2000

Page 66

B–4

Settings for 1771–AS and 1771–ASB Series A, B, C and D Remote I/O Adapters

Figure B.4 Module Switch Assembly Settings for 1771-AS, -ASB series A and B Adapter for PLC-2 Family Processors

Address Switch Assembly (SW-1) O 1 N

2

3

4

5 6

Switch Assembly (SW-2)

7 8

O F F

O 1 N

2

3

Pressed in at top Closed (ON)

4

O F F

First I/O group number (Table B.A)

Pressed in at bottom Open (OFF)

I/O rack number (Table B.A)

Always OFF

SD - always ON

SD2 - without complementary I/O - always ON

Maximum I/O Rack Distance ON - 10,000 cable ft. max. (57.6K baud) OFF - 5,000 cable ft. max. (115.2K baud)

SD2 - with complementary I/O -

ON - Primary chassis OFF - Complementary chassis

SD - always OFF SD2 - without complementary I/O - always OFF SD2 - with complementary I/O -

ON - Primary chassis OFF - Complementary chassis

Always ON

Table B.A I/O Rack Selection for PLC-2 Family Processors I/O Rack Number

Publication 1771-UM001A-US-P - February 2000

Switch Selections 4 5 6

First I/O Group Number

Switch Selections 7 8

1

On

On

On

0

On

On

2

On

On

Off

2

On

Off

3

On

Off

On

4

Off

On

4

On

Off

Off

6

Off

Off

5

Off

On

On

6

Off

On

Off

7

Off

Off

On

10819-I

Page 67

Settings for 1771–AS and 1771–ASB Series A, B, C and D Remote I/O Adapters

B–5

Figure B.5 Module Switch Assembly Settings for 1771-ASB series C and D Adapters for PLC-2 Family Processors

Switch Assembly (S2)

Address Switch Assembly (S1) O 1 N

2

3

4

5 6

O 1 N

7 8

2

3

5

4

Pressed in at top Closed (ON)

6

O F F

O F F

Pressed in at bottom Open (OFF) Off Link Response Ć ON for series B emulation OFF for unrestricted ATTENTION: Link response switch must be ON when using the following scanner modules: 1772-SD2

First I/O group number (Table B.B) I/O rack number (Table B.B) SD Ć always ON

SD2 Ć without complementary I/O Ć always ON SD2 Ć with complementary I/O Ć

ON Ć Primary chassis OFF Ć Complementary chassis

Switch Position 1 2 ON OFF OFF OFF ON ON OFF ON

Maximum I/O chassis distance

57.6K Baud Ć 10,000ft 115.2K Baud Ć 5,000ft Not Used Not Used

Always ON

Scan Ć on for all but last 4 slots off for all slots SD Ć always OFF SD2 Ć without complementary I/O Ć always OFF SD2 Ć with complementary I/O Ć

ON Ć Primary chassis OFF Ć Complementary chassis

10798-I

Table B.B I/O Rack Number and First I/O Group Switch Selections for the Address Switch Assembly S1 (PLC-2 Family Processors) I/O Rack Number

Switch Selections 4 5 6

First I/O Group Number

Switch Selections 7 8

1

On

On

On

0

On

On

2

On

On

Off

2

On

Off

3

On

Off

On

4

Off

On

4

On

Off

Off

6

Off

Off

5

Off

On

On

6

Off

On

Off

7

Off

Off

On

Publication 1771-UM001A-US-P - February 2000

Page 68

B–6

Settings for 1771–AS and 1771–ASB Series A, B, C and D Remote I/O Adapters

Figure B.6 Module Switch Assembly Settings for 1771-AS and 1771-ASB series A and B Adapters for PLC-3 Family Processors

Address Switch Assembly (SW-1) O 1 N

2

3

4

5 6

Switch Assembly (SW-2)

7 8

O F F

O 1 N

3

Pressed in at top Closed (ON)

4

O F F

First I/O group number (Table B.C) I/O rack number (Table B.C)

2

Pressed in at bottom Open (OFF) Always OFF

Maximum I/O Rack Distance ON - 10,000 cable ft. max. (57.6K baud) OFF - 5,000 cable ft. max. (115.2K baud)

10820-I

Table B.C I/O Rack Selection for PLC-3 Family Processors I/O Rack Number

I/O Rack Number

1

Switch Setting 2 3 4

00

On

On

On

On

On

On

01

On

On

On

On

On

02

On

On

On

On

03

On

On

On

On

04

On

On

On

05

On

On

06

On

07

1st I/O Group Number

Switch Selections 7 8

1

Switch Setting 2 3 4

20

On

Off

On

On

On

On

0

On

On

Off

21

On

Off

On

On

On

Off

2

On

Off

Off

On

22

On

Off

On

On

Off

On

4

Off

On

Off

Off

23

On

Off

On

On

Off

Off

6

Off

Off

Off

On

On

24

On

Off

On

Off

On

On

On

Off

On

Off

25

On

Off

On

Off

On

Off

On

On

Off

Off

On

26

On

Off

On

Off

Off

On

On

On

On

Off

Off

Off

27

On

Off

On

Off

Off

Off

10

On

On

Off

On

On

On

30

On

Off

Off

On

On

On

5

6

5

6

11

On

On

Off

On

On

Off

31

On

Off

Off

On

On

Off

12

On

On

Off

On

Off

On

32

On

Off

Off

On

Off

On

13

On

On

Off

On

Off

Off

33

On

Off

Off

On

Off

Off

14

On

On

Off

Off

On

On

34

On

Off

Off

Off

On

On

15

On

On

Off

Off

On

Off

35

On

Off

Off

Off

On

Off

16

On

On

Off

Off

Off

On

36

On

Off

Off

Off

Off

On

17

On

On

Off

Off

Off

Off

37

On

Off

Off

Off

Off

Off

Publication 1771-UM001A-US-P - February 2000

Page 69

Settings for 1771–AS and 1771–ASB Series A, B, C and D Remote I/O Adapters

B–7

Figure B.7 Module Switch Assembly Settings for 1771-ASB series C and D Adapters for PLC-3 Family Processors Address Switch Assembly (S1) O 1 N

2

3

4

5 6

7 8

O F F

Switch Assembly (S2) O 1 N

3

5

4

Pressed in at top Closed (ON)

6

Pressed in at bottom Open (OFF)

O F F

First I/O group number (Table B.D)

I/O rack number (Table B.D)

2

Switch Position Maximum I/O 1 2 chassis distance ON OFF 57.6K Baud Ć 10,000ft OFF OFF 115.2K Baud Ć 5,000ft 230.4K Baud Ć 2,500ft1 OFF ON ON ON Not Used

Off Link Response Ć ON for series B emulation OFF for unrestricted ATTENTION: Link response switch must be ON when using the following scanner modĆ ules: 1775-S4A 1775-S4B 1775-S5 1775-SR5 1775-SR

1 230.4K Baud with 1775-S5 revision A/G, and 1775-SR5 revision A/G scanners only.

Always OFF

Scan Ć On for all but last 4 slots Off for all slots

10799-I

Table B.D I/O Rack Switch Selections for the Address Switch Assembly (PLC-3 Family Processors) Rack #

1

2

6

Rack #

1

2

6

Rack #

1

2

00

On

On

On

On

On

On

20

On

Off

On

On

On

On

40

Off

On

On

On

01

On

On

On

On

On

Off

21

On

Off

On

On

On

Off

41

Off

On

On

02

On

On

03

On

On

On

On

Off

On

22

On

Off

On

On

Off

Off

23

On

Off

On

On

Off

On

42

Off

On

On

On

Off

Off

43

Off

On

04

On

On

On

Off

On

On

24

On

Off

On

Off

On

On

44

Of

05

On

On

On

Off

On

Off

25

On

Off

On

Off

On

Off

45

06

On

On

On

Off

Off

On

07

On

On

On

Off

Off

Off

26

On

Off

On

Off

Off

On

27

On

Off

On

Off

Off

Off

10

On

On

Off

On

On

On

30

On

Off

Off

On

On

11

On

On

Off

On

On

Off

31

On

Off

Off

On

12

On

On

Off

13

On

On

Off

On

Off

On

32

On

Off

Off

On

Off

Off

33

On

Off

Off

14

On

On

Off

Off

On

On

34

On

Off

15

On

On

Off

Off

On

Off

35

On

16 17

On

On

Off

Off

Off

On

36

On

On

Off

Off

Off

Off

37

Switch Selections 7 8

Note:

Rack address 77 is an illegal configuration. PLC-3 processors can scan racks 0-76.

1st I/O Group Number

Switch Setting 3 4 5

0

On

On

2

On

Off

4

Off

On

6

Off

Off

Switch Setting 3 4 5

Switch Setting 3 4 5

6

Rack #

1

2

Switch Setting 3 4 5

On

On

60

Off

Off

On

On

On

On

On

On

Off

61

Off

Off

On

On

On

Off

On

On

Off

On

62

Off

Off

On

On

Off

On

On

On

Off

Off

63

Off

Off

On

On

Off

Off

On

On

Off

On

On

64

Off

Off

On

Off

On

On

Off

On

On

Off

On

Off

65

Off

Off

On

Off

On

Off

46

Off

On

On

Off

Off

On

66

Off

Off

On

Off

Off

On

47

Off

On

On

Off

Off

Off

67

Off

Off

On

Off

Off

Off

On

50

Off

On

Off

On

On

On

70

Off

Off

Off

On

On

On

On

Off

51

Off

On

Off

On

On

Off

71

Off

Off

Off

On

On

Off

On

Off

On

52

Off

On

Off

On

Off

On

72

Off

Off

Off

On

Off

On

On

Off

Off

53

Off

On

Off

On

Off

Off

73

Off

Off

Off

On

Off

Off

Off

Off

On

On

54

Off

On

Off

Off

On

On

74

Off

Off

Off

Off

On

On

Off

Off

Off

On

Off

55

Off

On

Off

Off

On

Off

75

Off

Off

Off

Off

On

Off

On

Off

Off

Off

Off

On

56

Off

On

Off

Off

Off

On

76

Off

Off

Off

Off

Off

On

On

Off

Off

Off

Off

Off

57

Off

On

Off

Off

Off

Off

77

Not valid

Publication 1771-UM001A-US-P - February 2000

6