Page 23

Installing Your Module

Setting the I/O Chassis Switches

2–9

After setting the adapter module switch assemblies, you must also

• set the I/O chassis backplane switches Setting the Backplane Switch Assembly The backplane switch assembly is located on the backplane of the I/O chassis. You use it to select:

• • • • the last state of all outputs the processor restart lockout feature 1/2-, 1- or 2-slot addressing the last chassis in the I/O system (for PLC-2 family processors) Refer to the table below for backplane switch setting illustrations for the various processors. For Processor:

Refer to:

-

Figure 2.8 I/O Chassis Backplane Switch Assembly Settings for Remote Adapter Module in PLC-2 Family Processor System

2 3 4

O1 N O F F

Last State Switch Ć - ',+(,+* +!"* "& ',+(,+* +!"* - "*

5 6 8

ATTENTION: +' ('*"+"'& +' ',+(,+* +' +!"* "* "* +' - ',+(,+* +' +!"* "& %'+"'&

Addressing Switch Ć - 1 1

7

Processor Restart Lockout Ć - - - %,*+

Last Chassis Switch Ć - 1 &'+ !" - )',( 1 !" - )',( /', '&$/ +!"* +' /', +' - +'

-

Page 24 read from a scan by OCR; it may hold reading errors

2-10 Installing Your Module

ATTENTION: Set switch 1 to the OFF position to deenergize outputs wired to this chassis when a fault is detected. If switch 1 is set to the ON position, outputs connected to this chassis remain in their last state when a fault occurs and machine motion may continue after fault detection.

Always OFF

1771-A1/A1B chassis in PLC-3 Backup

ON - If any 1771-A1/A1B chassis contains starting I/O group 0 with 2-slot addressing and the PLC-3 is configured in backup mode. OFF - All other times.

ATTENTION: Set switch 1 to the OFF position to deenergize outputs wired to this chassis when a fault is detected. If switch 1 is set to the ON position, outputs connected to this chassis remain in their last state when a fault occurs and machine motion may continue after fault detection.

Always OFF

Last Chassis Switch -

ON - Chassis does not contain the highest numbered I/O group for the associated rack number OFF - Chassis does contain the highest numbered I/O group for the associated rack number

@ lf you have only a primary chassis, set this switch to OFF.

@ {Ifyou have both primary and complementary chassis, set the primary chassis to ON and the complementary chassis to OFF.

Publication 1771-UM001A-US-P - February 2000

Figure 2.9 1/0 Chassis Backplane Switch Assembly Settings for Remote Adapter Module in PLC-3 Family Processor System

Last State Switch - When ON, outputs of this chassis remain in last state. When OFF, outputs of this I/O chassis are deenergized

710 ZO when a fault is detected. CT d- [cc << Processor Restart Lockout - When ON, processor can restart I/O chassis

I When OFF, I/O chassis must be restarted at the chassis. | lo rti- Addressing Switches | a | 5 6 m_~ OFF ON You select 1/2-slot addressing Clie ON OFF You select 1-slot addressing

OFF OFF You select 2-slot addressing

ON ON Not allowed

10802-1 Figure 2.10

1/0 Chassis Backplane Switch Assembly Settings for Remote Adapter Module in PLC-5 Family Processor System

Last State Switch - When ON, outputs of this chassis remain in last state. When OFF, outputs of this I/O chassis are deenergized

710 ZO when a fault is detected. LT d- coor Processor Restart Lockout -

When ON, processor can restart I/O chassis m_~ When OFF, I/O chassis must be restarted at the chassis. | le Cts Addressing Switches 11° jag 5 6 __~ OFF ON You select 1/2-slot addressing Clo ON OFF You select 1-slot addressing

OFF OFF You select 2-slot addressing ON ON Not allowed

10802-1

Page 25

Installing Your Module

2–11

Figure 2.11 I/O Chassis Backplane Switch Assembly Settings for Remote Adapter Module in PLC-5 Family, SLC and ControlLogix Processor Systems in Remote Configuration

2 3 4

O1 N O F F

ATTENTION: '* ' ($ ON %$' ( $)(%)(' ($ ' ' # # & "$( $# $# +$) '* ($ OFF %$' ( $# ($ $)(%)(' * ($ ' ' '

5 6 7 8

Last State Switch Ć $)(%)(' ' ' # # $)(%)(' ' ' ' Processor Restart Lockout Ć ' ' ")'( ' *

$(

Figure 2.12 I/O Chassis Backplane Switch Assembly Settings for Remote Adapter Module in PLC-5/250 Processor System

O1 N O F F

ATTENTION: '* ($ OFF %$' ( $# ($ $)(%)(' * ($ ' ' ' '* ' ($ ON %$' ( $)(%)(' ($ ' ' # # & "$( $# $#

2 3 4

5 6 7 8

Last State Switch Ć $)(%)(' ' ' # # $)(%)(' ' ' ' Processor Restart Lockout Ć ' ' ")'( ' *

$(

$#

Page 26

2–12

Installing Your Module

Setting the I/O Chassis Power Supply Configuration Plug

You use the I/O chassis power-supply configuration plug (Figure 2.13) to identify the type of power supply you use with your remote chassis. This configuration plug is located on the backplane of series B I/O chassis. Figure 2.13 Series B I/O Chassis Power Supply Configuration Plug Settings

For Use With:

Set Chassis Configuration Plug to:

*)/!+ ,.**&1 ') .&! %(

*),%-%)(

*)/!+ ,.**&1 %( 1).+ +!')-! ,1,-!'

2 *),%-%)(

Y N

Y N

Y N

-

Wiring the Field Wiring Arm

The field wiring arm provides connection points for:

• I/O communication cables • a user-supplied I/O chassis restart pushbutton The wiring arm pivots on the front of the chassis to connect with the module’s printed circuit board, allowing you to remove the adapter module without disconnecting the system wiring. Connect input/output cables to the field wiring arm as shown in Figure 2.14.

Page 27

Installing Your Module

2–13

Figure 2.14 Field Wiring Arm Connection Diagram for the 1771-ASB Series E

!"+%

+%!0

!"+%

!"+% -.-

#.--%#2).-

ATTENTION: -. -.2 ,!*% #.--%#2).-1 2. 2%0,)-!+1 2(0.3'( 2%0,)-!+1 !0% #.--%#2%$ )-2%0-!++4 2. 2. !-$ 2. !-$ #!--.2 "% 31%$ &.0 !-4 .2(%0 /30/.1%-

1%0 13//+)%$ 0!#* 0%12!02 /31("322.-

#.--%#2).-

#.--%#2).-

#.--%#2).-

#.--%#2).-

!

ATTENTION: Do not remove or insert the adapter module from the I/O chassis while system power is on. Otherwise, you may damage module circuitry.

Terminals 1 and 4, 2 and 5, and 3 and 6 are internally connected on the module. If you use these terminals (4, 5, and 6) for connection of additional adapter modules, you disconnect the remaining adapter modules in the series connection when you disconnect the remote I/O adapter module wiring arm. If this is unsuitable for your application, make your connections to terminals 1, 2, and 3 only.

Page 28

2–14

Installing Your Module

Installing the Terminator

If this is the last remote I/O adapter on the link, you must use a terminating resistor to terminate both ends of the remote I/O link (scanner end and last adapter end). Connect the terminator across terminals 1 (blue) and 3 (clear). The size of the terminator is determined by the system configuration. Older configurations use a 150 ohm resistor at both ends. With newer products that can support it, you can use an 82 ohm terminator at both ends. The 82 ohm terminators provide “extended node” capability which allows you to have up to 32 physical devices on the RIO link. (The number of logical racks capable of being addressed by the scanner is not affected.) This allows 1/4, 1/2 and 3/4 racks, Dataliners, Redipanels and Panelview devices to be attached to the link.

! Compatibility of 1771 Remote I/O Products with Extended Node Numbers

ATTENTION: Devices that are operating at 230.4K Baud must have 82 ohm terminators in place for proper operation.

Certain products are not compatible with the extended node capabilities obtained with the use of the 82 ohm terminator resistors. These products are listed below. Table 2.E NonĆcompatible Products Device #

#

Series

#

Page 29

Installing Your Module

Module Installation

2–15

Once you’ve determined the power requirements, keying, and wiring for your adapter module, and have set the appropriate switch assemblies, you can use the following procedure to install it. Refer to the Industrial Automation Wiring and Grounding Guidelines for Noise Immunity (publication 1770-4.1) for proper grounding and wiring methods to use when installing your module. ATTENTION: Remove system power before removing or installing your module in the I/O chassis. Failure to observe this warning could damage module circuitry and injure people.

! lockingĆbar pins

1.

Remove power from the I/O chassis before inserting (or removing) the module.

2.

On chassis equipped with a chassis locking bar, pull the locking-bar pins to release the locking bar and swing it up.

3.

Insert the module into slot.

4.

Place the module in the plastic tracks on the top and bottom of the leftmost slot. These slots guide the module into position.

5.

Press firmly and evenly to seat the module in its backplane connectors.

! 6.

ATTENTION: Do not force the module into the backplane connector. If you cannot seat the module with firm pressure, check the alignment and keying. Forcing the module can damage the backplane connector or the module.

Snap the chassis locking bar (or locking latch on earlier chassis) over the top of the module to secure it. Make sure the locking pins on the locking bar are fully engaged. Note: The chassis locking bar will not close if all modules are not properly seated.

Summary

7.

Swing field wiring arm up into place and press firmly until it latches.

8.

Reapply system power and check for proper operation.

In this chapter you learned how to install your adapter module. Chapter 3 tells you how to configure your module.

Page 30 read from a scan by OCR; it may hold reading errors

2-16 Installing Your Module

Publication 1771-UM001A-US-P - February 2000