The text of a manual · part 1 of 1
AC/DC (120V) Input Module Cat. No. 1771-IAD Series C Installation Instructions, pages 1 to 8
Pages 1 to 8 of 8
The original document is the PDF (88 KB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
For the Allen-Bradley 1771-IAD and Allen-Bradley 1771-IAD/C
Page 1
AC/DC (120V) Input Module Cat. No. 1771-IAD Series C Installation Instructions
To The Installer
This document provides information on: important pre-installation considerations power supply requirements initial handling procedures installing the module using the indicators for troubleshooting module specifications
Pre-installation Considerations
The 1771-IAD Series C module is compatible with all chassis except the 1771-A1, 1771-A2 and 1771-A4 chassis. Make sure no other input module or single card block transfer module is placed in the same module group when using 2-slot addressing. Any discrete output module may be used within the same module group.
Power Requirements
Your module receives its power through the 1771 I/O chassis backplane from the chassis power supply. The module requires 195mA from the output of this supply. Add this to the requirements of all other modules in the I/O chassis to prevent overloading the chassis backplane and/or chassis power supply.
Initial Handling
The ac/dc input module is shipped in a static-shielded bag to guard against electrostatic discharge damage. Observe the following precautions when handling the module. ATTENTION: This module is equipped with a plastic cover that is unique to all assembly numbers with the prefix 961440. (This part number is located near the backplane edge connector pins on the component-side of the circuit board.) Do not use this plastic cover on any other module.
Page 2
Installation Instructions AC/DC (120V) Input Module Cat. No. 1771-IAD Series C
Electrostatic Discharge Damage ATTENTION: Under some conditions, electrostatic discharge can degrade performance or damage the module. Observe the following precautions to guard against electrostatic damage. Wear an approved wrist strap grounding device, or touch a grounded object to discharge yourself before handling the module. Do not touch the backplane connector or connector pins. If you configure or replace internal components, do not touch other circuit components inside the module. If available, use a static-free work station. When not in use, keep the module in its static-shielded bag.
Installing Your Module
In this section, we tell you how to: change the delay time jumper key your I/O chassis install your module make your wiring connections
Changing the Delay Time Jumper Your module is equipped with an adjustable delay time jumper. Use the jumper to select between two input channel delay times. The delay time you choose applies to all sixteen of the module’s channels. Use this delay time:
If you want:
5ms to detect typical input readings
20ms to prevent detection of false inputs in high-noise environments
The module is shipped with the delay time jumper preset to 5ms. To change the delay time jumper to 20ms, do the following: 1.
Locate the delay time jumper selection plug at the top-right edge of the module circuit board, as shown in the following figure.
2.
Use your finger to slide the jumper off the 5ms position (the middle post and the right post).
3.
Carefully reposition the jumper by sliding it onto the 20ms position (the middle post and the left post). Top-right edge of circuit board
20ms
5ms Delay Time Jumper (shown in preset 5ms position) 12636-I
2
Page 3
Installation Instructions AC/DC (120V) Input Module Cat. No. 1771-IAD Series C
Keying Your I/O Chassis Use the plastic keying bands, shipped with each I/O chassis, to key the I/O slots to accept only this type of module. The module circuit board is slotted in two places on the rear edge. The position of the keying bands on the backplane connector must correspond to these slots to allow insertion of the module. You can key any connector in an I/O chassis to receive this module except for the left-most connector reserved for adapter or processor modules. Place keying bands between the following numbers labeled on the backplane connector: Between 10 and 12 Between 14 and 16 You can change the position of these keys if system redesign and rewiring makes insertion of a different module necessary.
Installing Your Input Module To install the ac/dc input module in your 1771 I/O chassis, follow the steps listed below. ATTENTION: Remove power from the 1771 I/O chassis backplane and field wiring arm before removing or installing an I/O module. Failure to remove power from the backplane or field wiring arm could cause module damage, degradation of performance, or injury. Failure to remove power from the backplane could cause injury or equipment damage due to possible unexpected operation.
1.
Turn off power to the I/O chassis.
2.
Place the module in the plastic tracks on the top and bottom of the slot that guides the module into position.
3.
Do not force the module into its backplane connector. Apply firm, even pressure on the module to seat it properly.
4.
Snap the chassis latch over the top of the module to secure its position.
5.
Connect the field wiring arm to the module.
6.
Make wiring connections to the field wiring arm as indicated in Figure 1. 3
Page 4
Installation Instructions AC/DC (120V) Input Module Cat. No. 1771-IAD Series C
Connecting Wiring to the Input Module Connections to the input module are made to the field wiring arm (cat. no. 1771-WH) shipped with the module. Attach the field wiring arm to the pivot bar on the bottom of the I/O chassis. The field wiring arm pivots upward and connects with the module so you can install or remove the module without disconnecting the wires. Figure 1 Connection Diagram
L1 ac/dc High Terminal A Terminal B Terminal C Terminal D Input 00 Input 01 Input 02 Input 03 Input 04 Input 05 Input 06 Input 07 Input 10 Input 11 Input 12 Input 13 Input 14 Input 15 Input 16 Input 17 Terminal E
A B C D 00 01 02 03 04 05 06 07 10 11 12 13 14 15 16 17 E
L2 ac/dc Low
Field Wiring Arm Cat. No. 1771-WH (Actual wiring runs in this direction.)
10589-I
Connect one terminal of your 2-wire input device to terminals 00 thru 17 (Figure 1). Connect L1 (high) ac/dc line to the other terminal of your input devices. Connect terminal E to the L2 (low) ac/dc return. Terminals A thru D are not used. Use stranded 14 or 16 gauge wire to minimize the voltage drop over long cable distances. 4
Page 5
Installation Instructions AC/DC (120V) Input Module Cat. No. 1771-IAD Series C
Important: You can use an AC (120V) Output Module (cat. no. 1771-OAD) to directly drive terminals on an AC/DC (120V) Input Module (cat. no. 1771-IAD) (Figure 2). Figure 2 Driving a 1771-IAD Module with a 1771-OAD Module AC (12-120V) Output Module (Cat. No. 1771-OAD)
AC/DC (120V) Input Module (Cat. No. 1771-IAD)
L1 120V ac High
Note: 1771-OAD output voltage range is 12-138V ac. However, the on-state voltage range of the 1771-IAD is 79-138V ac.
ac Low L2 10590-I
You can also use a 1771-OA Output module to drive an AC/DC (120V) Input Module (cat. no. 1771-IAD) but you must connect one of the following between the output terminal and L2 (common) (Figure 3). 2500 ohm, 10W resistor RG-1676-1 Electrocube (San Gabriel, California) Use the same ac power source to power both modules to ensure proper phasing and prevent module damage.
5
Page 6
Installation Instructions AC/DC (120V) Input Module Cat. No. 1771-IAD Series C
Figure 3 Driving a 1771-IAD Module with a 1771-OA Module AC (120V) Output Module (Cat. No. 1771-OA)
AC/DC (120V) Input Module (Cat. No. 1771-IAD)
L1 ac High
2500 ohm 10W resistor Note: 1771-OA output voltage range is 92-138V ac. However, the on-state voltage range of the 1771-IAD is 79-138V ac.
Interpreting the Status Indicators
L2 ac Low
10591-I
The front panel of your module contains one green module active indicator, and 16 red status indicators (figure 4). When the green module active indicator lights, the rack power supply has properly established 5Vdc. To properly interpret the red status indicators, the module active indicator must be lit. The red status indicators are provided for system logic side indication of individual inputs. When a red indicator lights, voltage is present on the terminal. The module transfers this information to the backplane for the processor to read. See ‘‘Troubleshooting” for a description, probable cause, and recommended action to take for common faults based on indicator responses.
6
Page 7
Installation Instructions AC/DC (120V) Input Module Cat. No. 1771-IAD Series C
Figure 4 Status Indicators
Module Active Indicator (green) ACTIVE 00 10 01 11 02 12 03 13 04 14 05 15 06 16 07 17
00 to 17 Status Indicators (red)
10592-I
Troubleshooting
Use this table to help you interpret the 1771-IAD status indicators and to troubleshoot module and system faults.
Indicator Status (color)
Description of Fault or System Status
Action to Take
Module active ON (green)
Normal Indication
None
Module active ON (green) and Input status ON (red)
Check for voltage on terminal.
If voltage is present, take no action. If no voltage is present, replace the module.
Module active ON (green) and Input status OFF
Input devices not functioning properly or faulty input circuitry on module.
1. Check input devices. 2. If input devices are OK, replace module.
No voltage on terminal.
None
Not valid unless module active indicator is on; when active is off, indicators do not represent processor status.
1. Check chassis power supply and module input power. 2. If power supplies are OK, replace module.
Module active OFF and Input status ON (red) or OFF
7
Page 8
Installation Instructions AC/DC (120V) Input Module Cat. No. 1771-IAD Series C
Specifications
Inputs per Module
16
Module Location
1771 Series B or later I/O chassis, 1771-AM1, -AM2 chassis
Nominal Input Voltage
120V ac @ 50/60Hz; 125V dc
Nominal Input Current
9.9mA @ 120V ac 60Hz; 8.7mA @ 120V ac 50Hz; 2.56mA @ 125V dc
On-state Voltage Range
79V to 138V ac or dc
Minimum On-state Current
5.95mA @ 79V ac 60Hz; 1.5mA @ 79V dc
Maximum Off-state Voltage
43V ac or dc
Maximum Off-state Current
3.0mA @ 43V ac 60Hz; 0.8mA @ 43V dc
Input Impedance
11.2K ohms @ 60Hz (0.18 microfarad in parallel with 47K ohms, in series with 820 ohms)
Peak Inrush Current
Inrush = VPS/820 ohm, where VPS = customer supply peak voltage
Input Signal Delay Off to On On to Off
5ms (+3ms) or 20ms (+5ms) @ 120V ac 60Hz selectable 3ms (+.1ms) or 10ms (+1ms) @ 120V dc selectable 25ms (+5ms) @ 120V ac or dc
Power Dissipation
8.8 Watts (max.), 1.0 Watts (min.)
Thermal Dissipation
30.1 BTU/hr (max.), 3.42 BTU/hr (min.)
Backplane Current
195mA @ 5V
Isolation Voltage
Tested at 2500V dc for 1 second per UL508 & CSA C22.2 #142
Environmental Conditions Operational Temperature Storage Temperature Relative Humidity Conductors
Wire Size Category
Keying Field Wiring Arm Wiring Arm Screw Torque
0o to 60oC (32o to 140oF) -40o to 85oC (-40o to 185oF) 5 to 95% (without condensation) 14 gauge stranded maximum 3/64 inch insulation maximum 11 Between 10 and 12 Between 14 and 16 Catalog Number 1771-WH 7-9 inch-pounds
1 Refer to publication 1770-4.1, Programmable Controller Wiring and Grounding Guidelines.
Allen-Bradley has been helping its customers improve productivity and quality for 90 years. A-B designs, manufactures and supports a broad range of control and automation products worldwide. They include logic processors, power and motion control devices, man-machine interfaces and sensors. Allen-Bradley is a subsidiary of Rockwell International, one of the world’s leading technology companies.
With major offices worldwide. Algeria • Argentina • Australia • Austria • Bahrain • Belgium • Brazil • Bulgaria • Canada • Chile • China, PRC • Colombia • Costa Rica • Croatia • Cyprus • Czech Republic • Denmark • Ecuador • Egypt • El Salvador • Finland • France • Germany • Greece • Guatemala • Honduras • Hong Kong • Hungary • Iceland • India • Indonesia • Israel • Italy • Jamaica • Japan • Jordan • Korea • Kuwait • Lebanon • Malaysia • Mexico • New Zealand • Norway • Oman • Pakistan • Peru • Philippines • Poland • Portugal • Puerto Rico • Qatar • Romania • Russia–CIS • Saudi Arabia • Singapore • Slovakia • Slovenia • South Africa, Republic • Spain • Switzerland • Taiwan • Thailand • The Netherlands • Turkey • United Arab Emirates • United Kingdom • United States • Uruguay • Venezuela • Yugoslavia World Headquarters, Allen-Bradley, 1201 South Second Street, Milwaukee, WI 53204 USA, Tel: (1) 414 382-2000 Fax: (1) 414 382-4444
Publication 1771-2.73 November 1993 8 Supersedes Publication 1771-2.73 September 1992
PN 955115-83 Copyright 1993 Allen-Bradley Company, Inc. Printed in USA