Page 1 of AC/DC (120V) Input Module Cat. No. 1771-IAD Series C Installation Instructions

Manual · Allen-Bradley

AC/DC (120V) Input Module Cat. No. 1771-IAD Series C Installation Instructions

Manual8 pagesPDF 88 KB

Installation instructions for the Allen-Bradley 1771-IAD Series C AC/DC (120V) 16-input module: jumper, keying, wiring and specs.

Download the PDF88 KB

Names · 2 models

The models it names

Filed with · 2 models

Also filed with these models on the old site

Summary

What is in it

Allen-Bradley installation instructions for the 1771-IAD Series C AC/DC (120V) input module for the 1771 I/O chassis. They cover pre-installation considerations, power requirements, handling and electrostatic discharge, setting the delay time jumper, keying the I/O chassis, installing the module, wiring to the 1771-WH field wiring arm, driving it from 1771-OAD or 1771-OA output modules, the status indicators, troubleshooting and specifications.

Its parts

  1. To The Installer
  2. Pre-installation Considerations
  3. Power Requirements
  4. Initial Handling
  5. Installing Your Module
  6. Specifications

From the manual · read page by page

Key facts from this manual

Each line names its page in the PDF.

Installation instructions (publication 1771-2.73, November 1993) for the Allen-Bradley 1771-IAD Series C AC/DC (120V) input module. They cover handling, the delay time jumper, chassis keying, installation, field wiring, the status indicators, troubleshooting and the specifications.

Device
AC/DC (120V) input module with 16 inputs for the 1771 I/O chassis p. 1, 8
Input voltage
120V ac at 50/60Hz or 125V dc nominal; ON from 79V to 138V ac or dc; OFF at 43V or less p. 8
Compatible chassis
All 1771 chassis except the 1771-A1, 1771-A2 and 1771-A4 p. 1
Backplane current
195mA at 5V from the chassis power supply p. 1, 8
Field wiring arm
Cat. No. 1771-WH, shipped with the module; screw torque 7-9 inch-pounds p. 8
Input delay
OFF to ON 5ms or 20ms (ac), selectable by jumper; ON to OFF 25ms p. 8
Input current
9.9mA at 120V ac 60Hz; 8.7mA at 120V ac 50Hz; 2.56mA at 125V dc p. 8
Operating temperature
0 to 60°C (32 to 140°F); storage -40 to 85°C p. 8
Wire size
14 gauge stranded maximum, 3/64 inch insulation maximum p. 8
Chassis keying
Keying bands between 10 and 12 and between 14 and 16 p. 3
Indicators
One green module active indicator and 16 red input status indicators p. 6
Power dissipation
8.8 W maximum, 1.0 W minimum (30.1 BTU/hr maximum) p. 8
Driving from outputs
A 1771-OAD can drive the inputs directly; a 1771-OA needs a 2500 ohm, 10W resistor to L2 p. 5
Publication
1771-2.73, November 1993 p. 8

What this manual walks you through

  • Changing the delay time jumper from 5ms to 20ms p. 2
  • Keying the I/O chassis slot p. 3
  • Installing the module in a 1771 I/O chassis p. 3
  • Wiring input devices to the field wiring arm p. 4
  • Driving the module from a 1771-OAD or 1771-OA output module p. 5, 6
  • Reading the status indicators p. 6, 7
  • Troubleshooting from the indicator states p. 7
  • Guarding against electrostatic discharge p. 2

Good to know

  • Remove power from the chassis backplane and field wiring arm before removing or installing the module. p. 3
  • With 2-slot addressing, no other input module or single card block transfer module may share its module group. p. 1
  • The plastic cover belongs only to assemblies with the prefix 961440 and must not be used on other modules. p. 1
  • When a 1771-OA drives this module, power both from the same ac source. p. 5
  • The red status indicators mean something only while the green active indicator is lit. p. 6

Questions this manual answers

Which chassis does the 1771-IAD work in?

The Series C module works in all 1771 chassis except the 1771-A1, 1771-A2 and 1771-A4. p. 1

How do I set the 1771-IAD input delay to 20 ms?

Slide the delay time jumper at the top-right edge of the board from the 5ms posts onto the 20ms posts (middle and left). p. 2

What wiring arm does the 1771-IAD use?

The 1771-WH field wiring arm, which ships with the module. p. 4

1771-IAD active light on but input light off

The input devices may not be working, or the module's input circuit is faulty; check the input devices, then replace the module if they are good. p. 7

How much backplane current does the 1771-IAD draw?

195mA from the chassis power supply. p. 1

Contents

Chapters and sections

Each line opens the PDF at its page.

  1. 1771-2.73, AC/DC (120V) Input Module Installation Instructions1
  2. To The Installer1
  3. Pre-installation Considerations1
  4. Power Requirements1
  5. Initial Handling1
    1. Electrostatic Discharge Damage2
  6. Installing Your Module2
    1. Changing the Delay Time Jumper2
    2. Keying Your I/O Chassis3
    3. Installing Your Input Module3
    4. Connecting Wiring to the Input Module4
    5. Interpreting the Status Indicators6
    6. Troubleshooting7
  7. Specifications8
  8. Back Cover8

From the PDF’s own bookmarks.

The whole text · 1 part

Read the manual here as text

Its text as extracted from the PDF, unedited, in parts; each page opens the PDF at that page.

  1. Pages 1 to 81-8

The file

Revision and size

RevisionPublication 1771-2.73, November 1993
PublisherAllen-Bradley
Pages8
PDF88 KB
TextText from the PDF itself.

The first pages · 3 of 8

Look before you download

Each page opens the PDF at that page.

Page 1
Page 1of 8
Page 2
Page 2of 8
Page 3
Page 3of 8

More documents · 1