Summary

What is in it

Allen-Bradley product data for the 1771 Universal I/O family of digital DC input and output modules. An overview explains status indicators, keying, power supply requirements, addressing modes, fault mode jumpers, input filtering, surge suppression and fuses, with data table and chassis compatibility tables. It is followed by a specification sheet for each module, including DC input modules 1771-IB, -IBD, -IBN, -IC, -IG, -IQ, -IT and -IV and DC output modules 1771-OB, -OBD, -OC, -OG, -OQ and -OVN.

Its parts

  1. DC Input Module (Cat. No. 1771-IB)
  2. DC Input Module (Cat. No. 1771-IBD Series B)
  3. DC Input Module (Cat. No. 1771-IBN Series C)
  4. DC Input Module (Cat. No. 1771-IC)
  5. DC Input Module (Cat. No. 1771-ICD Series B)
  6. TTL Input Module (Cat. No. 1771-IG)
  7. DC Input Module (Cat. No. 1771-IGD)
  8. DC Input Module (Cat. No. 1771-IH)
  9. DC Input Module (Cat. No. 1771-IQ Series B)
  10. DC Input Module (Cat. No. 1771-IQ16 Series B)
  11. Fast Response DC Input Module (Cat. No. 1771-IT)
  12. DC Input Module (Cat. No. 1771-IV)
  13. DC (10-30V) Input Module (Cat. No. 1771-IVN Series C)
  14. DC Output Module (Cat. No. 1771-OB Series C)
  15. DC Output Module (Cat. No. 1771-OBD Series C)

From the manual

Key facts from this manual

Each line names its page in the PDF.

Product data (publication 1771-2.180, July 1996) for the 1771 digital dc input and output modules: thirteen dc input modules from 1771-IB to 1771-IVN and nine dc output modules from 1771-OB to 1771-OVN. Each module has a page of application notes, a wiring diagram and a specification table, after overview pages on addressing, fault modes, fuses and chassis compatibility. The ac modules such as the 1771-IA and 1771-IAD it is filed under are not in it; the overview names 1771-2.182 as the ac module document.

Read for this summary: pages 1 to 17, 22 to 23 and 44 to 45 of 59.

What it is
Digital dc I/O module for the 1771 Universal I/O chassis, interfacing ON/OFF devices to Allen-Bradley programmable controllers p. 1
Power source
Draws power through the 1771 I/O chassis backplane from the chassis power supply p. 2
Isolation voltage
1500V ac rms (each module read: IB, IBD, IBN, IG, OC) p. 13, 15, 17, 23, 45
Operating temperature
0 to 60 C (32 to 140 F); storage -40 to 85 C p. 13, 15, 17, 23, 45
Status indicators
Front-panel indicator for each input or output; some modules add a fuse-blown indicator p. 2
Wiring
14 gauge (2mm2) stranded maximum; wiring arm screw torque 7-9 inch-pounds p. 13
1771-IB
8 inputs, 10 to 27V dc, backplane current 74mA at 5V dc, wiring arm 1771-WA p. 13
1771-IBD Series B
16 inputs, 10 to 30V dc, backplane current 250mA, wiring arm 1771-WH (fused 1771-WHF or 1771-WHFB optional) p. 15
1771-IBN Series C
32 sinking inputs, 10 to 30V dc, backplane current 280mA maximum p. 17
1771-IG
8 TTL inputs, customer supply 5V dc (+0.25V), 500mA max per module, wiring arm 1771-WC p. 23
1771-OC Series C
8 outputs, 42 to 53V dc, 1.5A per output and 8A per module, fuses 2A 8AG one per output p. 45
Replacement fuse kits
1771-FC for output modules; 1771-FD (3A) for the 1771-WHF arm; 1771-FD2 (1.5A) for the 1771-WHFB arm p. 7
Fused wiring arms
1771-WHF or -WHFB, a fuse for each output, in place of the 1771-WH arm p. 6
Current chassis
1771-A1B, -A2B, -A3B, -A3B1, -A4B, -AM1, -AM2 p. 4

What this manual walks you through

  • Checking addressing modes and chassis compatibility for each module p. 4, 5
  • Setting the fault mode plug to last state or reset p. 3, 14
  • Keying I/O chassis slots to accept one module type p. 2
  • Adding surge suppression for inductive loads p. 6
  • Choosing replacement fuse kits p. 7
  • Wiring two- and three-wire devices to the 1771-IB p. 12, 13
  • Driving a 1771-IBN input module from a 1771-OBN output module p. 17
  • Selecting High = True or Low = True logic on the 1771-IG p. 22
  • Driving a 1771-IC input module from a 1771-OC output module p. 45

Good to know

  • Total the backplane current of all modules in a chassis to avoid overloading the power supply or backplane. p. 2
  • Modules marked R need an input module and an output module in two adjacent slots (even/odd) starting at slot 0. p. 4
  • The 1771-IBD needs a series B chassis, and with 2-slot addressing no other input module may share its module group. p. 14
  • An extra suppression device is advised when an output drives an inductive load in series with or parallel to a hard contact. p. 6
  • On the 1771-IBN, 14 gauge wire on all terminals may keep the wiring arm cover from closing. p. 17

Questions this manual answers

What input voltage does the 1771-IB take?

The 1771-IB has 8 inputs rated 10 to 27V dc, with 8mA at 12V dc and 24mA at 24V dc nominal input current. p. 13

Which wiring arm fits the 1771-IBD?

The standard arm is the 1771-WH; the fused 1771-WHF (3A) or 1771-WHFB (1.5A) is optional. p. 15

What fuses does the 1771-OC use?

It uses 2A 8AG fuses, one per output, and its top indicator lights when a fuse has blown. p. 44, 45

Can the 1771-IBN go in an older 1771 chassis?

No, the 1771-IBN must be used in a series B 1771 I/O chassis. p. 16

Is the 1771-IA described in this document?

No, this is the dc module data sheet; the overview names 1771-2.182 as the document for the ac input and output modules. p. 2

Contents

Chapters and sections

Each line opens the PDF at its page.

  1. 1771-2.180, 1771 Digital I/O DC Input andOutput Module Product Data1
  2. DC Input Module (Cat. No. 1771-IB)12
  3. DC Input Module (Cat. No. 1771-IBD Series B)14
  4. DC Input Module (Cat. No. 1771-IBN Series C)16
  5. DC Input Module (Cat. No. 1771-IC)18
  6. DC Input Module (Cat. No. 1771-ICD Series B)20
  7. TTL Input Module (Cat. No. 1771-IG)22
  8. DC Input Module (Cat. No. 1771-IGD)24
  9. DC Input Module (Cat. No. 1771-IH)26
  10. DC Input Module (Cat. No. 1771-IQ Series B)28
  11. DC Input Module (Cat. No. 1771-IQ16 Series B)30
  12. Fast Response DC Input Module (Cat. No. 1771-IT)32
  13. DC Input Module (Cat. No. 1771-IV)34
  14. DC (10-30V) Input Module (Cat. No. 1771-IVN Series C)36
  15. DC Output Module (Cat. No. 1771-OB Series C)38
  16. DC Output Module (Cat. No. 1771-OBD Series C)40
  17. DC Output Module (Cat. No. 1771-OBN Series B)42
  18. DC Output Module (Cat. No. 1771-OC Series C)44
  19. DC Output Module (Cat. No. 1771-OG)46
  20. DC Output Module (Cat. No. 1771-OGD Series B)48
  21. DC Output Module (Cat. No. 1771-OQ Series B)50
  22. DC Input Module (Cat. No. 1771-OQ16 Series B)52
  23. DC Output Module (Cat. No. 1771-OVN Series B)54
  24. Notes56
  25. Support Services58
  26. 1771-2.180, Back Cover59

From the PDF’s own bookmarks.

The whole text · 6 parts

Read the manual here as text

Its text as extracted from the PDF, unedited, in parts; each page opens the PDF at that page.

  1. Pages 1 to 101-10
  2. Pages 11 to 2011-20
  3. Pages 21 to 3021-30
  4. Pages 31 to 4031-40
  5. Pages 41 to 5041-50
  6. Pages 51 to 5951-59

The file

Revision and size

RevisionPublication 1771-2.180, July 1996
PublisherAllen-Bradley
Pages59
PDF987 KB
TextText from the PDF itself.

The first pages · 3 of 59

Look before you download

Each page opens the PDF at that page.

Page 1
Page 1of 59
Page 2
Page 2of 59
Page 3
Page 3of 59