Page 1 of Encoder/Counter Modules User Manual (Cat. Nos. 1771-IJ and 1771-IK)

Manual · Allen-Bradley

Encoder/Counter Modules User Manual (Cat. Nos. 1771-IJ and 1771-IK)

Manual68 pagesPDF 388 KB

User manual for the Allen-Bradley 1771-IJ and 1771-IK encoder/counter modules: switch settings, installation and PLC programming.

Download the PDF388 KB

Covers · 1 model

The models it covers

Summary

What is in it

The user manual for the Allen-Bradley 1771-IJ (5V dc) and 1771-IK (12-24V dc) encoder/counter modules for the 1771 I/O system. It explains how the module counts pulses from encoders and similar devices and drives two outputs from count comparisons, how to set its switches, install and wire it, and how to program it with single transfer or block transfer for PLC-2, PLC-3 and PLC-5 processors, including extending the count beyond 999, with specifications in the appendix.

Its parts

  1. Introduction
  2. Preliminary Adjustments
  3. Installation
  4. Module/Processor Communication
  5. Single Transfer Programming
  6. Block Transfer Programming
  7. Special Programming

From the manual

Key facts from this manual

Some pages are scans or cannot be read; this says only what the readable text supports. Each line names its page in the PDF.

Allen-Bradley user manual (publication 1771-UM006B-EN-P, June 2002) for the 1771-IJ and 1771-IK Encoder/Counter Modules, which count pulses from encoders and counters in a 1771 I/O chassis. It covers switch settings, installation and wiring, communication with the processor, single and block transfer programming, and specifications.

Read for this summary: pages 1 to 4, 7 to 14, 21 to 25, 28 to 29, 59 to 61 and 65 of 68.

What it is
Encoder/counter module that keeps its own count of input pulses from encoders, high speed optical counters and switches p. 9
External power
1771-IK: 12-24V dc external power supply p. 10
Input pulse rate
50kHz maximum p. 9
Outputs
1771-IK: 2 open collector outputs without pull-up resistors, 500mA max per output, Vout = Vext p. 59
Input thresholds
1771-IK: at Vext 12V dc, Vih = 7.2V dc max and Vil = 4.8V dc max; at Vext 24V dc, Vih = 14.4V dc max and Vil = 9.6V dc max p. 59
Count formats
BCD 000 to 999 with carry and borrow bits, or 12-bit binary p. 10, 29
Backplane current
5V: 1.2A typical, 1.4A maximum p. 59
Compatible processors
Any Allen-Bradley processor that uses the 1771 I/O structure; fits any 1771 I/O chassis p. 9, 22
Limit switch input
12 to 48V dc on voltage, 10mA maximum at 48V dc p. 12
Field wiring arms
Two 12-terminal gold-plated 1771-WB arms shipped with the module; screw torque 7-9 pound-inches (0.6-0.7Nm) p. 11, 60
Keying
1771-IK: left connector between 6 and 8 and between 20 and 22; right connector between 4 and 6 and between 32 and 34 p. 25
Input cable
Belden 8761 for pulse counting below 20K Hz, Belden 9182 up to 50k Hz, Belden 8725 for encoders below 20k Hz p. 22
Power dissipation
1771-IK: 12.1 Watts maximum (41.3 BTU/hr) p. 59
Operating temperature
32 to 140°F (0 to 60°C); storage -40 to 185°F (-40 to 85°C) p. 60

What this manual walks you through

  • Setting the SW-1 switches for transfer type, count resolution, encoder or counter mode and data format p. 13, 14
  • Choosing times 1, times 2 or times 4 count resolution p. 14
  • Reading the status indicators and the power-up self-test p. 11
  • Driving outputs from a separate load supply p. 12
  • Choosing and grounding shielded input cable p. 22, 24
  • Wiring encoder and counter applications to the field wiring arm p. 23, 24
  • Keying the I/O slot p. 25
  • Reading the count and status bits in the input status word p. 28, 29

Good to know

  • Remove power from the I/O chassis backplane and the wiring arm before removing or installing the module. p. 22
  • Input devices may be no more than 40 cable feet from the module. p. 22
  • The module must sit in a single module group and cannot straddle two groups. p. 22
  • A separate load supply for the outputs should not exceed 30V dc. p. 12
  • Single transfer programming is only for a module in a local I/O chassis. p. 13

Questions this manual answers

What power supply does the 1771-IK need?

A 12-24V dc external supply connected to the field wiring arm. System power comes through the backplane from the 5V dc chassis supply. p. 10, 12

How fast can the 1771-IK count pulses?

Its maximum detectable input pulse frequency is 50kHz. p. 9

What does the FAULT LED on the 1771-IK mean?

It flashes briefly during the power-up self-test; if it stays on, the module has detected a fault. It also lights if block transfer communication breaks down. p. 11

How do I key the I/O slot for a 1771-IK?

Snap keying bands on the upper backplane connectors: left connector between 6 and 8 and between 20 and 22, right connector between 4 and 6 and between 32 and 34. p. 25

What cable should I use for encoder inputs on the 1771-IK?

Belden 8725 four twisted pair cable for encoder applications below 20k Hz, with input devices no more than 40 cable feet away. p. 22

The whole text · 7 parts

Read the manual here as text

Its text as extracted from the PDF, unedited, in parts; each page opens the PDF at that page.

  1. Pages 1 to 101-10
  2. Pages 11 to 2011-20
  3. Pages 21 to 3021-30
  4. Pages 31 to 4031-40
  5. Pages 41 to 5041-50
  6. Pages 51 to 6051-60
  7. Pages 61 to 6861-68

The file

Revision and size

Part no.1771-UM006B-EN-P
RevisionJune 2002
PublisherRockwell Automation
Pages68