Encoder/Counter Modules User Manual (Cat. Nos. 1771-IJ and 1771-IK), pages 51 to 60

Pages 51 to 60 of 68

The original document is the PDF (388 KB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

For the Allen-Bradley 1771-IK

Page 51

Block Transfer Programming

6–7

PLC-3 Family Processors Use the following ladder logic with PLC-3 or PLC-3/10 processors. This program assumes that your application requires a single BTR and BTW instruction to pass data between the processor and the module. Ladder logic alternates the execution of BTR and BTW instructions. The processor checks data validity before accepting read data, and sets one enable bit at a time. Refer to Figure 6.5 for generalized ladder logic, and to Figure 6.6 for example ladder logic with entered values. Figure 6.5 Generalized Ladder Logic for PLC-3 Block Transfer

1

PLC-3 AC Power Loss Bit

2

XOR

XOR

A = BTW cntl B = BTW cntl

A = BTR cntl B = BTR cntl

R = BTW cntl

R = BTR cntl

BTR

BTW R

DN

LE

G EQU

M

A = BTW cntl B = BTR cntl

Data

DN

Length Cntl

3

BTW DN

ER BTR

R G

LE

M Data

DN

Length Cntl

ER 15045

Publication 1771-UM006B-EN-P - June 2002

Page 52

6–8

Block Transfer Programming

Figure 6.6 Sample Ladder Logic for PLC-3 Block Transfer RUNG NUMBER RM1 S0003

1

03

XOR

XOR

A XOR B = R

A XOR B = R

A : WB001:0030

A : WB001:0020

B : WB001:0030

B : WB001:0020

R : WB001:0030

R : WB001:0020

RUNG NUMBER RM2 2

WB001:0020 15 EQU A = B A : WB001:0030 B : WB001:0020

BTW BLOCK XFER WRITE 002 RACK : 1 GROUP : 1 = HIGH MODULE : FB002:0150 DATA: 0 LENGTH = FB001:0030 CNTL:

CNTL LE 02 CNTL DN 05 CNTL ER 03

RUNG NUMBER RM3 WB001:0030 3 05

BTR BLOCK XFER READ 002 RACK : 1 GROUP : 1 = HIGH MODULE : FB002:0220 DATA: 0 LENGTH = FB001:0020 CNTL:

CNTL LE 12 CNTL DN 15 CNTL ER 13 15064

Rung Descriptions Rung 1 - Rung one is true only at power up. It uses status word 3, bit 03 (the PLC-3’s AC power loss bit) to zero the control file of both the BTR and BTW instructions. Rung 2 - The equal instruction is used at power up. At power up, the BTR and BTW control files both equal zero, so the BTW instruction is enabled. Rung 2 and 3 - During normal program execution, the BTW and BTR instructions are alternately executed. The done bit of either instruction enables the next block transfer instruction. After power up, the BTR and BTW done bits are used to alternate reads and writes.

Publication 1771-UM006B-EN-P - June 2002

Page 53

Block Transfer Programming

6–9

PLC-5 Family Processors You can use the following ladder logic with PLC-5 processors. This program assumes that your application requires a single BTR and BTW to pass data between the processor and the module. Ladder logic alternates the execution of BTR and BTW instructions. The processor checks data validity before accepting read data, and sets one enable bit at a time. Refer to Figure 6.7 for generalized ladder logic, and to Figure 6.8 for example ladder logic with entered values. Figure 6.7 Generalized Ladder Logic for PLC-5 Block Transfer 1

BTW

BTR

EN

EN

BTW

BTR

EN

EN

2

BTW Control Block xxx

Data File yyy

Continuous no

BTR Control Block zzz

Data File aaa

Continuous no 15047

Publication 1771-UM006B-EN-P - June 2002

Page 54

6–10

Block Transfer Programming

Figure 6.8 Example Ladder Logic for PLC-5 Block Transfer File 2, Rung 0

File 2, Rung 1

N10:10

N11:10

15

15

N10:10

N11:10

15

15

BTW BLOCK TRNSFR WRITE

EN

Rack

0

Group

0

Module

0

Control Block

N10:10

Data File

N10:15

Length

0

Continuous

N

DN ER

BTR BLOCK TRNSFR READ

EN

Rack

0

Group

0

Module

DN

0

Control Block

N11:10

Data File

N11:15

Length

0

Continuous

N

ER

15965

Rung Descriptions Rungs 0 and 1 - Rungs 0 and 1 execute BTW and BTR instructions alternately. When the processor completes the BTW instruction, it enables the BTR instruction immediately in the same scan. Enabling a block transfer instruction places the block transfer request in queue. There is one queue for each I/O chassis. Waiting time depends on the number of queued requests ahead of it.

Publication 1771-UM006B-EN-P - June 2002

Page 55

Chapter

7

Special Programming Extending the Count Beyond 999

The input Status word stores a maximum count of 999 (BCD). If using binary resolution, the maximum count is 1111 1111 1111 (4095 binary). To count beyond these full scale values, you may want to use either of the following ladder programs for PLC–2 or PLC–3 family processors. Both programs (Figure 7.1 and Figure 7.2) extend the count beyond 999 (4095 binary) in the same manner. Either program compares the new count value with the value in the previous scan (old value). If the difference of the new value less the old value is greater than a constant (a constant less than 999/2 or 4095/2), the count passed through zero. If the sign of the difference is negative, the up counter is incremented by one; if positive the down counter is decremented by one.

Publication 1771-UM006B-EN-P - June 2002

Page 56

7–2

Special Programming

Figure 7.1 Ladder Logic for Extending the Count Beyond 999 (PLC-2 Program) SUBTRACT PREVIOUS COUNT FROM CURRENT COUNT. STORE IN 0077.

1

CURRENT PREVIOUS SCAN IJ/IK COUNT COUNT 0113 0577 GET GET 125 168

NEW/OLD COUNT DIFF. 0077 043

IF THE DIFFERENCE IS GREATER THAN A CONSTANT (COUNT PASSED THROUGH ZERO), THEN INCREMENT THE COUNT. THE CONSTANT MUST BE LESS THAN 1/2 THE TOTAL COUNTS OF THE IJ/IK (HALF OF 999 OR 4095).

2

NEW/OLD COUNT CONSTANT DIFF. 0077 0072 < GET 043 400

PASSED THROUGH ZERO 0076 00

AFTER PASSING THROUGH 0: IF THE SIGN OF THE DIFFERENCE IS NEGATIVE THEN INCREMENT THE COUNT, IF POSITIVE THEN DECREMENT THE COUNT.

3

PASSED DIFF. THROUGH VALUE ZERO NEGATIVE 0076 0077 00

4

16

DIFF. PASSED THROUGH VALUE POSITIVE ZERO 0077 0076 00

16

MOST SIGNIF DIGITS 0052 Ctu Pre 999 Acc 002 MOST SIGNIF DIGITS 0052 Ctd Pre 999 Acc 002

DISPLAY THE TOTAL COUNT AND MOVE THE CURRENT COUNT TO THE PREVIOUS COUNT

5

MOST SIGNIF DIGITS 0052 GET 002

CURRENT IJ/IK COUNT 0113 GET 125

Publication 1771-UM006B-EN-P - June 2002

PREVIOUS SCAN COUNT 0577 Put 168

Page 57

Special Programming

7–3

Figure 7.2 Ladder Logic for Extending the Count Beyond 999 (PLC-3 Program) MVM

RUNG NUMBER RMO

MOVE WITH MASK A : WB002:0200 0110000101011100 B : WB005:0000 000011111111111111 R : WB005:0001 0000000101011100 MOV MOVE FROM A TO R A : WB005:0001 0000000101011100 R : WN005:0000 348

RUNG NUMBER RM1

SUB A - B = R A : WN005:0000 348 B : WN005:0001 348 R : WN005:0002 0

RUNG NUMBER RM2 LES

A < B

A : WN005:0002 0

WN005:0002 ] / [ 17

A > B

A : WN005:0002 0 B : WN005:0004 500

CP = 32000 CA =

B : WN005:0003 -500 GRT

CTU COUNTER UP C0100

WN005:0002 ] [ 17

CTD COUNTR DOWN C0100 CP = 32000 CA =

RUNG NUMBER RM3

4

4

C0100 ( CU ) 17 C0100 ( DN ) 15 C0100 ( CD ) 16 C0100 ( DN ) 15

MOV MOVE FROM A TO R A : WN005:0000 348 R : WN005:0001 348

Publication 1771-UM006B-EN-P - June 2002

Page 58

7–4

Special Programming

Rung Descriptions (Figure 7.2) Rung 0 – This rung strips the upper byte of the count value and stores the value. A = BTR status B = Mask R = Temporary count storage with upper byte removed A = Temporary count storage with upper byte removed R = New count value Rung 1 – This rung subtracts the old count value from the new value and stores the difference with its sign. A = New count value B = Old count value R = Difference of new count value less old value Rung 2 – This rung looks at the sign and magnitude of the difference from rung 1 and compares it with a constant (a constant less than 999/2 or 4095/2). If positive, the up counter is incremented by one; if negative, the down counter is decremented by one. Rung 3 – This rung moves the new count value (A) to the old count storage location (R). A = New count value R – Old value storage location

Publication 1771-UM006B-EN-P - June 2002

Page 59

Appendix

A

Specifications

Specifications - 1771-IJ and ĆIK Encoder Counter Modules General Input Specifications

Number of Counters

1

Counter Input (switch selectable)

Single channel (counter) Dual channel (encoder)

Input Pulse Rate

50KHz maximum

Data Transfer Modes (switch selectable)

Single transfer mode Block transfer mode

1771-IJ External supply

5V dc, +0.25V

Input Ratings

Vin = 0-5V dc Vih (min) = 2.4V dc Vil (max) = 0.6V dc Device driving input terminal must be able to sink 16A minimum.

Output Ratings

2 open-collector outputs without internal pull-up resistors Iout = 500mA maximum per output Vout = 5V dc maximum

Power Dissipation

1771-IJ - 6.7 Watts maximum

Thermal Dissipation

1771-IJ - 22.9 BTU/hr

1771-IK External Supply (Vext)

12-24V dc Input circuits require 170mA maximum Output circuits require 1.08A maximum

Input Ratings

0 < Vin < Vext For Vext = 12V dc: Vih = 7.2V dc max; Vil = 4.8V dc max Device driving input terminal must sink (or source if selected on Channel A) 10mA For Vext = 24V dc: Vih = 14.4V dc max; Vil = 9.6V dc max Device driving input terminal must sink (or source if selected on Channel A) 20mA

Output Ratings

2 open collector outputs without internal pull-up resistors. Iout = 500mA max per output Vout = Vext

Power Dissipation

1771-IK - 12.1 Watts maximum

Thermal Dissipation

1771-IK - 41.3 BTU/hr

General Specifications

Module Location

Cat. No. 1771 I/O chassis

I/O Isolation

Tested to 1500V ac for 1s

Limit Switch Input

12-48V dc

Backplane Power Supply 5V Current Requirements

1.2A typical 1.4A maximum

Current consumption from external power supply

150mA @ 12V dc 75mA @ 24V dc

Publication 1794-UM006B-EN-P - June 2002

Page 60

A–2

Specifications

Specifications - 1771-IJ and ĆIK Encoder Counter Modules Indicators

2 Channel A and B status 1 Marker 1 Limit 2 Output 1 and 2 1 Red Fault

Keying

1771-IJ 1771-IK

Left connector: Between 6 and 8; 18 and 20 Right connector: Between 4 and 6; 32 and 34 Left connector: Between 6 and 8; 20 and 22 Right connector: Between 4 and 6; 32 and 34 Note: Modules must be in a single module group (slots 0 and 1). Do not straddle 2 module groups.,

Environmental Conditions Operational Temperature

IEC 60068-2-1 (Test Ad, Operating Cold) IEC 60068-2-2 (Test Bd, Operating Dry Heat) IEC 60068-2-14 (Test Nb, Operating Thermal Shock) 32 to 140°F (0 to 60°C)

Storage Temperature

IEC 60068-2-1 (Test Ab, Unpackaged, Nonoperating Cold) IEC 60068-2-2 (Test Bb, Unpackaged, Nonoperating Dry Heat) IEC 60068-2-14 (Test Na, Unpackaged, Nonoperating Thermal Shock) -40 to 185°F (-40 to 85°C)

Relative Humidity

IEC 60068-2-30 (Test Db, Unpackaged, Nonoperating Damp Heat) 5 to 95% noncondensing

Shock Operating Nonoperating

IEC 60068-2-27 (Test Ea, Unpackaged Shock) 30g 50g

Vibration

IEC 60068-2-6 (Test Fc, Operating) 2g @ 10-500Hz

ESD Immunity

IEC 61000-4-2 4kV contact discharges

Radiated RF Immunity

IEC 61000-4-3 10V/m with 1kHz sine-wave 80% AM from 30MHz to 1000MHz 10V/m with 200Hz 50% Pulse 100% AM at 900MHz

EFT/B Immunity

IEC 61000-4-4 +1kV @ 5kHz on signal ports

Surge Transient Immunity

IEC 61000-4-5 +2kV line-earth (CM) on shielded ports

Conducted RF Immunity

IEC 61000-4-6 10V rms with 1kHz sine wave 80% AM from 150kHz to 30MHz

Emissions

CISPR 11 Group 1, Class A (with appropriate enclosure)

Enclosure Type

None (open style

Input Conductors Wire Category Length (max)

Belden 8761 (for pulse counter applications below 20KHz); Belden 9182 (for frequencies up to 50KHz) Belden 8725 (for twisted pair encoder applications below 20KHz) 21 Sensor must be within 40ft of the module

Field Wiring Arm

Cat. No. 1771-WB

Field Wiring Arm Screw Torque

7-9 pound-inches (0.6-0.7Nm)

Publication 1794-UM006B-EN-P - June 2002