Browse
(440) 299-7778
Menu
(440) 299-7778
One-year parts and labor warranty30-day money-back guaranteeContact
Page 1 of DC (12-24V) Input Module, Cat. No. 1771-IB, Installation Data

Manual · Allen-Bradley

DC (12-24V) Input Module, Cat. No. 1771-IB, Installation Data

Manual6 pagesPDF 64 KB

Installation data for the Allen-Bradley 1771-IB DC (12-24V) input module: power, keying, wiring, status indicators and specifications.

Download the PDF64 KB

Covers · 1 model

The models it covers

Summary

What is in it

Installation data for the Allen-Bradley 1771-IB DC (12-24V) input module, an 8-input module for the 1771 I/O chassis. It lists compatible 2 and 3-wire devices, input filtering delays and power requirements, then covers electrostatic handling, keying the chassis, installing the module, wiring 2-wire and 3-wire devices through the 1771-WA field wiring arm, reading the red status LEDs, and the full specifications.

Its parts

  1. To The Installer
  2. Pre-installation Considerations
  3. Power Requirements
  4. Initial Handling
  5. Installing Your Module
  6. Interpreting the Status Indicators
  7. Specifications

From the manual · read page by page

Key facts from this manual

Each line names its page in the PDF.

Allen-Bradley installation data (publication 1771-2.4, May 1990) for the 1771-IB DC (12-24V) input module. It covers which field devices it accepts, its backplane power draw, static handling, keying the I/O chassis, installing the module and wiring 2-wire and 3-wire devices, reading the status indicators, and the module specifications.

What it is
8-input dc (12-24V) input module for a 1771 I/O chassis p. 6
Input voltage range
10 to 27V dc p. 6
Input current
8mA at 12V dc, 24mA at 24V dc nominal p. 6
On and off thresholds
On at 10V dc minimum; off at 7.0V dc and 3.0mA maximum p. 6
Backplane current
74mA @ 5V dc p. 1, 6
Field wiring arm
10-terminal wiring arm, cat. no. 1771-WA, shipped with the module p. 3
Compatible devices
2- and 3-wire dc proximity switches, photoelectric sensors, pushbuttons, limit, float and selector switches p. 1
Wiring
Inputs on terminals 0 through 7, dc common on terminal B, terminal A not used p. 4
Keying
Keying bands between 4 and 6 and between 14 and 16 p. 2
Power dissipation
5.7 Watts max, 0.4 Watts min; 19.3 BTU/hr max p. 6
Status indicators
8 red LEDs, one per input, lit when voltage is on the terminal p. 5
Driven by output modules
Can be driven directly from 1771-OBD and 1771-OB dc output modules p. 4

What this manual walks you through

  • Checking device leakage and the chassis power budget p. 1
  • Handling the module to avoid static damage p. 2
  • Keying an I/O chassis slot for the 1771-IB p. 2
  • Installing the module in a 1771 Series B I/O chassis p. 3
  • Wiring 2-wire and 3-wire input devices p. 4, 5
  • Reading the input status indicators p. 5

Good to know

  • Off-state leakage of 3-wire devices should not exceed 3mA. p. 1
  • Remove power from the chassis backplane and wiring arm before removing or installing the module. p. 3
  • Reverse polarity or ac voltage could damage the module. p. 3
  • When driving it from a 1771-OB or 1771-OBD, power both modules from the same dc source. p. 4
  • The left-most chassis connector is reserved for the adapter or processor and cannot be keyed for this module. p. 2

Questions this manual answers

How many inputs does the 1771-IB have?

Eight dc inputs, wired to terminals 0 through 7 of the 1771-WA wiring arm. p. 4, 6

What voltage does the 1771-IB accept?

10 to 27V dc; an input is on at 10V dc minimum. p. 6

Where do I put the keying bands for a 1771-IB?

Between 4 and 6 and between 14 and 16 on the backplane connector. p. 2

How much backplane current does the 1771-IB draw?

74mA from the chassis power supply. p. 1

What wiring arm goes with the 1771-IB?

The 10-terminal 1771-WA field wiring arm, which ships with the module. p. 3

Contents

Chapters and sections

Each line opens the PDF at its page.

  1. 1771-2.4, DC (12-24V) Input Module Installation Data1
  2. To The Installer1
  3. Pre-installation Considerations1
  4. Power Requirements1
  5. Initial Handling2
    1. Electrostatic Discharge Damage2
  6. Installing Your Module2
    1. Keying Your I/O Chassis2
    2. Installing the Input Module3
    3. Connecting Wiring to the Input Module3
  7. Interpreting the Status Indicators5
  8. Specifications6
  9. Back Cover6

From the PDF’s own bookmarks.

The whole text · 1 part

Read the manual here as text

Its text as extracted from the PDF, unedited, in parts; each page opens the PDF at that page.

  1. Pages 1 to 61-6

The file

Revision and size

Part no.1771-2.4
RevisionMay 1990
PublisherAllen-Bradley
Pages6
PDF64 KB
TextText from the PDF itself.
1771-2.4

The first pages · 3 of 6

Look before you download

Each page opens the PDF at that page.

Page 1
Page 1of 6
Page 2
Page 2of 6
Page 3
Page 3of 6

More documents · 1

For the same models