For the Allen-Bradley 1771-IB

Page 1

DC (12-24V) Input Module Cat. No. 1771-IB Installation Data

To The Installer

This document provides information on: important pre–installation considerations power supply requirements initial handling procedures installing the module using the indicators for troubleshooting module specifications

Pre-installation Considerations

The 1771–IB module is compatible with the following 2 and 3–wire devices: DC proximity switches photoelectric sensors pushbuttons limit switches float switches selector switches The off–state leakage current of your 3–wire devices should not exceed 3mA. This module contains input filtering to limit the effect of voltage transients caused by contact bounce and/or radiated electrical noise. The delay due to input filtering is nominally 12+7ms for turning inputs on, and 20+7ms for turning inputs off.

Power Requirements

Your module receives its power through the 1771 I/O chassis backplane from the chassis power supply. The module requires 74mA from the output of this supply. Add this to the requirements of all other modules in the I/O chassis to prevent overloading the chassis backplane and/or backplane power supply.

Page 2

Installation Data DC (12-24V) Input Module Cat. No. 1771-IB Initial Handling

The dc input module is shipped in a static–shielded bag to guard against electrostatic discharge damage. Observe the following precautions when handling the module.

Electrostatic Discharge Damage ATTENTION: Under some conditions, electrostatic discharge can degrade performance or damage the module. Observe the following precautions to guard against electrostatic damage.

Wear an approved wrist strap grounding device, or touch a grounded object to discharge yourself before handling the module. Do not touch the backplane connector or connector pins. If you configure or replace internal components, do not touch other circuit components inside the module. If available, use a static–free work station. When not in use, keep the module in a static–shielded bag.

Installing Your Module

In this section we tell you how to key your I/O chassis, install your module and make your wiring connections.

Keying Your I/O Chassis Use the plastic keying bands, shipped with each I/O chassis, to key the I/O slots to accept only this type of module. The module circuit board is slotted in two places on the rear edge. The position of the keying bands on the backplane connector must correspond to these slots to allow insertion of the module. You can key any connector in an I/O chassis to receive this module except for the left–most connector reserved for adapter or processor modules. Place keying bands between the following numbers labeled on the backplane connector: Between 4 and 6 Between 14 and 16 You can change the position of these keys if system redesign and rewiring makes insertion of a different module necessary.

2

Page 3

Installation Data DC (12-24V) Input Module Cat. No. 1771-IB

Installing the Input Module To install the dc input module in your 1771 Series B I/O chassis, follow the steps listed below. ATTENTION: Remove power from the 1771 I/O chassis backplane and wiring arm before removing or installing an I/O module. Failure to remove power from the backplane or wiring arm could cause module damage, degradation of performance, or injury. Failure to remove power from the backplane could cause injury or equipment damage due to possible unexpected operation.

1.

Turn off power to the I/O chassis.

2.

Place the module in the plastic tracks on the top and bottom of the slot that guide the module into position.

3.

Do not force the module into its backplane connector. Apply firm, even pressure on the module to seat it properly.

4.

Snap the chassis latch over the top of the module to secure its position.

5.

Connect the wiring arm to the module.

6.

Make wiring connections to the field wiring arm as indicated in Figures 1 and 2.

Connecting Wiring to the Input Module Connections to the input module are made to the 10 terminal field wiring arm (cat. no. 1771–WA) shipped with the module. Attach the wiring arm to the pivot bar on the bottom of the I/O chassis. The wiring arm pivots upward and connects with the module so you can install or remove the module without disconnecting the wires. ATTENTION: Observe proper polarity with dc power connections. Reverse polarity, or application of ac voltage could damage the module.

3

Page 4

Installation Data DC (12-24V) Input Module Cat. No. 1771-IB

Figure 1 Connection Diagram (2-Wire Devices) (See Applicable Codes and Laws) Not used

A

Input 0

0

Input 1

1

Input 2

2

Input 3

3

Input 4

4

Input 5

5

Input 6

6

Input 7

7

DC Common

B

+ DC Power Supply -

(Actual wiring runs in this direction.) 11833-I

Connect one terminal of your 2 or 3–wire input device to terminals 0 through 7 (Figure 1). Connect 3–wire input devices, such as Allen–Bradley proximity switches (Bulletin 871) to operate in a current source mode (Figure 2). Connect terminal B to the dc common. Terminal A is not used. Connect the +dc line to the other terminal of your input devices. Use stranded 14 or 16 gauge wire to minimize the voltage drop over long cable distances. Important: You can directly drive terminals on an DC (12–24V) Input Module (cat. no. 1771–IB) from terminals on the following modules: DC (10–60V) Output module (cat. no. 1771–OBD) DC (12–24V) Output module (cat. no. 1771–OB) Important: Use the same dc power source to power both modules to ensure that ground is at the same potential.

4

Page 5

Installation Data DC (12-24V) Input Module Cat. No. 1771-IB

Figure 2 Connection Diagram (3-Wire Devices) See Applicable Codes and Laws Not used

A

Input 0

0

Input 1

1

Input 2

2

Input 3

3

Input 4

4

Input 5

5

Input 6

6

Input 7

7

DC Common

B

+

+ + DC Power Supply -

(Actual wiring runs in this direction.)

Interpreting the Status Indicators

11834-I

The front panel of your module contains 8 red status LED indicators (figure 3). The red status indicators are provided for system logic side indication of individual inputs. When a red LED lights, voltage is present on the terminal. The module transfers this information to the backplane for the processor to read. Figure 3 Status Indicators

Not used Input 0 Input 1 Input 2 Input 3 Input 4 Input 5 Input 6 Input 7

Status Indicators

11835-I

5

Page 6

Installation Data DC (12-24V) Input Module Cat. No. 1771-IB

Specifications

Inputs per Module

8

Module Location

1771 I/O chassis

Input Voltage Range

10 to 27V dc

Nominal Input Current

8mA at 12V dc 24mA at 24V dc

Maximum Off-state Current

3.0mA

Maximum Off-state Voltage

7.0V dc

Minimum On-state Voltage

10V dc

Input Impedance

1 to 2K ohms maximum (on-state) 2 to 3K ohms maximum (off-state)

Input Signal Delay

Low to high propagation delay 12ms +7ms High to low propagation delay 20ms +7ms

Power Dissipation

5.7 Watts (max.), 0.4 Watts (min.)

Thermal Dissipation

19.3 BTU/hr (max.), 1.4 BTU/hr (min.)

Backplane Current

74mA @ 5V dc +5%

Opto-electrical Isolation Environmental Conditions Operational Temperature Storage Temperature Relative Humidity Conductors

Wire Size Category

Keying

1500V ac rms 0o to 60oC (32o to 140oF) -40o to 85oC (-40o to 185oF) 5 to 95% (without condensation) 14 gage stranded maximum 3/64 inch insulation maximum 21 Between 4 and 6 Between 14 and 16

Field Wiring Arm

Catalog Number 1771-WA

1 Refer to publication 1770-4.1, Programmable Controller Wiring and Grounding Guidelines.

As a subsidiary of Rockwell International, one of the world’s largest technology companies, Allen-Bradley meets today’s challenges of industrial automation with over 85 years of practical plant-floor experience. More than 11,000 employees throughout the world design, manufacture and apply a wide range of control and automation products and supporting services to help our customers continuously improve quality, productivity and time to market. These products and services not only control individual machines but integrate the manufacturing process, while providing access to vital plant floor data that can be used to support decision-making throughout the enterprise.

With offices in major cities worldwide WORLD HEADQUARTERS Allen-Bradley 1201 South Second Street Milwaukee, WI 53204 USA Tel: (1) 414 382-2000 Telex: 43 11 016 FAX: (1) 414 382-4444

EUROPE/MIDDLE EAST/AFRICA HEADQUARTERS Allen-Bradley Europe B.V. Amsterdamseweg 15 1422 AC Uithoorn The Netherlands Tel: (31) 2975/43500 Telex: (844) 18042 FAX: (31) 2975/60222

Publication 1771–2.4 – May 1990 6

ASIA/PACIFIC HEADQUARTERS Allen-Bradley (Hong Kong) Limited Room 1006, Block B, Sea View Estate 28 Watson Road Hong Kong Tel: (852) 887-4788 Telex: (780) 64347 FAX: (852) 510-9436

Supersedes publication 1771–2.4 – January 1986 and 1771–2.4–DU1 – October 1987

CANADA HEADQUARTERS Allen-Bradley Canada Limited 135 Dundas Street Cambridge, Ontario N1R 5X1 Canada Tel: (1) 519 623-1810 FAX: (1) 519 623-8930

LATIN AMERICA HEADQUARTERS Allen-Bradley 1201 South Second Street Milwaukee, WI 53204 USA Tel: (1) 414 382-2000 Telex: 43 11 016 FAX: (1) 414 382-2400

PN 955107–15 Copyright 1991 Allen-Bradley Company, Inc. Printed in USA