Page 1 of 1771 Digital I/O AC Input and Output Modules Product Data

Manual · Allen-Bradley

1771 Digital I/O AC Input and Output Modules Product Data

Manual61 pagesPDF 1.1 MB

Product data for the Allen-Bradley 1771 digital AC input and output modules, including the 1771-IA and 1771-OD16.

Download the PDF1.1 MB

Names · 2 models

The models it names

Filed with · 2 models

Also filed with these models on the old site

Summary

What is in it

Allen-Bradley product data for the 1771 Universal I/O family of digital AC input and output modules. An overview covers status indicators, keying, power, module placement, addressing modes, fault mode jumpers, input filtering, surge suppression, fuses and fuse kits, and EU and agency compliance. One specification sheet per module follows, with schematic, connection diagram and application notes for input modules such as the 1771-IA, -IA2, -IAD, -ID and -IM and output modules such as the 1771-OA, -OD, -OD16, -OM and -OR.

Its parts

  1. Overview
  2. AC/DC Input Module (Cat. No. 1771-IA Series C, and 1771-IA2)
  3. AC/DC Input Module (Cat. No. 1771-IAD Series D)
  4. AC Input Module (Cat. No. 1771-IAN)
  5. Isolated AC/DC Input Module (Cat. No. 1771-ID)
  6. Isolated AC/DC Input Module (Cat. No. 1771-ID01)
  7. Isolated AC/DC Input Module (Cat. No. 1771-ID16)
  8. AC/DC Input Module (Cat. No. 1771-IM)
  9. AC/DC Input Module (Cat. No. 1771-IMD Series B)
  10. AC Input Module (Cat. No. 1771-IN)
  11. AC/DC Input Module (Cat. No. 1771-IND Series B)
  12. AC Output Module (Cat. No. 1771-OA Series B)
  13. AC Output Module (Cat. No. 1771-OAD Series C)
  14. AC Output Module (Cat. No. 1771-OAN)
  15. Isolated AC Output Module (Cat. No. 1771-OD Series C)

From the manual

Key facts from this manual

Each line names its page in the PDF.

Product data sheet (publication 1771-2.182, July 1996) for the whole family of 1771 digital ac input and output modules: 1771-IA series C, -IA2, -IAD, -IAN, -ID, -ID01, -ID16, -IM, -IMD, -IN, -IND, -OA, -OAD, -OAN, -OD, -OD16, -ODD, -ODZ, -OM, -OMD, -ON, -OND, -OP and -OR. It gives a wiring diagram and a specification table for each module, plus general guidance on keying, fault modes, surge suppression and fuses.

Read for this summary: pages 1 to 13 and 40 to 41 of 61.

Device
Digital ac I/O module for the 1771 Universal I/O chassis p. 1
Module power
From the 1771 I/O chassis backplane power supply p. 3
Status indicators
One per input or output on the front panel p. 3
Operating temperature
0 to 60 C (32 to 140 F) p. 13, 41
Wire size
14 gauge (2 mm2) stranded maximum p. 13, 41
Wiring arm torque
7-9 inch-pounds p. 13
1771-IA inputs
8 inputs, 120V ac at 47-63Hz or 125V dc p. 13
1771-IA on-state range
87 to 138V ac or 97 to 138V dc; 5.2mA minimum p. 13
1771-IA backplane current
75mA p. 13
1771-IA wiring arm
1771-WA p. 13
1771-OD16 outputs
16 isolated outputs, 74 to 138V ac, 47-63Hz p. 41
1771-OD16 current
2A per output continuous, 8A per module; 20A surge for 100ms p. 41
1771-OD16 fuses
3A 2AG slow-blow, one per output (Littelfuse 229003); kit 1771-FE p. 41
1771-OD16 chassis and arm
1771-A1B thru -A4B or later chassis; 1771-WN wiring arm; 200mA backplane current p. 41

What this manual walks you through

  • Choosing last-state or reset fault mode with a jumper p. 4
  • Keying I/O slots for one module type p. 3
  • Checking addressing modes and chassis compatibility for each module p. 5, 6
  • Placing modules to limit noise and heat p. 3
  • Adding surge suppression across inductive loads p. 7
  • Choosing fused wiring arms and replacement fuse kits p. 8
  • Driving a 1771-IA input from a 1771-OA output p. 12, 13
  • Wiring a 1771-OD16 output to a 1771-ID16 input p. 41

Good to know

  • The 1771-IA is meant for input devices with off-state leakage below 2.8mA. p. 12
  • The leftmost chassis slot is reserved for an adapter or processor, not an I/O module. p. 3
  • Module current draws should be totaled so the chassis supply and backplane are not overloaded. p. 3
  • On the 1771-OD16 the fuse-blown indicator may not work when the load current is 5mA or less. p. 40
  • 14 gauge wire on every 1771-OD16 terminal may keep the wiring arm cover from closing. p. 41

Questions this manual answers

How many inputs does a 1771-IA module have?

Eight inputs, rated 120V ac at 47-63Hz or 125V dc. p. 13

What fuse does the 1771-OD16 use?

One 3A 2AG slow-blow fuse per output, Littelfuse 229003; a five-fuse kit is cat. no. 1771-FE. p. 41

Which wiring arm fits the 1771-IA?

The 1771-WA field wiring arm. p. 13

How much current can a 1771-OD16 output carry?

Up to 2A continuous per output and 8A per module, with a 20A surge for 100ms. p. 41

Can a 1771-OA output drive a 1771-IA input?

Yes, with a 2.5K ohm 10W resistor or an RG-1676-1 snubber between the output terminal and L2, both modules on the same supply. p. 12

Contents

Chapters and sections

Each line opens the PDF at its page.

  1. 1771-2.182, 1771 Digital I/O AC Input and Output Modules Product Data1
  2. 1771-IA Series C, and 1771-IA2)12
  3. AC/DC Input Module (Cat. No. 1771-IAD Series D)14
  4. Isolated AC/DC Input Module (Cat. No. 1771-ID)16
  5. Isolated AC/DC Input Module (Cat. No. 1771-ID)18
  6. Isolated AC/DC Input Module (Cat. No. 1771-ID01)20
  7. Isolated AC/DC Input Module (Cat. No. 1771-ID16)22
  8. AC/DC Input Module (Cat. No. 1771-IM)24
  9. AC/DC Input Module (Cat. No. 1771-IMD Series B)26
  10. AC Input Module (Cat. No. 1771-IN)28
  11. AC/DC Input Module (Cat. No. 1771-IND Series B)30
  12. AC Output Module (Cat. No. 1771-OA Series B)32
  13. AC Output Module (Cat. No. 1771-OAD Series C)34
  14. AC Output Module (Cat. No. 1771-OAN)36
  15. Isolated AC Output Module (Cat. No. 1771-OD Series C)38
  16. Isolated AC Output Module (Cat. No. 1771-OD16)40
  17. Isolated AC Output Module (Cat. No. 1771-ODD)42
  18. Isolated AC Output Module (Cat. No. 1771-ODZ)44
  19. AC Output Module (Cat. No. 1771-OM)46
  20. AC Output Module (Cat. No. 1771-OMD Series B)48
  21. AC Output Module (Cat. No. 1771-ON)50
  22. AC Output Module (Cat. No. 1771-OND Series B)52
  23. Protected AC Output Module (Cat. No. 1771-OP)54
  24. Isolated AC Output Module (Cat. No. 1771-OR Series B)56
  25. Notes58
  26. Support Services60
  27. 1771-2.182, Back Cover61
    1. 1771-2.182, 1771 Digital I/O AC Input and Output Modules Product Data1

From the PDF’s own bookmarks.

The whole text · 7 parts

Read the manual here as text

Its text as extracted from the PDF, unedited, in parts; each page opens the PDF at that page.

  1. Pages 1 to 91-9
  2. Pages 10 to 1810-18
  3. Pages 19 to 2719-27
  4. Pages 28 to 3628-36
  5. Pages 37 to 4537-45
  6. Pages 46 to 5446-54
  7. Pages 55 to 6155-61

The file

Revision and size

RevisionPublication 1771-2.182, July 1996
PublisherAllen-Bradley
Pages61
PDF1.1 MB
TextText from the PDF itself.

The first pages · 3 of 61

Look before you download

Each page opens the PDF at that page.

Page 1
Page 1of 61
Page 2
Page 2of 61
Page 3
Page 3of 61