1771 Digital I/O AC Input and Output Modules Product Data, pages 28 to 36

Pages 28 to 36 of 61

The original document is the PDF (1.1 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

For the Allen-Bradley 1771-IA and Allen-Bradley 1771-OD16

Page 28

1771 Digital I/O AC Input and Output Modules

27

AC Input Module (Cat. No. 1771-IN)

Simplified Schematic

1.02K 1.02K Opto Isolation

Backplane Logic Circuitry ac Input dc (pos)

Input Indication .022µF

Input Filter

1.18K 1.02K 1.02K ac l ow d c (common) 18510

Application Notes

Connection Diagram

Device Compatibility. This module is designed to operate with ac proximity switches and other input devices with an off-state leakage current less than 2.8mA peak.

Not used

A

Input 0

O

Input 1

1

Input 2

2

Input 3

3

Input 4

4

Input 5

5

Input 6

6

Input 7

7

L2

B

Connection to Output Module. You can use an ac (24V) output module (cat. no. 1771-ON) to directly drive terminals on an ac/dc (24V) input module (cat. no. 1771-IN), but you must connect a 250 ohm, 5W resistor between the output terminal and L2 (common). Use the same ac power source to power both modules to ensure proper phasing and to prevent module damage. Status Indicators. The front panel has eight red status indicators. Each status indicator is provided for field side indication of individual inputs. An indicator lights when the corresponding input circuit has ac power applied to it. Inrush Current Considerations. Due to capacitive impedance input, there is an initial current associated with the 1771-IN. The peak inrush current at turn-on can be calculated as follows: Peak Inrush Current = VPS/1.02K ohms where: VPS = customer supply peak voltage.

L1 24V ac high

L2 ac low

(Actual wiring runs in this direction.)

11902-I

Publication 1771-2.182 - July 1996

Page 29

28

1771 Digital I/O AC Input and Output Modules

AC Input Module (Cat. No. 1771-IN)

Status Indicators

Specifications (Cat. No. 1771-IN) Inputs per Module

8

Module Location

1771 I/O chassis

Nominal Input Voltage

24V ac @ 47-63Hz

Nominal Input Current

15.5mA @ 24V ac 50Hz 18.0mA @ 24V ac 60Hz

On-state Current (minimum)

7.4 mA

On-state Voltage Range

12 to 28V ac

Off-state Voltage (maximum)

10.5V ac

Off-state Current (maximum)

2.8mA ac

Input Impedance Input Signal Delay

Refer to simplified schematic Off to On On to Off

18+10ms 18+10ms

Power Dissipation

3.1 Watts (max.), 0.4 Watts (min.)

Thermal Dissipation

10.6 BTU/hr (max.), 1.4 BTU/hr (min.)

Backplane Current

80mA

Isolation Voltage

Isolation meets or exceeds UL Standard 508, and CSA Standard C22.2 No. 142.

Environmental Conditions Operational Temperature Storage Temperature Relative Humidity Conductors

Wire Size Category

Keying Field Wiring Arm Wiring Arm Screw Torque Agency Certification (when product or packaging is marked)

Installation Instructions 1

Not used Input 0 Input 1 Input 2 Input 3 Input 4 Input 5 Input 6 Input 7

11904-I

Sample Connection Diagram Driving a 1771-IN Module with a 1771-ON Module

0o to 60oC (32o to 140oF) -40o to 85oC (-40o to 185oF) 5 to 95% without condensation 14 gauge (2mm2) stranded maximum 3/64 inch (1.2mm) insulation maximum 21

L1

L1

A ac high

O

Between 4 and 6 Between 10 and 12 Catalog Number 1771-WA 7-9 inch pounds • CSA certified • CSA Class I, Division 2, Groups A, B, C, D certified • UL listed • CE marked for all applicable directives

O 1

2

2

3

3

4

4

5

5 250 ohm 5 Watt Resistor

7 L2

A

1

6

1771-2.41

You use this conductor-category information for planning conductor routing as described in the system-level installation manual.

AC (24V) Input Module (Cat. No. 1771-IN)

AC (24V) Output Module (Cat. No. 1771-ON)

6 7 8

8

L2 ac low 11903-I

Publication 1771-2.182 - July 1996

Page 30

1771 Digital I/O AC Input and Output Modules

29

AC/DC Input Module (Cat. No. 1771-IND Series B)

Simplified Schematic Backplane Logic Circuitry

Opto Isolation

4.9K

Logic Circuitry

LED

.022µF E ac Input dc (pos)

.68µF

1.18K

Input Indication

100 ac low dc (common)

.022µF

21

1

A

18499

Chassis ground

Application Notes

Connection Diagram

Product Compatibility. This module must be used with a 1771-A1B thru -A4B or later I/O chassis. Connection to Output Modules. You can use an ac (24V) output module (cat. no. 1771-OND) to directly drive terminals on an ac (24V) input module (cat. no. 1771-IND). You can also use an output module (cat. no. 1771-ON) to drive an ac input module (cat. no. 1771-IND), but you must connect a 470 ohm, 3W resistor between the output terminal and L2 (common). Use the same ac power source to power both modules to ensure proper phasing and prevent module damage. Setting the Fault Mode. Use the jumper below to set the fault mode to last state (LS) or reset position. Top edge of circuit board Fault Mode Selection Plug (shown in last state position) RESET

LS

10548-I

Status Indicators. The front panel has one green, module-active indicator, and 16 red status indicators. The 1771-IND performs diagnostics in a handshaking mode when first powered up. Upon successful completion of the diagnostics, the module-active indicator is illuminated. The status indicators are provided for system logic side indication of individual inputs. Each indicator is illuminated when its corresponding circuit has ac/dc voltage applied to it. Inrush Current Considerations. Due to capacitive impedance input, there is an initial current associated with the 1771-IND. The peak inrush current at turn-on can be calculated as follows: Peak Inrush Current = VPS/100 ohms where: VPS = customer supply peak voltage.

L1 Not used Not used Not used Input 00 Input 01 Input 02 Input 03 Input 04 Input 05 Input 06 Input 07 Input 10 Input 11 Input 12 Input 13 Input 14 Input 15 Input 16 Input 17 L2

A B C D 00 01 02 03 04 05 06 07 10 11 12 13 14 15 16 17 E

Terminal A must be connected to L1 to balance the line in an un- grounded application. L1 ac high

L2 ac low

(Actual wiring runs in this direction.)

10426-I

Publication 1771-2.182 - July 1996

Page 31

30

1771 Digital I/O AC Input and Output Modules

AC/DC Input Module (Cat. No. 1771-IND Series B) Specifications (Cat. No. 1771-IND/B) Inputs per Module

16

Module Location

1771-A1B thru -A4B or later I/O chassis -AM1, -AM2 I/O chassis

Nominal Input Voltage

24V ac @ 50/60Hz 24V dc

Nominal Input Current

6.3mA @ 24V ac 50Hz 7.2mA @ 24V ac 60Hz 3.8mA at 24V dc

On-state Voltage Range

16V to 30V ac 9V to 30V dc

On-state Current (minimum)

3.0mA at 10V ac, 60Hz 1.4mA at 9V dc

Off-state Voltage (maximum)

5V ac at 50/60Hz; 3.7V dc

Off-state Current (maximum)

1.5mA at 5V ac, 60Hz 0.6mA at 5V dc

Input Impedance

0.68µF in parallel with 6.28K (3.9K ohms at 60Hz); in series with 100 ohms

Peak Inrush Current

Vps/100 ohms, where Vps = customer supply peak voltage

Input Signal Delay

Off to On On to Off

35ms +10ms for 24V ac 10ms for 24V dc 45ms +15ms for 24V ac 50ms for 24V dc

Power Dissipation

8.3 Watts (max.), 1.3 Watts (min.)

Thermal Dissipation

28.4 BTU/hr (max.), 4.4 BTU/hr (min.)

Backplane Current

250mA @ 5V dc +5%

Isolation Voltage

Isolation meets or exceeds UL Standard 508, and CSA Standard C22.2 No. 142.

Environmental Conditions Operational Temperature Storage Temperature Relative Humidity Conductors

Wire Size Category

Keying Field Wiring Arm Wiring Arm Screw Torque Agency Certification (when product or packaging is marked)

Installation Instructions 1

Module Active Indicator (green) ACTIVE 00 10 01 11 02 12 03 13 04 14 05 15 06 16 07 17

00 to 17 Status Indicators (red)

10429-I

Sample Connection Diagram Driving a 1771-IND Module with a 1771-OND Module AC (24V) Input Module (Cat. No. 1771-IND)

AC (24V) Output Module (Cat. No. 1771-OND)

L1 24V ac high

0o to 60oC (32o to 140oF) -40o to 85oC (-40o to 185oF) 5 to 95% (without condensation) 14 gauge (2mm2) stranded maximum 3/64 inch (1.2mm) insulation maximum 11 Between 20 and 22 Between 34 and 36 Catalog Number 1771-WH 7-9 inch-pounds • CSA certified • CSA Class I, Division 2, Groups A, B, C, D certified • UL listed • CE marked for all applicable directives 1771-2.96

You use this conductor-category information for planning conductor routing as described in the system-level installation manual.

Publication 1771-2.182 - July 1996

Status Indicators

L2 ac low

10427-I

Page 32

1771 Digital I/O AC Input and Output Modules

31

AC Output Module (Cat. No. 1771-OA Series B)

Simplified Schematic

Fuse Blown Indication 100K 100

Backplane Logic Circuitry

Opto Isolation

Rect & Filter Circuit

0.047µF

MOV

22

100K

100

L1

Fuse 2A

200K

365K

MOV

7.5K

L2

Neon Output Indicator Output 18503

Application Notes Device Compatibility. An output on the 1771-OA module can drive an Allen-Bradley motor starter up to a size 4, provided its supply voltage does not drop below 92V ac.

Connection Diagram L1 L1

A

Minimum/Maximum Load Current. The module needs a minimum load current of 50mA to stay on. If your device pulls less than 50mA the triac may not operate. The maximum load current the module can deliver is 1.5A per output, not to exceed 6A total per module.

Output 0

O

Output 1

1

Output 2

2

Output 3

3

Connection to Input Modules. You can use an output of the 1771-OA module to drive an input of a 120V ac input module (1771-IA, -IA2, -ID, and -IAD). However, you must connect a 2.5K ohm, 10W resistor between the output and L2 (ac low). As an alternative you can connect an electrocube snubber (part number RG-1676-1). Use the same ac power source to power both modules to ensure proper phasing and prevent module damage.

Output 4

4

Output 5

5

Output 6

6

Output 7

7

L2

B

Status Indicators. The module has eight status indicators and a fuse-blown indicator. The status indicators show the ON/OFF condition of an individual output. When the indicator is illuminated, the corresponding output is energized. The fuse-blown indicator, normally OFF, is illuminated when you blow a fuse. The indicators are provided for field side indication of individual outputs.

(Actual wiring runs in this direction.)

120V ac high

Output Device

L2 ac low

11884-I

Publication 1771-2.182 - July 1996

Page 33

32

1771 Digital I/O AC Input and Output Modules

AC Output Module (Cat. No. 1771-OA Series B) Specifications (Cat. No. 1771-OA/B) Outputs per Module

8

Module Location

1771 I/O chassis

Output Voltage Range Output Current Rating

92 to 138V ac @ 47 - 63Hz 1.5A per output

4A per output for 8.3ms at 120V ac, repeatable every 1 second

Load Current (minimum)

50mA per output @ 120V ac, 60Hz

On-State Voltage Drop

2V at 100mA

Signal Delay

Off to On On to Off

1.0ms 8.3ms @ 60Hz 10.7 Watts, 2V (max.), 1.1 Watts (min.)

Thermal Dissipation

36.6 BTU/hr (max.), 3.4 BTU/hr (min.)

Backplane Current

210mA @ 5V dc + 5%

Isolation Voltage

Isolation meets or exceeds UL Standard 508, and CSA Standard C22.2 No. 142.

Category

11886-I

5mA per output @ 120V ac

Power Dissipation

Environmental Conditions Operational Temperature Storage Temperature Relative Humidity Conductors Wire Size

Fuse-Blown Indicator Output 0 Output 1 Output 2 Output 3 Status Indicators Output 4 Output 5 Output 6 Output 7 not to exceed 6A per module

Surge Current (maximum)

Off-State Leakage Current (max.)

Status Indicators

0o to 60oC (32o to 140oF) -40o to 85oC (-40o to 185oF) 5 to 95% (without condensation) 14 gauge (2mm2) stranded maximum 3/64 inch (1.2mm) insulation maximum 11

Sample Connection Diagram Driving a 1771-IAD Module with a 1771-OA Module

AC/DC (120V) Input Module 1771-IAD

AC (120V) Output Module 1771-OA

Keying

Between 4 and 6 Between 12 and 14

A

Fuse

2A, 250V Buss AGC-2 fuse Littlefuse Part No. 312002

1

Field Wiring Arm

Catalog Number 1771-WA

Wiring Arm Screw Torque Agency Certification (when product or packaging is marked)

Installation Instructions 1

7-9 inch pounds • CSA certified • CSA Class I, Division 2, Groups A, B, C, D certified • UL listed • CE marked for all applicable directives 1771-2.5

You use this conductor-category information for planning conductor routing as described in the system-level installation manual.

L1 ac high

0

2 3 4 5 6 7

2.5K ohm 10 Watt Resistor

B

L2 ac low

11885-I

Publication 1771-2.182 - July 1996

Page 34

1771 Digital I/O AC Input and Output Modules

33

AC Output Module (Cat. No. 1771-OAD Series C)

Simplified Schematic 1.2K Output Status Indicator Backplane Logic Circuitry

+5V

+5V

680

Fuse Blown Indicator

Opto Isolation

50

10 L1

10A Fuse

Opto Isolation

MOV

STD

Fuse Blown CSI Jumper

100

0.033µF Output 18515

Application Notes Product Compatibility. This module must be used with a 1771-A1B thru -A4B or later I/O chassis. An output from this module can drive an Allen-Bradley size 5 motor starter provided its supply voltage does not drop below 92V ac. Connection to Wiring Arm. You need four ac (L1) connections on the wiring arm to accommodate the total required surge rating on the module without overstressing any single connection on the field wiring arm. Connect all ac (L1) connections to the copper four-position jumper(part number 976328-01) . The jumper is included on the wiring arm supplied with the 1771-OAD module.

The module-active indicator must be on to properly interpret the status indicators. The status indicators provide system logic side indication of individual outputs. They indicate the state to which the triac is commanded by the processor, and are powered by circuitry within the module. The indicators turn on and off as commanded by the processor. They do not indicate the presence or absence of ac power at an output terminal.

Connection Diagram

Connection to Input Modules. This module can directly drive terminals on ac/dc input modules (cat. nos. 1771-IAD, -IND). It can also drive ac/dc input modules (cat. no. 1771-IA or -ID) but you must connect a 2500 ohm 10W resistor between the outputs and L2 (common). As an alternative you can use an electrocube snubber (part number RG-1676-1). Use the same power source to ensure proper phasing and prevent module damage. Setting the Fuse-blown Mode Jumper. Set the jumper to STD for display of a fuse-blown condition on the indicator only. Set the jumper to CSI to display a fuse-blown condition on the indicator, and to set all 16 bits in the input image table for monitoring fuse-blown status in the user program. NOTE: Do not set the jumper to CSI if using the module in a complementary mode. Top-right edge of circuit board

STD

CSI

Fuse Blown Jumper (shown in preset STD position) 12636-I

Status Indicators. The front panel has one green, module-active indicator, 16 red status indicators and one red fuse-blown indicator. In STD mode, the module-active indicator lights when the module is powered and the processor is in RUN mode. In CSI mode, the module-active indicator lights when the 5V dc backplane current has stabilized.

L1 L1 L1 L1 Output 00 Output 01 Output 02 Output 03 Output 04 Output 05 Output 06 Output 07 Output 10 Output 11 Output 12 Output 13 Output 14 Output 15 Output 16 Output 17 L2

A

L1 ac high

B C D 00 01 02 03

Output Device

04 05 06 07 10 11 12 13 14 15 16 17 E

Optional L2 ac low 12218-I

(Actual wiring runs in this direction.)

Publication 1771-2.182 - July 1996

Page 35

34

1771 Digital I/O AC Input and Output Modules

AC Output Module (Cat. No. 1771-OAD Series C) Specifications (Cat. No. 1771-OAD Series C) Outputs per Module Module Location Output Voltage Range Output Current Rating Surge Current (maximum) Load Current (minimum) On-State Voltage Drop (max.) Off-State Leakage Current (max.) Signal Delay Off to On On to Off Power Dissipation Thermal Dissipation Backplane Current Isolation Voltage Environmental Conditions Operational Temperature Storage Temperature Relative Humidity Conductors Wire Size Category Keying Fuse Field Wiring Arm Standard Optional Fused Wiring Arm Screw Torque Relay Compatibility Agency Certification (when product or packaging is marked) Installation Instructions 1

16 1771-A1B thru -A4B or later I/O chassis, 1771-AM1, -AM2 I/O chassis 10 to 138V ac @ 47 - 63Hz 2A per output - not to exceed 8A per module 25A per output for 100ms, repeatable every 1 second 25A per module for 100ms, repeatable every 1 second 5mA per output 1.5V at load current < 50mA 5.8V at load current > 50mA 3.0mA per output @ 138V ac Zero crossing: 8.3ms @ 60Hz; 10.0ms @ 50Hz Zero crossing: 8.3ms @ 60Hz; 10.0ms @ 50Hz 13.0 Watts (max.), 1.5 Watts (min.) 48.0 BTU/hr (max.), 5.13 BTU/hr (min.) 295mA Isolation meets or exceeds UL Standard 508, and CSA Standard C22.2 No. 142. 0o to 60oC (32o to 140oF) -40o to 85oC (-40o to 185oF) 5 to 95% (without condensation) 14 gauge (2mm2) stranded maximum 3/64 inch (1.2mm) insulation maximum 11 Between 10 and 12 Between 20 and 22 10A, 250V rectifier fuse (1/4 x 1-1/4 inch), Littelfuse PN 322010 Catalog Number 1771-WH Cat. No. 1771-WHF 7-9 inch pounds 700-HC14A1 700-HC14A1-4 700-HT12AA1 700-HF32A1 700-HTM12RA1 700-HP32A1-4 700-HB32A1 100-A09 100-A30 100-A18

Status Indicators

Module Active Indicator (green)

ACTIVE 00 10 01 11 02 12 03 13 04 14 05 15 06 16 07 17 FUSE

00 to 17 Status Indicators (red) Fuse Blown Indicator (red) 12220-I

Sample Connection Diagram Driving a 1771-IAD Module with a 1771-OAD Module AC/DC (120V) Input Module (Cat. No. 1771-IAD)

AC (12-120V) Output Module (Cat. No. 1771-OAD)

L1 120V ac high

• CSA certified • CSA Class I, Division 2, Groups A, B, C, D certified • UL listed • CE marked for all applicable directives 1771-5.24

You use this conductor-category information for planning conductor routing as described in the system-level installation manual.

Optional

L2 ac low 12219-I

Publication 1771-2.182 - July 1996

Page 36

1771 Digital I/O AC Input and Output Modules

35

AC Output Module (Cat. No. 1771-OAN)

Simplified Schematic LED Output Indication L1 Backplane Logic Circuitry

47 Opto Isolation

.01 µF

4A MOV Output 18600

Application Notes Product Compatibility. This module must be used with a 1771-A1B thru -A4B or later I/O chassis. An output from this module can drive an Allen-Bradley size 2 motor starter, provided its supply voltage does not drop below 120V ac. Connection to Input Modules. You can use this module to directly drive terminals on ac/dc input modules (cat. nos. 1771-IA/IA2, -IAD, or -IAN). Status Indicators. The front panel has 32 status indicators. The status indicators provide system logic side indication of individual outputs. Each indicator is lit when its corresponding output is energized

Connection Diagram

Output 00

2

Output 02 Output 04 Output 06 N.C. Output 10 Output 12 Output 14

4

Output 16 N.C. Output 00 Output 02 Output 04 Output 06 N.C. Output 10 Output 12 Output 14 Output 16 N.C.

6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40

L1 Output 1 Output 3 Output 5 Output 7 L1 Output 11 Output 13 Output 15 Output 17 L1 Output 1 Output 3 Output 5 Output 7 L1 Output 11 Output 13 Output 15 Output 17

L1 ac high ac Output Device

L2 ac low

(See applicable codes and laws.) (Actual wiring runs in this direction.) 11852-I

Publication 1771-2.182 - July 1996