Page 19

18

1771 Digital I/O AC Input and Output Modules

Isolated AC/DC Input Module (Cat. No.1771-ID)

Status Indicators

Specifications (Cat. No. 1771-ID) Inputs per Module

6

Module Location

1771 I/O chassis

On-state Voltage Range

92-138V ac/dc, 47-63Hz

Nominal Input Current

6.91mA @ 120V ac 50Hz 8.0mA @ 120V ac 60Hz 8.0mA @ 120V dc

Input Signal Delay

Off to On On to Off

On-state Current (minimum)

5.0mA 1.7mA

Off-state Voltage (maximum)

45V ac

Imput Impedance

Refer to simplified schematic

Power Dissipation

4.4 Watts (max.), 0.4 Watts (min.)

Thermal Dissipation

15.0 BTU/hr (max.), 1.3 BTU/hr (min.)

Backplane Current

74mA

Isolation Voltage

Isolation meets or exceeds UL Standard 508, and CSA Standard C22.2 No. 142.

Conductors

Wire Size Category

Keying Field Wiring Arm Wiring Arm Screw Torque Agency Certification (when product or packaging is marked)

Installation Instructions 1

Not used Input 0 Input 1 Input 2 Input 3 Input 4 Input 5 Not used Not used

24+10ms for ac 10+4ms for dc 24+10ms for ac 20+9ms for dc

Off-state Current (maximum)

Environmental Conditions Operational Temperature Storage Temperature Relative Humidity

ISOLATED AC/DC

0o to 60oC (32o to 140oF) -40o to 85oC (-40o to 185oF) 5 to 95% without condensation 14 gauge (2mm2) stranded maximum

10439-I

Sample Connection Diagram Driving a 1771-ID Module with an Output Module Input Module (Cat. No. 1771-ID)

3/64 inch (1.2mm) insulation maximum 11 Between 4 and 6 Between 28 and 30 Catalog Number 1771-WD 7-9 inch-pounds • CSA certified • CSA Class I, Division 2, Groups A, B, C, D certified • UL listed • CE marked for all applicable directives 1771-2.19

You use this conductor-category information for planning conductor routing as described in the system-level installation manual.

Status Indicators ac high L1 1

Output Modules (Cat. No. 1771-OA, OD, OP) A

2 3

O

4

1

5

2

6

3 4

7 8 9

2.5K Ohm 10W Resistor

10

5 6 7

11

B

12 L2 ac low Actual wiring runs in this direction.

10438-I

Publication 1771-2.182 - July 1996

Page 20

1771 Digital I/O AC Input and Output Modules

19

Isolated AC/DC Input Module (Cat. No. 1771-ID01)

Simplified Schematic 20K Opto Isolation Backplane Logic Circuitry

Input Filter

100V ac Input dc (pos) 750K

100K

Input Indication

1M

20K ac l ow dc (common)

18505

Application Notes Device Compatibility. This module is designed to operate with ac input devices such as limit switches, float switches, selector switches and pushbutton switches. Connection to Output Module. You can use an ac (220/240V) output module (cat. no. 1771-OM) to directly drive terminals on an ac/dc (220/240V) input module (cat. no.1771-ID01), but you must connect a 3.3K ohm 20W resistor or an electrocube snubber (part number RG-1676-32) between the output terminal and L2 (common). Use the same ac power source to power both modules to ensure proper phasing and prevent module damage. Status Indicators. The front panel has 6 orange status indicators. Each status indicator is illuminated when its corresponding circuit has ac/dc voltage applied to it. The indicators are provided for system field side indication of individual inputs. Inrush Current Considerations. The peak inrush current at turn-on can be calculated as follows: Peak inrush current = (VPS - 100)/40K ohms Where: VPS = customer supply peak voltage

Connection Diagram Input 0A

1

Input 0B

2

Input 1A

3

Input 1B

4

Input 2A

5

Input 2B

6

Input 3A

7

Input 3B

8

Input 4A

9

Input 4B

10

Input 5A

11

Input 5B

12

L1 L2

220/240V ac/dc supply

L1 L2 L1 L2 L1 L2 L1 L2 L1 L2 L1 ac high or +dc

(Actual wiring runs in this direction.)

220/240V ac/dc supply 220/240V ac/dc supply 220/240V ac/dc supply 220/240V ac/dc supply 220/240V ac/dc supply L2 ac low or dc common

(See applicable codes and laws.) 11920-I

Publication 1771-2.182 - July 1996

Page 21

20

1771 Digital I/O AC Input and Output Modules

Isolated AC/DC Input Module (Cat. No. 1771-ID01)

Status Indicators

Specifications (Cat. No. 1771-ID01) Inputs per Module

6

Module Location

1771 I/O chassis

Nominal Input Voltage

220/240V ac @ 47 - 63Hz 240V dc

Nominal Input Current

3.0mA @ 220V ac 50Hz 3.5mA @ 220V ac 60Hz 3.0mA @ 220V dc

Input Voltage Range

184V ac to 276V ac; 184V dc to 276V dc

Input Signal Delay

Off to On On to Off

20+10ms for ac 10+4ms for dc 20+10ms for ac 20+9ms for dc

On-state Current (minimum)

1.8mA

On-state Voltage (minimum)

184V ac

Off-state Current (maximum)

ac: 0.7mA; dc: 1.0mA

Off-state Voltage (maximum)

102.09V ac; 144.4V dc

Input Impedance

Refer to simplified schematic

Power Dissipation

2.4 Watts (max.), 0.4 Watts (min.)

Thermal Dissipation

8.2 BTU/hr (max.), 1.4 BTU/hr (min.)

Backplane Current

74mA

Isolation Voltage

Isolation meets or exceeds UL Standard 508, and CSA Standard C22.2 No. 142.

Environmental Conditions Operational Temperature Storage Temperature Relative Humidity Conductors

Wire Size Category

Keying

Field Wiring Arm Wiring Arm Screw Torque Agency Certification (when product or packaging is marked)

Installation Instructions 1

0o to 60oC (32o to 140oF) -40o to 85oC (-40o to 185oF) 5 to 95% without condensation 14 gauge (2mm2) stranded maximum 3/64 inch (1.2mm) insulation maximum 11 Between 4 and 6 Between 14 and 16 Between 28 and 30 Catalog Number 1771-WD 7-9 inch-pounds • CSA certified • CSA Class I, Division 2, Groups A, B, C, D certified • UL listed • CE marked for all applicable directives 1771-2.102

You use this conductor-category information for planning conductor routing as described in the system-level installation manual.

Publication 1771-2.182 - July 1996

Not used Input 0 Input 1 Input 2 Input 3 Input 4 Input 5 Not used Not used

Status Indicators

11922-I

Sample Connection Diagram Driving a 1771-IDO1 Module with a 1771-OM Module Isolated ac/dc Input Module (Cat. No. 1771-ID01)

1

220/240V ac Output Module L1 (Cat. No. 1771-OM) ac high

2 3

A

4

O

5

1

6

2

7

3

8

4

9

5

10 11

3.3K Ohm, 20W Resistor

12

6 7 B

L2 ac low

(Actual wiring runs in this direction.)

11921-I

Page 22

1771 Digital I/O AC Input and Output Modules

21

Isolated AC/DC Input Module (Cat. No 1771-ID16)

Simplified Schematic

220

+5V Opto Isolation

LED Input Indication Backplane Logic Circuitry ac Input +dc

MOV

68.1K

.33 µ F

Input Filter

178K

23.7K ac low dc common

261K

499K

18506

Application Notes

Connection Diagram

Device Compatibility. This module is designed to operate with limit switches, float switches, selector switches and pushbutton switches. Product Compatibility. This module must be used with a 1771-A1B thru -A4B or later I/O chassis. Connection to Output Modules. You can use an ac output module (Cat. No. 1771-OA, 1771-OD or 1771-OP) to directly drive terminals on an ac (120V) input module (Cat. No. 1771-ID16), but you must connect a 2.5K ohm, 10W resistor between the output terminal an L2 (common). You can use an ac (120V) output module (Cat. No. 1771-OD16 or -OAD) to drive the 1771-ID16 module without using a resistor. Setting the Filter Time Jumpers. Use the figure below to set the filter time jumpers to fast or normal. Top of Circuit board

FAST

NORM E2

FAST

NORM

CH0-7 CH10-17

E1

Filter Time Jumpers E1 = Jumper for inputs 00 through 07 E2 = Jumper for inputs 10 through 17 10557-I

Status Indicators. The front panel has one green module active indicator and 16 red status indicators. The 16 status indicators will light when the field load has been applied to the field wiring arm of the module. The active indicator will light when the module has successfully started up and initialized. Inrush Current Considerations. Due to capacitive impedance input, there is an initial current associated with the 1771-ID16. The peak inrush current at turn-on can be calculated as follows: Peak Inrush Current = (VPS)/220 ohms where: VPS = customer supply peak voltage.

L2 ac low L2 - 0 L2 - 1 L2 - 2 L2 - 3 Not Used L2 - 4 L2 - 5 L2 - 6 L2 - 7 Not used L2 - 10 L2 - 11

2 4 6 8 10 12 14 16 18 20 22 24

L2 - 12 L2 - 13 Not used L2 - 14 L2 - 15 L2 - 16

26 28

L2 - 17

38

Not used

40

30 32 34 36

Input 0 Input 1 Input 2 Input 3 Not used Input 4 Input 5 Input 6 Input 7 Not used Input 10 Input 11 Input 12 Input 13 Not used Input 14 Input 15 Input 16 Input 17 Not used

L1 ac high 120V ac Supply ac low L2

(Actual wiring runs in this direction.) 10558-I

Publication 1771-2.182 - July 1996

Page 23

22

1771 Digital I/O AC Input and Output Modules

Isolated AC/DC Input Module (Cat. No 1771-ID16)

Status Indicators

Specifications (Cat. No. 1771-ID16) Inputs per Module

16

Module Location

1771-A1B thru -A4B or later I/O chassis 1771-AM1, -AM2 Chassis

Input Voltage Range

74-138V ac, 47-63Hz; 105-138V dc

Nominal Input Voltage

120V ac/dc

Nominal Input Current

120V ac: 12.4mA @ 50Hz; 14.9mA @ 60Hz 120V dc: 2.5mA

On-state Voltage (minimum)

74V ac; 105V dc

On-state Current (minimum)

6.0mA @ 74V ac, 47-63Hz 2.0mA @ 105V dc

Off-state Voltage (maximum)

45V ac; 66V dc

Off-state Current (minimum)

4mA @ 45V ac, 47-63Hz; 0.8mA @ 63V dc

Input Signal Delay

Off to On On to Off

1.0ms for ac; 1.0ms for dc Selectable: 9ms or 18.0ms for ac; 9ms for dc

Input Impedance (minimum)

ac: 9.3K ohms @ 47Hz; 6.9K ohms @ 63Hz dc: 75K ohms off; 48K ohms on

Power Dissipation

7.0 Watts (max.), 0.3 Watts (min.)

Thermal Dissipation

23.8 BTU/hr (max.), 1.0 BTU/hr (min.)

Backplane Current

75mA maximum

Isolation Voltage

Isolation meets or exceeds UL Standard 508, and CSA Standard C22.2 No. 142.

Maximum Cable Length

14 gauge (2mm2) stranded maximum2 3/64 inch (1.2mm) insulation maximum 11

Keying

Catalog Number 1771-WN

Wiring Arm Screw Torque

7-9 inch-pounds • CSA certified • CSA Class I, Division 2, Groups A, B, C, D certified • UL listed • CE marked for all applicable directives

Installation Instructions 2

1771-2.189

You use this conductor-category information for planning conductor routing as described in the system-level installation manual. 14 gauge wire connected to all terminals may not allow the field wiring arm cover to close. A smaller gauge wire may be required.

L2 ac low

Publication 1771-2.182 - July 1996

AC (120V) Isolated Output Module (Cat. No. 1771-OD16)

2 4 6

2 4 6

8 10 12

8 10 12 14

14 16 18 20 22 24

Between 22 and 24 Between 26 and 28

Field Wiring Arm

1

AC/DC (120V) Isolated Input Module (Cat. No. 1771-ID16)

5 to 95% (without condensation)

Category

Agency Certification (when product or packaging is marked)

Sample Connection Diagram Driving a 1771-ID16 Module with a 1771-OD16 Module

0o to 60oC (32o to 140oF) -40o to 85oC (-40o to 185oF)

Conductors Wire Size

Input Status Indicators (red)

10560-I

1000ft (304.8m)

Environmental Conditions Operational Temperature Storage Temperature Relative Humidity

ACTIVE Indicator (green)

ACTIVE 00 10 01 11 02 12 03 13 04 14 05 15 06 16 07 17

16 18 20 22 24

26 28

26 28

30 32 34 36

30 32 34 36

38

38

40

40

120V ac Supply

L1 ac high

10559-I

Page 24

1771 Digital I/O AC Input and Output Modules

23

AC/DC Input Module (Cat. No. 1771-IM)

Simplified Schematic

20K Opto Isolation

Backplane Logic Circuitry

Input Filter

100V ac Input dc (pos) 1M

Input Indication

100K

750K

20K ac low dc (common)

18507

Application Notes Device Compatibility. This module is designed to operate with ac limit switches, selector switches, float switches and pushbutton switches. Connection to Output Module. You can use an ac (220/240V) output module (cat. no.1771-OM, -OMD, -OR) to directly drive terminals on an ac/dc (220/240V) input module (cat. no.1771-IM), but you must connect a 3.3K ohm, 20W resistor between the output terminal and L2 (common). As an alternative you can use an electrocube snubber (part number RG-1676-32). Use the same ac power source to power both modules to ensure proper phasing and to prevent module damage. Status Indicators. The front panel has 8 status indicators. Each indicator is illuminated when its corresponding input circuit has ac/dc voltage applied. The indicators are provided for field side indication of individual inputs. Inrush Current Considerations. The peak inrush current at turn-on can be calculated as follows: Peak inrush current = (VPS - 100)/40K ohms Where: VPS = customer supply peak voltage

Connection Diagram Not used

A

Input 0

O

Input 1

1

Input 2

2

Input 3

3

Input 4

4

Input 5

5

Input 6

6

Input 7

7

L2

B

(Actual wiring runs in this direction.)

L1 220/240V ac high or +dc

L2 ac low or dc common

11836-I

Publication 1771-2.182 - July 1996

Page 25

24

1771 Digital I/O AC Input and Output Modules

AC/DC Input Module (Cat. No. 1771-IM)

Status Indicators

Specifications (Cat. No. 1771-IM) Inputs per Module

8

Module Location

1771 I/O chassis

Nominal Input Voltage

220/240V ac @ 47 - 63Hz 240V dc

Nominal Input Current

3.0mA @ 220V ac 50Hz 3.5mA @ 220V ac 60Hz 2.6mA @ 240V dc

On-state Current (minimum)

2.9mA

Off-state Current (maximum)

1.0mA

Off-state Voltage (maximum)

92V ac/114V ac

Input Voltage Range

184V ac to 276V ac on-state 184V dc to 276V dc on-state

Input Impedance

Refer to simplified schematic

Input Signal Delay

Off to On

20+6ms for ac 10+4ms for dc 20+6ms for ac 20+9ms for dc

On to Off Power Dissipation

2.4 Watts (max.); 0.4 Watts (min.)

Thermal Dissipation

10.9 BTU/hr (max.); 3.2 BTU/hr (min.)

Backplane Current

75mA

Isolation Voltage

Isolation meets or exceeds UL Standard 508, and CSA Standard C22.2 No. 142.

Environmental Conditions Operational Temperature Storage Temperature Relative Humidity Conductors

Category Keying Field Wiring Arm

Agency Certification (when product or packaging is marked)

1

Sample Connection Diagram Driving a 1771-IM Module with a 1771-OM Module AC (220/240V) Output Module (Cat. No. 1771-OM)

AC/DC (220/240V) Input Module (Cat. No. 1771-IM)

L1 ac high

O

O

14 gauge (2mm2) stranded maximum 3/64 inch (1.2mm) insulation maximum 11

1

1

2

2

Between 6 and 8 Between 30 and 32

3

3

4

4

5

5

7-9 inch-pounds • CSA certified • CSA Class I, Division 2, Groups A, B, C, D certified • UL listed • CE marked for all applicable directives

Installation Instructions

11838-I

A

Catalog Number 1771-WA

Wiring Arm Screw Torque

Not used Input 0 Input 1 Input 2 Input 3 Input 4 Input 5 Input 6 Input 7

A

0o to 60oC (32o to 140oF) -40o to 85oC (-40o to 185oF) 5 to 95% without condensation

Wire Size

AC INPUT 220V

1771-2.20

You use this conductor-category information for planning conductor routing as described in the system-level installation manual.

6

3.3K Ohms 20W resistor

7 B

7 B

L2 ac low

11837-I

Publication 1771-2.182 - July 1996

6

Page 26

1771 Digital I/O AC Input and Output Modules

25

AC/DC Input Module (Cat. No. 1771-IMD Series B) Simplified Schematic

Backplane Log ic Circuitry

Opto Isolation

Logic Circuitry

360K

9.76K

1K ac Input dc (pos)

0.15µF ac low dc (common)

Neon Input Indication

18509

Connection Diagram

Application Notes Product Compatibility. This module must be used with a 1771-A1B thru -A4B or later I/O chassis. Connection to Output Modules. You can use an ac (220V) output module (cat. no. 1771-OMD) to directly drive terminals on an ac (220V) input module (cat. no. 1771-IMD). You can also use a 1771-OM or -OR output module to drive an ac (220V) input module (cat. no. 1771-IMD) but you must connect a 10K ohm 10W resistor between the output terminal and L2 (common). Use the same ac power source to power both modules to ensure proper phasing and prevent module damage. Setting the Fault Mode. Use the jumper below to set the fault mode to last state (LS) or reset. Top edge of circuit board Fault Mode Selection Plug (shown in last state position) RESET

LS

10548-I

Status Indicators. The front panel has one green, module-active indicator, and 16 red status indicators. The 1771-IMD performs diagnostics in a handshaking mode when first powered up. Upon successful completion of the diagnostics, the green module-active indicator is illuminated. Each status indicator is provided for system logic side indication of individual inputs. When a status indicator is illuminated, voltage is present on the terminal.

L1 Not used Not used Not used Not used Input 00 Input 01 Input 02 Input 03 Input 04 Input 05 Input 06 Input 07 Input 10 Input 11 Input 12 Input 13 Input 14 Input 15 Input 16 Input 17 L2 ac high

A B C D 00 01 02 03 04 05 06 07 10 11 12 13 14 15 16 17 E

L2 ac low

(Actual wiring runs in this direction.)

10549-I

Inrush Current Considerations. Due to capacitive impedance input, there is an initial current associated with the 1771-IMD. The peak inrush current at turn-on can be calculated as follows: Peak Inrush Current = VPS/1K ohms where: VPS = customer supply peak voltage.

Publication 1771-2.182 - July 1996

Page 27

26

1771 Digital I/O AC Input and Output Modules

AC/DC Input Module (Cat. No. 1771-IMD Series B)

Status Indicators

Specifications (Cat. No. 1771-IMD/B) Inputs per Module

16

Module Location

1771-A1B thru -A4B or later I/O Chassis 1771-AM1, -AM2 I/O chassis

Nominal Input Voltage

220V ac @ 50/60Hz; 220V dc

Nominal Input Current

9.9mA @ 220V ac 50Hz 10.4mA @ 220V ac 60Hz 0.6mA @ 220V dc

On-state Voltage Range

184V to 250V ac 166V to 230V dc

On-state Current (minimum)

8.7mA at 184V ac, 50Hz 0.43mA at 166V dc

Off-state Voltage (maximum)

92V ac or dc

Off-state Current (maximum)

3mA at 92V ac 0.25mA at 92V dc 0.15µF capacitor (21.2K impedance at 50Hz) in parallel with a 370K resistor; in series with 1K ohm

Input Impedance Input Signal Delay

Off to On On to Off

15+8ms for ac and dc 172+56ms for ac and dc

Power Dissipation

5.8 Watts (max.), 1.3 Watts (min.)

Thermal Dissipation

19.8 BTU/hr (max.), 4.5 BTU/hr (min.)

Backplane Current

250mA @ 5V dc +5%

Isolation Voltage

Isolation meets or exceeds UL Standard 508, and CSA Standard C22.2 No. 142.

Environmental Conditions Operational Temperature Storage Temperature Relative Humidity Conductors

Wire Size Category

Keying Field Wiring Arm Wiring Arm Screw Torque Agency Certification (when product or packaging is marked)

Installation Instructions 1

ACTIVE 00 10 01 11 02 12 03 13 04 14 05 15 06 16 07 17

Module Active Indicator (green) 00 to 17 Status Indicators (red)

10552-I

Sample Connection Diagram Driving a 1771-IMD Module with a 1771-OMD Module AC (220V) Output Module (Cat. No. 1771-OMD)

AC (220V) Input Module (Cat. No. 1771-IMD)

0o to 60oC (32o to 140oF) -40o to 85oC (-40o to 185oF) 5 to 95% without condensation 14 gauge (2mm2) stranded maximum 3/64 inch (1.2mm) insulation maximum 11

L1 220V ac high

Between 2 and 4 Between 12 and 14 Catalog Number 1771-WH 7-9 inch-pounds • CSA certified • CSA Class I, Division 2, Groups A, B, C, D certified • UL listed • CE marked for all applicable directives 1771-5.27

You use this conductor-category information for planning conductor routing as described in the system-level installation manual.

L2 ac low 10550-I

Publication 1771-2.182 - July 1996