Page 19
18
1771 Digital I/O AC Input and Output Modules
Isolated AC/DC Input Module (Cat. No.1771-ID)
Status Indicators
Specifications (Cat. No. 1771-ID) Inputs per Module
6
Module Location
1771 I/O chassis
On-state Voltage Range
92-138V ac/dc, 47-63Hz
Nominal Input Current
6.91mA @ 120V ac 50Hz 8.0mA @ 120V ac 60Hz 8.0mA @ 120V dc
Input Signal Delay
Off to On On to Off
On-state Current (minimum)
5.0mA 1.7mA
Off-state Voltage (maximum)
45V ac
Imput Impedance
Refer to simplified schematic
Power Dissipation
4.4 Watts (max.), 0.4 Watts (min.)
Thermal Dissipation
15.0 BTU/hr (max.), 1.3 BTU/hr (min.)
Backplane Current
74mA
Isolation Voltage
Isolation meets or exceeds UL Standard 508, and CSA Standard C22.2 No. 142.
Conductors
Wire Size Category
Keying Field Wiring Arm Wiring Arm Screw Torque Agency Certification (when product or packaging is marked)
Installation Instructions 1
Not used Input 0 Input 1 Input 2 Input 3 Input 4 Input 5 Not used Not used
24+10ms for ac 10+4ms for dc 24+10ms for ac 20+9ms for dc
Off-state Current (maximum)
Environmental Conditions Operational Temperature Storage Temperature Relative Humidity
ISOLATED AC/DC
0o to 60oC (32o to 140oF) -40o to 85oC (-40o to 185oF) 5 to 95% without condensation 14 gauge (2mm2) stranded maximum
10439-I
Sample Connection Diagram Driving a 1771-ID Module with an Output Module Input Module (Cat. No. 1771-ID)
3/64 inch (1.2mm) insulation maximum 11 Between 4 and 6 Between 28 and 30 Catalog Number 1771-WD 7-9 inch-pounds • CSA certified • CSA Class I, Division 2, Groups A, B, C, D certified • UL listed • CE marked for all applicable directives 1771-2.19
You use this conductor-category information for planning conductor routing as described in the system-level installation manual.
Status Indicators ac high L1 1
Output Modules (Cat. No. 1771-OA, OD, OP) A
2 3
O
4
1
5
2
6
3 4
7 8 9
2.5K Ohm 10W Resistor
10
5 6 7
11
B
12 L2 ac low Actual wiring runs in this direction.
10438-I
Publication 1771-2.182 - July 1996
Page 20
1771 Digital I/O AC Input and Output Modules
19
Isolated AC/DC Input Module (Cat. No. 1771-ID01)
Simplified Schematic 20K Opto Isolation Backplane Logic Circuitry
Input Filter
100V ac Input dc (pos) 750K
100K
Input Indication
1M
20K ac l ow dc (common)
18505
Application Notes Device Compatibility. This module is designed to operate with ac input devices such as limit switches, float switches, selector switches and pushbutton switches. Connection to Output Module. You can use an ac (220/240V) output module (cat. no. 1771-OM) to directly drive terminals on an ac/dc (220/240V) input module (cat. no.1771-ID01), but you must connect a 3.3K ohm 20W resistor or an electrocube snubber (part number RG-1676-32) between the output terminal and L2 (common). Use the same ac power source to power both modules to ensure proper phasing and prevent module damage. Status Indicators. The front panel has 6 orange status indicators. Each status indicator is illuminated when its corresponding circuit has ac/dc voltage applied to it. The indicators are provided for system field side indication of individual inputs. Inrush Current Considerations. The peak inrush current at turn-on can be calculated as follows: Peak inrush current = (VPS - 100)/40K ohms Where: VPS = customer supply peak voltage
Connection Diagram Input 0A
1
Input 0B
2
Input 1A
3
Input 1B
4
Input 2A
5
Input 2B
6
Input 3A
7
Input 3B
8
Input 4A
9
Input 4B
10
Input 5A
11
Input 5B
12
L1 L2
220/240V ac/dc supply
L1 L2 L1 L2 L1 L2 L1 L2 L1 L2 L1 ac high or +dc
(Actual wiring runs in this direction.)
220/240V ac/dc supply 220/240V ac/dc supply 220/240V ac/dc supply 220/240V ac/dc supply 220/240V ac/dc supply L2 ac low or dc common
(See applicable codes and laws.) 11920-I
Publication 1771-2.182 - July 1996
Page 21
20
1771 Digital I/O AC Input and Output Modules
Isolated AC/DC Input Module (Cat. No. 1771-ID01)
Status Indicators
Specifications (Cat. No. 1771-ID01) Inputs per Module
6
Module Location
1771 I/O chassis
Nominal Input Voltage
220/240V ac @ 47 - 63Hz 240V dc
Nominal Input Current
3.0mA @ 220V ac 50Hz 3.5mA @ 220V ac 60Hz 3.0mA @ 220V dc
Input Voltage Range
184V ac to 276V ac; 184V dc to 276V dc
Input Signal Delay
Off to On On to Off
20+10ms for ac 10+4ms for dc 20+10ms for ac 20+9ms for dc
On-state Current (minimum)
1.8mA
On-state Voltage (minimum)
184V ac
Off-state Current (maximum)
ac: 0.7mA; dc: 1.0mA
Off-state Voltage (maximum)
102.09V ac; 144.4V dc
Input Impedance
Refer to simplified schematic
Power Dissipation
2.4 Watts (max.), 0.4 Watts (min.)
Thermal Dissipation
8.2 BTU/hr (max.), 1.4 BTU/hr (min.)
Backplane Current
74mA
Isolation Voltage
Isolation meets or exceeds UL Standard 508, and CSA Standard C22.2 No. 142.
Environmental Conditions Operational Temperature Storage Temperature Relative Humidity Conductors
Wire Size Category
Keying
Field Wiring Arm Wiring Arm Screw Torque Agency Certification (when product or packaging is marked)
Installation Instructions 1
0o to 60oC (32o to 140oF) -40o to 85oC (-40o to 185oF) 5 to 95% without condensation 14 gauge (2mm2) stranded maximum 3/64 inch (1.2mm) insulation maximum 11 Between 4 and 6 Between 14 and 16 Between 28 and 30 Catalog Number 1771-WD 7-9 inch-pounds • CSA certified • CSA Class I, Division 2, Groups A, B, C, D certified • UL listed • CE marked for all applicable directives 1771-2.102
You use this conductor-category information for planning conductor routing as described in the system-level installation manual.
Publication 1771-2.182 - July 1996
Not used Input 0 Input 1 Input 2 Input 3 Input 4 Input 5 Not used Not used
Status Indicators
11922-I
Sample Connection Diagram Driving a 1771-IDO1 Module with a 1771-OM Module Isolated ac/dc Input Module (Cat. No. 1771-ID01)
1
220/240V ac Output Module L1 (Cat. No. 1771-OM) ac high
2 3
A
4
O
5
1
6
2
7
3
8
4
9
5
10 11
3.3K Ohm, 20W Resistor
12
6 7 B
L2 ac low
(Actual wiring runs in this direction.)
11921-I
Page 22
1771 Digital I/O AC Input and Output Modules
21
Isolated AC/DC Input Module (Cat. No 1771-ID16)
Simplified Schematic
220
+5V Opto Isolation
LED Input Indication Backplane Logic Circuitry ac Input +dc
MOV
68.1K
.33 µ F
Input Filter
178K
23.7K ac low dc common
261K
499K
18506
Application Notes
Connection Diagram
Device Compatibility. This module is designed to operate with limit switches, float switches, selector switches and pushbutton switches. Product Compatibility. This module must be used with a 1771-A1B thru -A4B or later I/O chassis. Connection to Output Modules. You can use an ac output module (Cat. No. 1771-OA, 1771-OD or 1771-OP) to directly drive terminals on an ac (120V) input module (Cat. No. 1771-ID16), but you must connect a 2.5K ohm, 10W resistor between the output terminal an L2 (common). You can use an ac (120V) output module (Cat. No. 1771-OD16 or -OAD) to drive the 1771-ID16 module without using a resistor. Setting the Filter Time Jumpers. Use the figure below to set the filter time jumpers to fast or normal. Top of Circuit board
FAST
NORM E2
FAST
NORM
CH0-7 CH10-17
E1
Filter Time Jumpers E1 = Jumper for inputs 00 through 07 E2 = Jumper for inputs 10 through 17 10557-I
Status Indicators. The front panel has one green module active indicator and 16 red status indicators. The 16 status indicators will light when the field load has been applied to the field wiring arm of the module. The active indicator will light when the module has successfully started up and initialized. Inrush Current Considerations. Due to capacitive impedance input, there is an initial current associated with the 1771-ID16. The peak inrush current at turn-on can be calculated as follows: Peak Inrush Current = (VPS)/220 ohms where: VPS = customer supply peak voltage.
L2 ac low L2 - 0 L2 - 1 L2 - 2 L2 - 3 Not Used L2 - 4 L2 - 5 L2 - 6 L2 - 7 Not used L2 - 10 L2 - 11
2 4 6 8 10 12 14 16 18 20 22 24
L2 - 12 L2 - 13 Not used L2 - 14 L2 - 15 L2 - 16
26 28
L2 - 17
38
Not used
40
30 32 34 36
Input 0 Input 1 Input 2 Input 3 Not used Input 4 Input 5 Input 6 Input 7 Not used Input 10 Input 11 Input 12 Input 13 Not used Input 14 Input 15 Input 16 Input 17 Not used
L1 ac high 120V ac Supply ac low L2
(Actual wiring runs in this direction.) 10558-I
Publication 1771-2.182 - July 1996
Page 23
22
1771 Digital I/O AC Input and Output Modules
Isolated AC/DC Input Module (Cat. No 1771-ID16)
Status Indicators
Specifications (Cat. No. 1771-ID16) Inputs per Module
16
Module Location
1771-A1B thru -A4B or later I/O chassis 1771-AM1, -AM2 Chassis
Input Voltage Range
74-138V ac, 47-63Hz; 105-138V dc
Nominal Input Voltage
120V ac/dc
Nominal Input Current
120V ac: 12.4mA @ 50Hz; 14.9mA @ 60Hz 120V dc: 2.5mA
On-state Voltage (minimum)
74V ac; 105V dc
On-state Current (minimum)
6.0mA @ 74V ac, 47-63Hz 2.0mA @ 105V dc
Off-state Voltage (maximum)
45V ac; 66V dc
Off-state Current (minimum)
4mA @ 45V ac, 47-63Hz; 0.8mA @ 63V dc
Input Signal Delay
Off to On On to Off
1.0ms for ac; 1.0ms for dc Selectable: 9ms or 18.0ms for ac; 9ms for dc
Input Impedance (minimum)
ac: 9.3K ohms @ 47Hz; 6.9K ohms @ 63Hz dc: 75K ohms off; 48K ohms on
Power Dissipation
7.0 Watts (max.), 0.3 Watts (min.)
Thermal Dissipation
23.8 BTU/hr (max.), 1.0 BTU/hr (min.)
Backplane Current
75mA maximum
Isolation Voltage
Isolation meets or exceeds UL Standard 508, and CSA Standard C22.2 No. 142.
Maximum Cable Length
14 gauge (2mm2) stranded maximum2 3/64 inch (1.2mm) insulation maximum 11
Keying
Catalog Number 1771-WN
Wiring Arm Screw Torque
7-9 inch-pounds • CSA certified • CSA Class I, Division 2, Groups A, B, C, D certified • UL listed • CE marked for all applicable directives
Installation Instructions 2
1771-2.189
You use this conductor-category information for planning conductor routing as described in the system-level installation manual. 14 gauge wire connected to all terminals may not allow the field wiring arm cover to close. A smaller gauge wire may be required.
L2 ac low
Publication 1771-2.182 - July 1996
AC (120V) Isolated Output Module (Cat. No. 1771-OD16)
2 4 6
2 4 6
8 10 12
8 10 12 14
14 16 18 20 22 24
Between 22 and 24 Between 26 and 28
Field Wiring Arm
1
AC/DC (120V) Isolated Input Module (Cat. No. 1771-ID16)
5 to 95% (without condensation)
Category
Agency Certification (when product or packaging is marked)
Sample Connection Diagram Driving a 1771-ID16 Module with a 1771-OD16 Module
0o to 60oC (32o to 140oF) -40o to 85oC (-40o to 185oF)
Conductors Wire Size
Input Status Indicators (red)
10560-I
1000ft (304.8m)
Environmental Conditions Operational Temperature Storage Temperature Relative Humidity
ACTIVE Indicator (green)
ACTIVE 00 10 01 11 02 12 03 13 04 14 05 15 06 16 07 17
16 18 20 22 24
26 28
26 28
30 32 34 36
30 32 34 36
38
38
40
40
120V ac Supply
L1 ac high
10559-I
Page 24
1771 Digital I/O AC Input and Output Modules
23
AC/DC Input Module (Cat. No. 1771-IM)
Simplified Schematic
20K Opto Isolation
Backplane Logic Circuitry
Input Filter
100V ac Input dc (pos) 1M
Input Indication
100K
750K
20K ac low dc (common)
18507
Application Notes Device Compatibility. This module is designed to operate with ac limit switches, selector switches, float switches and pushbutton switches. Connection to Output Module. You can use an ac (220/240V) output module (cat. no.1771-OM, -OMD, -OR) to directly drive terminals on an ac/dc (220/240V) input module (cat. no.1771-IM), but you must connect a 3.3K ohm, 20W resistor between the output terminal and L2 (common). As an alternative you can use an electrocube snubber (part number RG-1676-32). Use the same ac power source to power both modules to ensure proper phasing and to prevent module damage. Status Indicators. The front panel has 8 status indicators. Each indicator is illuminated when its corresponding input circuit has ac/dc voltage applied. The indicators are provided for field side indication of individual inputs. Inrush Current Considerations. The peak inrush current at turn-on can be calculated as follows: Peak inrush current = (VPS - 100)/40K ohms Where: VPS = customer supply peak voltage
Connection Diagram Not used
A
Input 0
O
Input 1
1
Input 2
2
Input 3
3
Input 4
4
Input 5
5
Input 6
6
Input 7
7
L2
B
(Actual wiring runs in this direction.)
L1 220/240V ac high or +dc
L2 ac low or dc common
11836-I
Publication 1771-2.182 - July 1996
Page 25
24
1771 Digital I/O AC Input and Output Modules
AC/DC Input Module (Cat. No. 1771-IM)
Status Indicators
Specifications (Cat. No. 1771-IM) Inputs per Module
8
Module Location
1771 I/O chassis
Nominal Input Voltage
220/240V ac @ 47 - 63Hz 240V dc
Nominal Input Current
3.0mA @ 220V ac 50Hz 3.5mA @ 220V ac 60Hz 2.6mA @ 240V dc
On-state Current (minimum)
2.9mA
Off-state Current (maximum)
1.0mA
Off-state Voltage (maximum)
92V ac/114V ac
Input Voltage Range
184V ac to 276V ac on-state 184V dc to 276V dc on-state
Input Impedance
Refer to simplified schematic
Input Signal Delay
Off to On
20+6ms for ac 10+4ms for dc 20+6ms for ac 20+9ms for dc
On to Off Power Dissipation
2.4 Watts (max.); 0.4 Watts (min.)
Thermal Dissipation
10.9 BTU/hr (max.); 3.2 BTU/hr (min.)
Backplane Current
75mA
Isolation Voltage
Isolation meets or exceeds UL Standard 508, and CSA Standard C22.2 No. 142.
Environmental Conditions Operational Temperature Storage Temperature Relative Humidity Conductors
Category Keying Field Wiring Arm
Agency Certification (when product or packaging is marked)
1
Sample Connection Diagram Driving a 1771-IM Module with a 1771-OM Module AC (220/240V) Output Module (Cat. No. 1771-OM)
AC/DC (220/240V) Input Module (Cat. No. 1771-IM)
L1 ac high
O
O
14 gauge (2mm2) stranded maximum 3/64 inch (1.2mm) insulation maximum 11
1
1
2
2
Between 6 and 8 Between 30 and 32
3
3
4
4
5
5
7-9 inch-pounds • CSA certified • CSA Class I, Division 2, Groups A, B, C, D certified • UL listed • CE marked for all applicable directives
Installation Instructions
11838-I
A
Catalog Number 1771-WA
Wiring Arm Screw Torque
Not used Input 0 Input 1 Input 2 Input 3 Input 4 Input 5 Input 6 Input 7
A
0o to 60oC (32o to 140oF) -40o to 85oC (-40o to 185oF) 5 to 95% without condensation
Wire Size
AC INPUT 220V
1771-2.20
You use this conductor-category information for planning conductor routing as described in the system-level installation manual.
6
3.3K Ohms 20W resistor
7 B
7 B
L2 ac low
11837-I
Publication 1771-2.182 - July 1996
6
Page 26
1771 Digital I/O AC Input and Output Modules
25
AC/DC Input Module (Cat. No. 1771-IMD Series B) Simplified Schematic
Backplane Log ic Circuitry
Opto Isolation
Logic Circuitry
360K
9.76K
1K ac Input dc (pos)
0.15µF ac low dc (common)
Neon Input Indication
18509
Connection Diagram
Application Notes Product Compatibility. This module must be used with a 1771-A1B thru -A4B or later I/O chassis. Connection to Output Modules. You can use an ac (220V) output module (cat. no. 1771-OMD) to directly drive terminals on an ac (220V) input module (cat. no. 1771-IMD). You can also use a 1771-OM or -OR output module to drive an ac (220V) input module (cat. no. 1771-IMD) but you must connect a 10K ohm 10W resistor between the output terminal and L2 (common). Use the same ac power source to power both modules to ensure proper phasing and prevent module damage. Setting the Fault Mode. Use the jumper below to set the fault mode to last state (LS) or reset. Top edge of circuit board Fault Mode Selection Plug (shown in last state position) RESET
LS
10548-I
Status Indicators. The front panel has one green, module-active indicator, and 16 red status indicators. The 1771-IMD performs diagnostics in a handshaking mode when first powered up. Upon successful completion of the diagnostics, the green module-active indicator is illuminated. Each status indicator is provided for system logic side indication of individual inputs. When a status indicator is illuminated, voltage is present on the terminal.
L1 Not used Not used Not used Not used Input 00 Input 01 Input 02 Input 03 Input 04 Input 05 Input 06 Input 07 Input 10 Input 11 Input 12 Input 13 Input 14 Input 15 Input 16 Input 17 L2 ac high
A B C D 00 01 02 03 04 05 06 07 10 11 12 13 14 15 16 17 E
L2 ac low
(Actual wiring runs in this direction.)
10549-I
Inrush Current Considerations. Due to capacitive impedance input, there is an initial current associated with the 1771-IMD. The peak inrush current at turn-on can be calculated as follows: Peak Inrush Current = VPS/1K ohms where: VPS = customer supply peak voltage.
Publication 1771-2.182 - July 1996
Page 27
26
1771 Digital I/O AC Input and Output Modules
AC/DC Input Module (Cat. No. 1771-IMD Series B)
Status Indicators
Specifications (Cat. No. 1771-IMD/B) Inputs per Module
16
Module Location
1771-A1B thru -A4B or later I/O Chassis 1771-AM1, -AM2 I/O chassis
Nominal Input Voltage
220V ac @ 50/60Hz; 220V dc
Nominal Input Current
9.9mA @ 220V ac 50Hz 10.4mA @ 220V ac 60Hz 0.6mA @ 220V dc
On-state Voltage Range
184V to 250V ac 166V to 230V dc
On-state Current (minimum)
8.7mA at 184V ac, 50Hz 0.43mA at 166V dc
Off-state Voltage (maximum)
92V ac or dc
Off-state Current (maximum)
3mA at 92V ac 0.25mA at 92V dc 0.15µF capacitor (21.2K impedance at 50Hz) in parallel with a 370K resistor; in series with 1K ohm
Input Impedance Input Signal Delay
Off to On On to Off
15+8ms for ac and dc 172+56ms for ac and dc
Power Dissipation
5.8 Watts (max.), 1.3 Watts (min.)
Thermal Dissipation
19.8 BTU/hr (max.), 4.5 BTU/hr (min.)
Backplane Current
250mA @ 5V dc +5%
Isolation Voltage
Isolation meets or exceeds UL Standard 508, and CSA Standard C22.2 No. 142.
Environmental Conditions Operational Temperature Storage Temperature Relative Humidity Conductors
Wire Size Category
Keying Field Wiring Arm Wiring Arm Screw Torque Agency Certification (when product or packaging is marked)
Installation Instructions 1
ACTIVE 00 10 01 11 02 12 03 13 04 14 05 15 06 16 07 17
Module Active Indicator (green) 00 to 17 Status Indicators (red)
10552-I
Sample Connection Diagram Driving a 1771-IMD Module with a 1771-OMD Module AC (220V) Output Module (Cat. No. 1771-OMD)
AC (220V) Input Module (Cat. No. 1771-IMD)
0o to 60oC (32o to 140oF) -40o to 85oC (-40o to 185oF) 5 to 95% without condensation 14 gauge (2mm2) stranded maximum 3/64 inch (1.2mm) insulation maximum 11
L1 220V ac high
Between 2 and 4 Between 12 and 14 Catalog Number 1771-WH 7-9 inch-pounds • CSA certified • CSA Class I, Division 2, Groups A, B, C, D certified • UL listed • CE marked for all applicable directives 1771-5.27
You use this conductor-category information for planning conductor routing as described in the system-level installation manual.
L2 ac low 10550-I
Publication 1771-2.182 - July 1996