For the Allen-Bradley 1771-IA and Allen-Bradley 1771-OD16
Page 46
1771 Digital I/O AC Input and Output Modules
45
AC Output Module (Cat. No. 1771-OM)
Simplified Schematic
Fuse Blown Indication 200K 100
System Circuitry
Opto Isolation
Rect & Filter Circuit
0.047µF
L1
Fuse 2A
820K
MOV
30K
22 100
200K
L2
430K
Output Indicator
Output 18516
Application Notes
Connection Diagram
Device Compatibility. You can drive an Allen-Bradley motor starter size 4 , provided its supply voltage does not drop below 184 V. Minimum/Maximum Load Current. The module needs a minimum load current of 60mA to stay on. If your device pulls less than 60mA the triac will not operate. The maximum load current the module can deliver is 2A per output, not to exceed 6A total per module. Connection to Input Modules. You can use an ac (220/240V) output module (cat. no. 1771-OM) to drive terminals on an ac (220/240V) input module (cat. no. 1771-IM), but you must connect a 3.3K ohm, 20 Watt resistor between the output terminal and L2 (common). You can also use an ac (220/240V) output module (cat. no.1771-OM) to drive terminals on an ac (220V) input module (cat. no. 1771-IMD), but you must connect a 10K ohm, 10 Watt resistor or an electrocube snubber (part number RG-1676-32) between the output terminal and L2 (common). Use the same power source to power both modules to ensure proper phasing, and to prevent module damage. Status Indicators. The front panel has eight orange status indicators and one orange fuse-blown indicator. The status indicators light when the corresponding output is energized. The fuse-blown indicator lights when any of the 8 fuses in the module are blown. The indicators are provided for field side indication of individual outputs.
L1
A
Output 0
O
Output 1
1
Output 2
2
Output 3
3
Output 4
4
Output 5
5
Output 6
6
Output 7
7
L2
B
L1 220/240V ac High
Load
Suppression
Relay Contact
MS
L2 ac Low
Actual wiring runs in this direction. 11896-I
Publication 1771-2.182 - July 1996
Page 47
46
1771 Digital I/O AC Input and Output Modules
AC Output Module (Cat. No. 1771-OM) Specifications (Cat. No. 1771-OM) Outputs per Module
8
Module Location
1771 I/O chassis
Output Voltage Range
184 to 250V ac @ 47 - 63Hz
Output Current Rating
2A per output
Surge Current (maximum) per Output and Module
20A for 100ms, repeatable every 10 seconds
Load Current (minimum)
60mA per output @ 220V ac, 60Hz not to exceed 6A per module
On-State Voltage Drop (max.)
1.6V at 2A
Off-State Leakage Current (max.)
2mA per output @ 220V ac
Signal Delay
Off to On On to Off
13.2 Watts (max.), 1.2 Watts (min.)
Thermal Dissipation
45.1 BTU/hr (max.), 4.1 BTU/hr (min.)
Backplane Current
225mA @ 5V dc +5%
Isolation Voltage
Isolation meets or exceeds UL Standard 508, and CSA Standard C22.2 No. 142.
Conductors
Wire Size Category
0o to 60oC (32o to 140oF) -40o to 85oC (-40o to 185oF) 5 to 95% (without condensation)
Between 6 and 8 Between 28 and 30
Fuse
2A, 250V 3AG Normal Blow (1 per output) Buss Fuse AGC-2, Littelfuse 312002
Wiring Arm Screw Torque Agency Certification (when product or packaging is marked)
Installation Instructions 1
Status Indicators
Note: An output terminal need not be connected to a load in order for its status indicator to light. 11898-I
Sample Connection Diagram Driving a 1771-IMD Module with a 1771-OM Module
AC (220V) Input Module (Cat. No. 1771-IMD)
14 gauge (2mm2) stranded maximum 3/64 inch (1.2mm) insulation maximum 21
Keying
Field Wiring Arm
Fuse Blown Output 0 Output 1 Output 2 Output 3 Output 4 Output 5 Output 6 Output 7
1.0ms 8.3ms @ 60Hz
Power Dissipation
Environmental Conditions Operational Temperature Storage Temperature Relative Humidity
Status Indicators
Catalog Number 1771-WA 7-9 inch pounds
AC (220/240V) Output Module (Cat. No. 1771-OM)
A
• CSA certified • CSA Class I, Division 2, Groups A, B, C, D certified • UL listed • CE marked for all applicable directives
O
1771-2.18
4
You use this conductor-category information for planning conductor routing as described in the system-level installation manual.
A B C D 00 01 02
L1 ac high
1 2 3
10K ohm 10W resistor or electrocube snubber (part number RG-1676-32)
5 6 7 B
03 04 05 06 07 10 11 12 13 14 15 16 17 E
L2 ac low 11897-I
Publication 1771-2.182 - July 1996
Page 48
1771 Digital I/O AC Input and Output Modules
47
AC Output Module (Cat. No. 1771-OMD Series B)
Simplified Schematic LED Output Indication
L2 MOV 275V L1
Backplane Logic Circuitry
Opto Isolation
Logic Circuitry
10A
100 .022µF
MOV 275V Output 18508
Application Notes
Connection Diagram
Device Compatibility. An output from this module can drive an Allen-Bradley size 5 motor starter provided its supply voltage does not drop below 184V.
AC (220V) Output Module (Cat. No. 1771-OMD)
Product Compatibility. This module must be used with a 1771-A1B thru -A4B or later I/O chassis. Connection to Wiring Arm. You need 4 ac (L1) connections on the wiring arm to accommodate the total surge rating on the module without overstressing any single connection on the field wiring arm. Use the copper four-position jumper (part number 976328-01) that comes with the wiring arm supplied with the 1771-OMD module for distributing ac (L1) across the connections. Connection to Input Modules. This module can directly drive terminals on ac/dc input modules (cat. nos. 1771-IMD). You can also use a 1771-OMD to drive ac/dc input modules (cat. nos. 1771-IM, -ID01) but you must connect a 10K ohm 10W resistor between the outputs and L2 (common). As an alternative you can use an electrocube snubber (part number RG-1676-32). Use the same ac power source to ensure proper phasing and prevent module damage. Setting the Fault Mode. Use the jumper below to set the fault mode to the last state (LS) or reset position. LS
Bottom edge of circuit board
RESET
Fault Mode Selection Plug (shown in last state position)
Status Indicators. The front panel has one green, module-active indicator, 16 red status indicators and one red fuse-blown indicator. The 1771-OMD performs diagnostics in a handshaking mode when first powered up. Upon successful completion of the diagnostics, the module-active indicator lights. It turns off if a fault occurs in the data paths or the opto-isolators. Each status indicator provides system logic side indication of individual outputs. They light when the corresponding output is energized.
L1 L1 L1 L1 Output 00 Output 01 Output 02 Output 03 Output 04 Output 05 Output 06 Output 07 Output 10 Output 11 Output 12 Output 13 Output 14 Output 15 Output 16 Output 17 L2
A B C D 00 01 02 03 04 05 06 07 10 11 12 13 14 15 16 17 E
L1 ac high
Output Device
L2 ac low 11924-I
Publication 1771-2.182 - July 1996
Page 49
48
1771 Digital I/O AC Input and Output Modules
AC Output Module (Cat. No. 1771-OMD Series B) Specifications (Cat. No. 1771-OMD/B) Outputs per Module
16
Module Location
1771-A1B thru -A4B or later I/O chassis 1771-AM1, -AM2 I/O chassis
Output Voltage Range
184 to 250V ac @ 47 - 63Hz
Output Current Rating
2A per output - not to exceed 8A per module
Surge Current (maximum)
25A per output for 100ms, repeatable every 1 second 25A per module for 100ms, repeatable every 1 second
Load Current (minimum)
10mA per output @ 220V ac, 60Hz
On-State Voltage Drop
1.5V at 2A (max.)
Off-State Leakage Current
4mA per output @ 220V ac (max.)
Signal Delay
Off to On On to Off
1.0ms 8.3-9.1ms @ 60Hz
Power Dissipation
17.3 Watts (max.); 3.7 Watts (min.)
Thermal Dissipation
59.0 BTU/hr (max.); 12.6 BTU/hr (min.)
Backplane Current
700mA @ 5V dc +5%
Isolation Voltage
Isolation meets or exceeds UL Standard 508, and CSA Standard C22.2 No. 142.
Environmental Conditions Operational Temperature Storage Temperature Relative Humidity Conductors
Wire Size Category
0o to 60oC (32o to 140oF) -40o to 85oC (-40o to 185oF) 5 to 95% without condensation 14 gauge (2mm2) stranded maximum 3/64 inch (1.2mm) insulation maximum 11
Keying
Between 2 and 4 Between 6 and 8
Fuse
10A, 250V rectifier fuse (1/4 x 1-1/4 inch), Littelfuse PN 322010 3AB
Field Wiring Arm Standard Optional Fused
Catalog Number 1771-WH Catalog Number 1771-WHF, -WHFB
Wiring Arm Screw Torque
7-9 inch pounds
Status Indicators
Module Active Indicator (green)
ACTIVE 00 10 01 11 02 12 03 13 04 14 05 15 06 16 07 17 FUSE
00 to 17 Status Indicators (red) Fuse Blown Indicator (red) 11927-I
Sample Connection Diagram Driving a 1771-IM Module with a 1771-OMD Module AC/DC (220V) Input Module (Cat. No. 1771-IM)
AC (220V) Output Module (Cat. No. 1771-OMD)
L1 220V ac High
10K Ohm, 10W resistor or electrocube snubber (part number RG-1676-32)
Agency Certification • CSA certified (when product or packaging is • CSA Class I, Division 2, marked) Groups A, B, C, D certified • UL listed • CE marked for all applicable directives Installation Instructions 1
1771-5.26
You use this conductor-category information for planning conductor routing as described in the system-level installation manual.
L2 ac low Note: 1771-OMD output voltage range is 184-250V ac. However, the on-state voltage range of the 1771-IM is 184-276V ac. 11926-I
Publication 1771-2.182 - July 1996
Page 50
1771 Digital I/O AC Input and Output Modules
49
AC Output Module (Cat. No. 1771-ON)
Simplified Schematic
1.2K
Fuse Blown Indication 68
Output Logic
Opto Isolation
Rect & Filter CIrcuit
.1µF
L1
Fuse 2A
8.2K
MOV
10
L2 47K 5.1K
4.7K
Output Indication
Output 18511
Application Notes
Connection Diagram
Device Compatibility. An output on the 1771-ON module can drive an Allen-Bradley motor starter up to a size 3, provided its supply voltage does not drop below 20V ac. Connection to Input Modules. You can use an ac (24V) output module (Cat. No. 1771-ON) to drive an ac (24V) input module (Cat. No. 1771-IN) but you must connect a 250 ohm 5W resistor between the output terminal and L2 (common). When using a (Cat. No. 1771-ON) to drive an ac (24V) input module (Cat. No. 1771-IND) connect a 470 ohm, 3W resistor between the output terminal and L2 (common). Use the same ac power source to power both modules to ensure proper phasing and prevent module damage. Status Indicators. The front panel has eight red status indicators and a fuse-blown indicator. The top indicator lights when a fuse has blown. The eight status indicators light when the corresponding output is energized. The indicators are provided for field side indication of individual outputs.
L1
A
Output 0
0
Output 1
1
Output 2
2
Output 3
3
Output 4
4
Output 5
5
Output 6
6
Output 7
7
L2
B
(Actual wiring runs in this direction.)
L1 24V ac high Output Device
L2 ac low
11899-I
Publication 1771-2.182 - July 1996
Page 51
50
1771 Digital I/O AC Input and Output Modules
AC Output Module (Cat. No. 1771-ON) Specifications (Cat. No. 1771-ON) Outputs per Module
8
Module Location
1771 I/O chassis
Output Voltage Range Nominal Output Voltage Output Current Rating (maximum) Surge Current (maximum) per Output and Module Minimum Load Current
20 to 30V ac @ 47 - 63Hz 24V ac, 50/60Hz 1.5A per output - not to exceed 6A per module
100mA per output @ 24V ac, 60Hz 2V at 100mA
Off State Leakage Current (max.)
4mA per output @ 30V ac
Off to On On to Off
1.0ms 8.3ms @ 60Hz
Power Dissipation
13.2 Watts (max.), 1.2 Watts (min.)
Thermal Dissipation
45.1 BTU/hr (max.), 4.1 BTU/hr (min.)
Backplane Current
225mA @ 5V dc + 5%
Isolation Voltage
Isolation meets or exceeds UL Standard 508, and CSA Standard C22.2 No. 142.
Environmental Conditions Operational Temperature Storage Temperature Relative Humidity Conductors
Wire Size Category
Keying Fuse
Field Wiring Arm Wiring Arm Screw Torque Agency Certification (when product or packaging is marked)
Installation Instructions 1
0o to 60oC (32o to 140oF) -40o to 85oC (-40o to 185oF) 5 to 95% (without condensation) 14 gauge (2mm2) stranded maximum 3/64 inch (1.2mm) insulation maximum 11 Between 4 and 6 Between 12 and 14
Status Indicators
11901-I
Sample Connection Diagram Driving a 1771-IN Module with a 1771-ON Module AC (24V) Output Module (Cat. No. 1771-ON)
A O
AC/DC (24V) Input Module (Cat. No. 1771-IN) L1 24V ac high
A O
250V 2A Normal Blow Bussman Fuse AGC-2 Littelfuse 312002
1
1
2
2 3
Catalog Number 1771-WA
3 4
4
7-9 inch pounds • CSA certified • CSA Class I, Division 2, Groups A, B, C, D certified • UL listed • CE marked for all applicable directives 1771-2.42
`You use this conductor-category information for planning conductor routing as described in the system-level installation manual.
Fuse Blown Output 0 Output 1 Output 2 Output 3 Output 4 Output 5 Output 6 Output 7
4A for 10msec
On State Voltage Drop (max.) Signal Delay
Status Indicators
5
5 250 ohm 5 Watt Resistor
6 7
6 7 B
B L2 ac low Actual wiring runs in this direction.
11900-I
Publication 1771-2.182 - July 1996
Page 52
1771 Digital I/O AC Input and Output Modules
51
AC Output Module (Cat. No. 1771-OND Series B)
Simplified Schematic Output Indication (logic)
L2 MOV 60V L1
Backplane System Circuitry
Opto Isolation
Logic Circuitry
10A
47
MOV 60V
.22µF
Output 18498
Application Notes
Connection Diagram
Device Compatibility, An output from this module can drive an Allen- Bradleysize 3 motor starter provided its supply voltage does not drop below 20 V ac. Product Compatibility. This module must be used with a 1771-A1B thru -A4B or later I/O chassis. Connection to Wiring Arm. You need 4 ac (L1) connections on the wiring arm to accommodate the total required surge rating on the module without over stressing any single connection on the field wiring arm. Make ac (L1) connection to the wiring arm using the copper four-position jumper (pt. no. 976328-01) supplied with the field wiring arm to connect the top 4 terminals. Connection to Input Modules. You can use an ac (24V) output module (cat. no. 1771-OND) to directly drive terminals on an ac input module (cat. no. 1771-IND). You can also use an output module (cat. no. 1771-OND) to drive an ac (24V) input module (cat. no. 1771-IN) but you must connect a 250 ohm, 5W resistor between the output terminal and L2 (common). Use the same power source to power both modules to ensure proper phasing and to prevent module damage. Setting the Fault Mode. Use the jumper below to set the fault mode to the last state (LS) or reset position.
LS
Bottom edge of circuit board
RESET
Fault Mode Selection Plug (shown in last state position)
Status Indicators. The module front panel has one green module-active indicator, 16 red status indicators and one red fuse-blown indicator. The 1771-OND performs diagnostics in a handshaking mode when first powered up. Upon successful completion of the diagnostics, the green module-active indicator lights. It turns off if a fault occurs in the data paths or the opto-isolators. The status indicators provide system logic side indication of individual outputs. They light when the corresponding output has been energized.
L1 L1 L1 L1 Output 00 Output 01 Output 02 Output 03 Output 04 Output 05 Output 06 Output 07 Output 10 Output 11 Output 12 Output 13 Output 14 Output 15 Output 16 Output 17 L2
A B C D 00 01 02 03 04
L1 24V ac
Output Device
05 06 07 10 11 12 13 14 15 16 17
L2
E ac low
(Actual wiring runs in this direction.) 10674-I
Publication 1771-2.182 - July 1996
Page 53
52
1771 Digital I/O AC Input and Output Modules
AC Output Module (Cat. No. 1771-OND Series B)
Status Indicators
Specifications (Cat. No. 1771-OND/B) Outputs per Module
16
Module Location
1771-A1B thru -A4B I/O chassis 1771-AM1, -AM2 I/O Chassis
Output Voltage Range
10 to 60V ac @ 47 - 63Hz
Output Current Rating
2A per output
Surge Current (maximum)
not to exceed 8A per module
25A per output for 100ms, repeatable every 1 second 25A per module for 100ms, repeatable every 1 second
Load Current (minimum)
50mA per output @ 24V ac, 60Hz
On-State Voltage Drop (max.)
1.6V at 2A
Off-State Leakage Current (max.)
3mA per output @ 24V ac
Signal Delay
Off to On On to Off
1.0ms 8.3-9.1ms @ 60Hz
Power Dissipation
16.5 Watts (max.); 3.7 Watts (min.)
Thermal Dissipation
56.2 BTU/hr (max.); 12.6 BTU/hr (min.)
Backplane Current
700mA @ 5V dc +5%
Isolation Voltage
Isolation meets or exceeds UL Standard 508, and CSA Standard C22.2 No. 142.
Environmental Conditions Operational Temperature Storage Temperature Relative Humidity Conductors
0o to 60oC (32o to 140oF) -40o to 85oC (-40o to 185oF) 5 to 95% (without condensation)
Category Keying
Between 20 and 22 Between 32 and 34
Fuse
10A, 250V rectifier fuse (1/4 x 1-1/4 inch), Littelfuse PN 322010
Field Wiring Arm Standard
Fuse Blown Indicator (red) 10676-I
Sample Connection Diagram Driving a 1771-IN Module with a 1771-OND Module AC (24V) Output Module (Cat. No. 1771-OND)
AC (24V) Input Module (Cat. No. 1771-IN)
L1 24V ac high
Catalog Number 1771-WH Catalog Number 1771-WHF, -WHFB
Optional Fused Wiring Arm Screw Torque
7-9 inch-pounds • CSA certified • CSA Class I, Division 2, Groups A, B, C, D certified • UL listed • CE marked for all applicable directives
Installation Instructions 1
00 to 17 Status Indicators (red)
14 gauge (2mm2) stranded maximum 3/64 inch (1.2mm) insulation maximum 11
Wire Size
Agency Certification (when product or packaging is marked)
Module Active Indicator (green) ACTIVE 00 10 01 11 02 12 03 13 04 14 05 15 06 16 07 17 FUSE
250 Ohm 5W resistor
1771-5.41
You use this conductor-category information for planning conductor routing as described in the system-level installation manual.
L2 ac low
10675-I
Publication 1771-2.182 - July 1996
Page 54
1771 Digital I/O AC Input and Output Modules
53
Protected AC Output Module (Cat. No. 1771-OP)
Simplified Schematic
Neon Fuse Blown Indicator
100K
L1
100 Backplane Logic Circuitry
Opto Isolation
Rect & Filter Circuit
5 Amp Fuse
.047µF 200K
200K
22 100
MOV 200K
100K
MOV
Neon Output Indicator
Neon Triac Failure Indicator Output
Protection Circuit Alarm Fuse
5.6K 2W
.5 Amp
1.5Ohm 5W
L2
18504
Application Notes
Connection Diagram
Device Compatibility. An output from this module can drive an Allen-Bradley Size-5 motor starter, provided its supply voltage does not drop below 92V ac. L1
A
Not used
O
Not used
1
Connection to Input Modules. The cat. no. 1771-OP can drive an input of a 120V ac input module (1771-IA, -IA2, , -IAD, -ID). However, you must connect a 2.5K ohm, 10W external resistor or an electrocube (part number RG-1676-1) between the output terminal and L2 (common). Use the same ac power source to power both modules to ensure proper phasing and to prevent module damage.
Output 0
2
Output 1
3
Output 2
4
Output 3
5
Status Indicators. The front panel has six status indicators. TheTriac Fail indicator lights when one of the output triacs has failed and caused the output fuse to open. The fuse-blown indicator lights when an output fuse has opened. The four output indicators show the ON/OFF state of outputs. The indicators provide field side indication of individual outputs.
Not used
6
Not used
7
L2
B
Minimum/Maximum Load Current. The maximum load current the module can deliver is 2A per output not to exceed 6A per module. The triac needs a minimum of 80mA of load current to stay on.
ATTENTION: Do not configure the module so that 120V ac is fed back into the output of the module. Failure to observe this caution can result in damage to the module circuitry.
L1 120V ac high
Output Device
L2 ac low
(Actual wiring runs in this direction.) 11891-I