For the Allen-Bradley 1771-IA and Allen-Bradley 1771-OD16

Page 46

1771 Digital I/O AC Input and Output Modules

45

AC Output Module (Cat. No. 1771-OM)

Simplified Schematic

Fuse Blown Indication 200K 100

System Circuitry

Opto Isolation

Rect & Filter Circuit

0.047µF

L1

Fuse 2A

820K

MOV

30K

22 100

200K

L2

430K

Output Indicator

Output 18516

Application Notes

Connection Diagram

Device Compatibility. You can drive an Allen-Bradley motor starter size 4 , provided its supply voltage does not drop below 184 V. Minimum/Maximum Load Current. The module needs a minimum load current of 60mA to stay on. If your device pulls less than 60mA the triac will not operate. The maximum load current the module can deliver is 2A per output, not to exceed 6A total per module. Connection to Input Modules. You can use an ac (220/240V) output module (cat. no. 1771-OM) to drive terminals on an ac (220/240V) input module (cat. no. 1771-IM), but you must connect a 3.3K ohm, 20 Watt resistor between the output terminal and L2 (common). You can also use an ac (220/240V) output module (cat. no.1771-OM) to drive terminals on an ac (220V) input module (cat. no. 1771-IMD), but you must connect a 10K ohm, 10 Watt resistor or an electrocube snubber (part number RG-1676-32) between the output terminal and L2 (common). Use the same power source to power both modules to ensure proper phasing, and to prevent module damage. Status Indicators. The front panel has eight orange status indicators and one orange fuse-blown indicator. The status indicators light when the corresponding output is energized. The fuse-blown indicator lights when any of the 8 fuses in the module are blown. The indicators are provided for field side indication of individual outputs.

L1

A

Output 0

O

Output 1

1

Output 2

2

Output 3

3

Output 4

4

Output 5

5

Output 6

6

Output 7

7

L2

B

L1 220/240V ac High

Load

Suppression

Relay Contact

MS

L2 ac Low

Actual wiring runs in this direction. 11896-I

Publication 1771-2.182 - July 1996

Page 47

46

1771 Digital I/O AC Input and Output Modules

AC Output Module (Cat. No. 1771-OM) Specifications (Cat. No. 1771-OM) Outputs per Module

8

Module Location

1771 I/O chassis

Output Voltage Range

184 to 250V ac @ 47 - 63Hz

Output Current Rating

2A per output

Surge Current (maximum) per Output and Module

20A for 100ms, repeatable every 10 seconds

Load Current (minimum)

60mA per output @ 220V ac, 60Hz not to exceed 6A per module

On-State Voltage Drop (max.)

1.6V at 2A

Off-State Leakage Current (max.)

2mA per output @ 220V ac

Signal Delay

Off to On On to Off

13.2 Watts (max.), 1.2 Watts (min.)

Thermal Dissipation

45.1 BTU/hr (max.), 4.1 BTU/hr (min.)

Backplane Current

225mA @ 5V dc +5%

Isolation Voltage

Isolation meets or exceeds UL Standard 508, and CSA Standard C22.2 No. 142.

Conductors

Wire Size Category

0o to 60oC (32o to 140oF) -40o to 85oC (-40o to 185oF) 5 to 95% (without condensation)

Between 6 and 8 Between 28 and 30

Fuse

2A, 250V 3AG Normal Blow (1 per output) Buss Fuse AGC-2, Littelfuse 312002

Wiring Arm Screw Torque Agency Certification (when product or packaging is marked)

Installation Instructions 1

Status Indicators

Note: An output terminal need not be connected to a load in order for its status indicator to light. 11898-I

Sample Connection Diagram Driving a 1771-IMD Module with a 1771-OM Module

AC (220V) Input Module (Cat. No. 1771-IMD)

14 gauge (2mm2) stranded maximum 3/64 inch (1.2mm) insulation maximum 21

Keying

Field Wiring Arm

Fuse Blown Output 0 Output 1 Output 2 Output 3 Output 4 Output 5 Output 6 Output 7

1.0ms 8.3ms @ 60Hz

Power Dissipation

Environmental Conditions Operational Temperature Storage Temperature Relative Humidity

Status Indicators

Catalog Number 1771-WA 7-9 inch pounds

AC (220/240V) Output Module (Cat. No. 1771-OM)

A

• CSA certified • CSA Class I, Division 2, Groups A, B, C, D certified • UL listed • CE marked for all applicable directives

O

1771-2.18

4

You use this conductor-category information for planning conductor routing as described in the system-level installation manual.

A B C D 00 01 02

L1 ac high

1 2 3

10K ohm 10W resistor or electrocube snubber (part number RG-1676-32)

5 6 7 B

03 04 05 06 07 10 11 12 13 14 15 16 17 E

L2 ac low 11897-I

Publication 1771-2.182 - July 1996

Page 48

1771 Digital I/O AC Input and Output Modules

47

AC Output Module (Cat. No. 1771-OMD Series B)

Simplified Schematic LED Output Indication

L2 MOV 275V L1

Backplane Logic Circuitry

Opto Isolation

Logic Circuitry

10A

100 .022µF

MOV 275V Output 18508

Application Notes

Connection Diagram

Device Compatibility. An output from this module can drive an Allen-Bradley size 5 motor starter provided its supply voltage does not drop below 184V.

AC (220V) Output Module (Cat. No. 1771-OMD)

Product Compatibility. This module must be used with a 1771-A1B thru -A4B or later I/O chassis. Connection to Wiring Arm. You need 4 ac (L1) connections on the wiring arm to accommodate the total surge rating on the module without overstressing any single connection on the field wiring arm. Use the copper four-position jumper (part number 976328-01) that comes with the wiring arm supplied with the 1771-OMD module for distributing ac (L1) across the connections. Connection to Input Modules. This module can directly drive terminals on ac/dc input modules (cat. nos. 1771-IMD). You can also use a 1771-OMD to drive ac/dc input modules (cat. nos. 1771-IM, -ID01) but you must connect a 10K ohm 10W resistor between the outputs and L2 (common). As an alternative you can use an electrocube snubber (part number RG-1676-32). Use the same ac power source to ensure proper phasing and prevent module damage. Setting the Fault Mode. Use the jumper below to set the fault mode to the last state (LS) or reset position. LS

Bottom edge of circuit board

RESET

Fault Mode Selection Plug (shown in last state position)

Status Indicators. The front panel has one green, module-active indicator, 16 red status indicators and one red fuse-blown indicator. The 1771-OMD performs diagnostics in a handshaking mode when first powered up. Upon successful completion of the diagnostics, the module-active indicator lights. It turns off if a fault occurs in the data paths or the opto-isolators. Each status indicator provides system logic side indication of individual outputs. They light when the corresponding output is energized.

L1 L1 L1 L1 Output 00 Output 01 Output 02 Output 03 Output 04 Output 05 Output 06 Output 07 Output 10 Output 11 Output 12 Output 13 Output 14 Output 15 Output 16 Output 17 L2

A B C D 00 01 02 03 04 05 06 07 10 11 12 13 14 15 16 17 E

L1 ac high

Output Device

L2 ac low 11924-I

Publication 1771-2.182 - July 1996

Page 49

48

1771 Digital I/O AC Input and Output Modules

AC Output Module (Cat. No. 1771-OMD Series B) Specifications (Cat. No. 1771-OMD/B) Outputs per Module

16

Module Location

1771-A1B thru -A4B or later I/O chassis 1771-AM1, -AM2 I/O chassis

Output Voltage Range

184 to 250V ac @ 47 - 63Hz

Output Current Rating

2A per output - not to exceed 8A per module

Surge Current (maximum)

25A per output for 100ms, repeatable every 1 second 25A per module for 100ms, repeatable every 1 second

Load Current (minimum)

10mA per output @ 220V ac, 60Hz

On-State Voltage Drop

1.5V at 2A (max.)

Off-State Leakage Current

4mA per output @ 220V ac (max.)

Signal Delay

Off to On On to Off

1.0ms 8.3-9.1ms @ 60Hz

Power Dissipation

17.3 Watts (max.); 3.7 Watts (min.)

Thermal Dissipation

59.0 BTU/hr (max.); 12.6 BTU/hr (min.)

Backplane Current

700mA @ 5V dc +5%

Isolation Voltage

Isolation meets or exceeds UL Standard 508, and CSA Standard C22.2 No. 142.

Environmental Conditions Operational Temperature Storage Temperature Relative Humidity Conductors

Wire Size Category

0o to 60oC (32o to 140oF) -40o to 85oC (-40o to 185oF) 5 to 95% without condensation 14 gauge (2mm2) stranded maximum 3/64 inch (1.2mm) insulation maximum 11

Keying

Between 2 and 4 Between 6 and 8

Fuse

10A, 250V rectifier fuse (1/4 x 1-1/4 inch), Littelfuse PN 322010 3AB

Field Wiring Arm Standard Optional Fused

Catalog Number 1771-WH Catalog Number 1771-WHF, -WHFB

Wiring Arm Screw Torque

7-9 inch pounds

Status Indicators

Module Active Indicator (green)

ACTIVE 00 10 01 11 02 12 03 13 04 14 05 15 06 16 07 17 FUSE

00 to 17 Status Indicators (red) Fuse Blown Indicator (red) 11927-I

Sample Connection Diagram Driving a 1771-IM Module with a 1771-OMD Module AC/DC (220V) Input Module (Cat. No. 1771-IM)

AC (220V) Output Module (Cat. No. 1771-OMD)

L1 220V ac High

10K Ohm, 10W resistor or electrocube snubber (part number RG-1676-32)

Agency Certification • CSA certified (when product or packaging is • CSA Class I, Division 2, marked) Groups A, B, C, D certified • UL listed • CE marked for all applicable directives Installation Instructions 1

1771-5.26

You use this conductor-category information for planning conductor routing as described in the system-level installation manual.

L2 ac low Note: 1771-OMD output voltage range is 184-250V ac. However, the on-state voltage range of the 1771-IM is 184-276V ac. 11926-I

Publication 1771-2.182 - July 1996

Page 50

1771 Digital I/O AC Input and Output Modules

49

AC Output Module (Cat. No. 1771-ON)

Simplified Schematic

1.2K

Fuse Blown Indication 68

Output Logic

Opto Isolation

Rect & Filter CIrcuit

.1µF

L1

Fuse 2A

8.2K

MOV

10

L2 47K 5.1K

4.7K

Output Indication

Output 18511

Application Notes

Connection Diagram

Device Compatibility. An output on the 1771-ON module can drive an Allen-Bradley motor starter up to a size 3, provided its supply voltage does not drop below 20V ac. Connection to Input Modules. You can use an ac (24V) output module (Cat. No. 1771-ON) to drive an ac (24V) input module (Cat. No. 1771-IN) but you must connect a 250 ohm 5W resistor between the output terminal and L2 (common). When using a (Cat. No. 1771-ON) to drive an ac (24V) input module (Cat. No. 1771-IND) connect a 470 ohm, 3W resistor between the output terminal and L2 (common). Use the same ac power source to power both modules to ensure proper phasing and prevent module damage. Status Indicators. The front panel has eight red status indicators and a fuse-blown indicator. The top indicator lights when a fuse has blown. The eight status indicators light when the corresponding output is energized. The indicators are provided for field side indication of individual outputs.

L1

A

Output 0

0

Output 1

1

Output 2

2

Output 3

3

Output 4

4

Output 5

5

Output 6

6

Output 7

7

L2

B

(Actual wiring runs in this direction.)

L1 24V ac high Output Device

L2 ac low

11899-I

Publication 1771-2.182 - July 1996

Page 51

50

1771 Digital I/O AC Input and Output Modules

AC Output Module (Cat. No. 1771-ON) Specifications (Cat. No. 1771-ON) Outputs per Module

8

Module Location

1771 I/O chassis

Output Voltage Range Nominal Output Voltage Output Current Rating (maximum) Surge Current (maximum) per Output and Module Minimum Load Current

20 to 30V ac @ 47 - 63Hz 24V ac, 50/60Hz 1.5A per output - not to exceed 6A per module

100mA per output @ 24V ac, 60Hz 2V at 100mA

Off State Leakage Current (max.)

4mA per output @ 30V ac

Off to On On to Off

1.0ms 8.3ms @ 60Hz

Power Dissipation

13.2 Watts (max.), 1.2 Watts (min.)

Thermal Dissipation

45.1 BTU/hr (max.), 4.1 BTU/hr (min.)

Backplane Current

225mA @ 5V dc + 5%

Isolation Voltage

Isolation meets or exceeds UL Standard 508, and CSA Standard C22.2 No. 142.

Environmental Conditions Operational Temperature Storage Temperature Relative Humidity Conductors

Wire Size Category

Keying Fuse

Field Wiring Arm Wiring Arm Screw Torque Agency Certification (when product or packaging is marked)

Installation Instructions 1

0o to 60oC (32o to 140oF) -40o to 85oC (-40o to 185oF) 5 to 95% (without condensation) 14 gauge (2mm2) stranded maximum 3/64 inch (1.2mm) insulation maximum 11 Between 4 and 6 Between 12 and 14

Status Indicators

11901-I

Sample Connection Diagram Driving a 1771-IN Module with a 1771-ON Module AC (24V) Output Module (Cat. No. 1771-ON)

A O

AC/DC (24V) Input Module (Cat. No. 1771-IN) L1 24V ac high

A O

250V 2A Normal Blow Bussman Fuse AGC-2 Littelfuse 312002

1

1

2

2 3

Catalog Number 1771-WA

3 4

4

7-9 inch pounds • CSA certified • CSA Class I, Division 2, Groups A, B, C, D certified • UL listed • CE marked for all applicable directives 1771-2.42

`You use this conductor-category information for planning conductor routing as described in the system-level installation manual.

Fuse Blown Output 0 Output 1 Output 2 Output 3 Output 4 Output 5 Output 6 Output 7

4A for 10msec

On State Voltage Drop (max.) Signal Delay

Status Indicators

5

5 250 ohm 5 Watt Resistor

6 7

6 7 B

B L2 ac low Actual wiring runs in this direction.

11900-I

Publication 1771-2.182 - July 1996

Page 52

1771 Digital I/O AC Input and Output Modules

51

AC Output Module (Cat. No. 1771-OND Series B)

Simplified Schematic Output Indication (logic)

L2 MOV 60V L1

Backplane System Circuitry

Opto Isolation

Logic Circuitry

10A

47

MOV 60V

.22µF

Output 18498

Application Notes

Connection Diagram

Device Compatibility, An output from this module can drive an Allen- Bradleysize 3 motor starter provided its supply voltage does not drop below 20 V ac. Product Compatibility. This module must be used with a 1771-A1B thru -A4B or later I/O chassis. Connection to Wiring Arm. You need 4 ac (L1) connections on the wiring arm to accommodate the total required surge rating on the module without over stressing any single connection on the field wiring arm. Make ac (L1) connection to the wiring arm using the copper four-position jumper (pt. no. 976328-01) supplied with the field wiring arm to connect the top 4 terminals. Connection to Input Modules. You can use an ac (24V) output module (cat. no. 1771-OND) to directly drive terminals on an ac input module (cat. no. 1771-IND). You can also use an output module (cat. no. 1771-OND) to drive an ac (24V) input module (cat. no. 1771-IN) but you must connect a 250 ohm, 5W resistor between the output terminal and L2 (common). Use the same power source to power both modules to ensure proper phasing and to prevent module damage. Setting the Fault Mode. Use the jumper below to set the fault mode to the last state (LS) or reset position.

LS

Bottom edge of circuit board

RESET

Fault Mode Selection Plug (shown in last state position)

Status Indicators. The module front panel has one green module-active indicator, 16 red status indicators and one red fuse-blown indicator. The 1771-OND performs diagnostics in a handshaking mode when first powered up. Upon successful completion of the diagnostics, the green module-active indicator lights. It turns off if a fault occurs in the data paths or the opto-isolators. The status indicators provide system logic side indication of individual outputs. They light when the corresponding output has been energized.

L1 L1 L1 L1 Output 00 Output 01 Output 02 Output 03 Output 04 Output 05 Output 06 Output 07 Output 10 Output 11 Output 12 Output 13 Output 14 Output 15 Output 16 Output 17 L2

A B C D 00 01 02 03 04

L1 24V ac

Output Device

05 06 07 10 11 12 13 14 15 16 17

L2

E ac low

(Actual wiring runs in this direction.) 10674-I

Publication 1771-2.182 - July 1996

Page 53

52

1771 Digital I/O AC Input and Output Modules

AC Output Module (Cat. No. 1771-OND Series B)

Status Indicators

Specifications (Cat. No. 1771-OND/B) Outputs per Module

16

Module Location

1771-A1B thru -A4B I/O chassis 1771-AM1, -AM2 I/O Chassis

Output Voltage Range

10 to 60V ac @ 47 - 63Hz

Output Current Rating

2A per output

Surge Current (maximum)

not to exceed 8A per module

25A per output for 100ms, repeatable every 1 second 25A per module for 100ms, repeatable every 1 second

Load Current (minimum)

50mA per output @ 24V ac, 60Hz

On-State Voltage Drop (max.)

1.6V at 2A

Off-State Leakage Current (max.)

3mA per output @ 24V ac

Signal Delay

Off to On On to Off

1.0ms 8.3-9.1ms @ 60Hz

Power Dissipation

16.5 Watts (max.); 3.7 Watts (min.)

Thermal Dissipation

56.2 BTU/hr (max.); 12.6 BTU/hr (min.)

Backplane Current

700mA @ 5V dc +5%

Isolation Voltage

Isolation meets or exceeds UL Standard 508, and CSA Standard C22.2 No. 142.

Environmental Conditions Operational Temperature Storage Temperature Relative Humidity Conductors

0o to 60oC (32o to 140oF) -40o to 85oC (-40o to 185oF) 5 to 95% (without condensation)

Category Keying

Between 20 and 22 Between 32 and 34

Fuse

10A, 250V rectifier fuse (1/4 x 1-1/4 inch), Littelfuse PN 322010

Field Wiring Arm Standard

Fuse Blown Indicator (red) 10676-I

Sample Connection Diagram Driving a 1771-IN Module with a 1771-OND Module AC (24V) Output Module (Cat. No. 1771-OND)

AC (24V) Input Module (Cat. No. 1771-IN)

L1 24V ac high

Catalog Number 1771-WH Catalog Number 1771-WHF, -WHFB

Optional Fused Wiring Arm Screw Torque

7-9 inch-pounds • CSA certified • CSA Class I, Division 2, Groups A, B, C, D certified • UL listed • CE marked for all applicable directives

Installation Instructions 1

00 to 17 Status Indicators (red)

14 gauge (2mm2) stranded maximum 3/64 inch (1.2mm) insulation maximum 11

Wire Size

Agency Certification (when product or packaging is marked)

Module Active Indicator (green) ACTIVE 00 10 01 11 02 12 03 13 04 14 05 15 06 16 07 17 FUSE

250 Ohm 5W resistor

1771-5.41

You use this conductor-category information for planning conductor routing as described in the system-level installation manual.

L2 ac low

10675-I

Publication 1771-2.182 - July 1996

Page 54

1771 Digital I/O AC Input and Output Modules

53

Protected AC Output Module (Cat. No. 1771-OP)

Simplified Schematic

Neon Fuse Blown Indicator

100K

L1

100 Backplane Logic Circuitry

Opto Isolation

Rect & Filter Circuit

5 Amp Fuse

.047µF 200K

200K

22 100

MOV 200K

100K

MOV

Neon Output Indicator

Neon Triac Failure Indicator Output

Protection Circuit Alarm Fuse

5.6K 2W

.5 Amp

1.5Ohm 5W

L2

18504

Application Notes

Connection Diagram

Device Compatibility. An output from this module can drive an Allen-Bradley Size-5 motor starter, provided its supply voltage does not drop below 92V ac. L1

A

Not used

O

Not used

1

Connection to Input Modules. The cat. no. 1771-OP can drive an input of a 120V ac input module (1771-IA, -IA2, , -IAD, -ID). However, you must connect a 2.5K ohm, 10W external resistor or an electrocube (part number RG-1676-1) between the output terminal and L2 (common). Use the same ac power source to power both modules to ensure proper phasing and to prevent module damage.

Output 0

2

Output 1

3

Output 2

4

Output 3

5

Status Indicators. The front panel has six status indicators. TheTriac Fail indicator lights when one of the output triacs has failed and caused the output fuse to open. The fuse-blown indicator lights when an output fuse has opened. The four output indicators show the ON/OFF state of outputs. The indicators provide field side indication of individual outputs.

Not used

6

Not used

7

L2

B

Minimum/Maximum Load Current. The maximum load current the module can deliver is 2A per output not to exceed 6A per module. The triac needs a minimum of 80mA of load current to stay on.

ATTENTION: Do not configure the module so that 120V ac is fed back into the output of the module. Failure to observe this caution can result in damage to the module circuitry.

L1 120V ac high

Output Device

L2 ac low

(Actual wiring runs in this direction.) 11891-I

Publication 1771-2.182 - July 1996