For the Allen-Bradley 1771-IA and Allen-Bradley 1771-OD16
Page 55
54
1771 Digital I/O AC Input and Output Modules
Protected AC Output Module (Cat. No. 1771-OP) Specifications (Cat. No. 1771-OP)
Status Indicators
Outputs per Module
4
Module Location
1771 I/O chassis
Output Voltage Range
92 to 138V ac @ 47 - 63Hz
Output Current Rating (maximum)
2A per output
Surge Current (maximum) per Output and Module
20A for 60ms, repeatable every 2 seconds
Load Current (minimum)
80mA per output @ 120V ac, 60Hz
On-State Voltage Drop (max.)
2V ac at 100mA
Off-State Leakage Current (max.)
6mA per output @ 120V ac
Signal Delay
1.0ms 8.3ms at 60Hz
Power Dissipation
13.9 Watts (max.), 1.8 Watts (min.)
Thermal Dissipation
47.2 BTU/hr (max.), 6.1 BTU/hr (min.)
Backplane Current
350mA @ 5V dc + 5%
Isolation Voltage
Isolation meets or exceeds UL Standard 508, and CSA Standard C22.2 No. 142.
Environmental Conditions Operational Temperature Storage Temperature Relative Humidity Conductors Wire Size
0o to 60oC (32o to 140oF) -40o to 85oC (-40o to 185oF) 5 to 95% without condensation 14 gauge (2mm2) stranded maximum 3/64 inch (1.2mm) insulation maximum 11
Category Keying
Between 6 and 8 Between 26 and 28
Fuses
0.5A Bussmann GLD1/2 5A Bussmann 250V Normal Littelfuse 312005 5A
Field Wiring Arm Wiring Arm Screw Torque
Sample Connection Diagram Driving a 1771-IA Module with a 1771-OP Module Protected AC (120V) Output Module Cat. No. 1771-OP
AC (120V) Input Module Cat. No. 1771-IA L1
A ac High
A
O
O
1
1
2
2
3
3
4
4
5
5
Catalog Number 1771-WA
6
7-9 inch-pounds
7
• CSA certified • CSA Class I, Division 2, Groups A, B, C, D certified • UL listed • CE marked for all applicable directives
Installation Instructions 1
Note: The Triac Fail indicator illuminates when one of the output triacs has shorted and caused the output fuse to open. If the light is on,the module should be returned to Allen-Bradley for repair.
11893-I
Off to On On to Off
Agency Certification (when product or packaging is marked)
Triac Fail Fuse Blown Output 0 Output 1 Output 2 Output 3 Not used Not used Not used not to exceed 6A per module
B
2.5K Ohm 10 Watt
6 L2 ac low
7 B
1771-2.23
You use this conductor-category information for planning conductor routing as described in the system-level installation manual. 11892-I
Publication 1771-2.182 - July 1996
Page 56
1771 Digital I/O AC Input and Output Modules
55
Isolated AC Output Module (Cat. No. 1771-OR Series B)
Simplified Schematic +5V
1.2k
Output Status Indicator
LED
Backplane Circuitry
Opto Isolation
470K
Indication (fuse blown)
470K
100 Rect & Filter Circuit
L1 5.0 Amp Fuse
0.047µF 22
MOV 100 Output 18497
Application Notes Device Compatibility. An output from this module can drive an Allen- Bradley size 5 motor starter provided its supply voltage does not drop below 184V ac. Minimum/ Maximum Load Current. The maximum load current the module can handle is 2A per output not to exceed 6A per module. The triac needs a minimum load current of 60mA to stay on. Connection to Input Modules. You can use an isolated ac (220V) output module (cat. no.1771-OR) to directly drive terminals on an ac input module (cat. no. 1771-IM or -IMD). However, you must connect a 3.3K ohm, 20W resistor between the output terminal and L2 (common). Status Indicators. The front panel has 12 status indicators. The top six indicators show the state of each output and are driven by the logic circuitry on the controller side of the module. An indicator lights when the corresponding output is energized. The bottom six indicators indicate a fuse-blown condition at the respective output.
Connection Diagram
Output 0A
1
Output 0B
2
Output 1A
3
Output 1B
4
Output 2A
5
Output 2B
6
Output 3A
7
Output 3B
L1 ac high
220V ac Supply
L2 ac low
Output Device
8
Output 4A
9
Output 4B
10
Output 5A
11
Output 5B
12
(Actual wiring runs in this direction.)
11382-I
Publication 1771-2.182 - July 1996
Page 57
56
1771 Digital I/O AC Input and Output Modules
Isolated AC Output Module (Cat. No. 1771-OR Series B) Specifications (Cat. No. 1771-OR/B) Outputs per Module
6
Module Location
1771 I/O chassis
Nominal Output Voltage
220V ac, 50/60Hz
Output Voltage Range
184 to 276V ac @ 47 - 63Hz
Output Current Rating
2A per output - not to exceed 6A per module
Surge Current (maximum) per Output and Module
15A for 100ms, repeatable every 2 seconds
Load Current (minimum)
2V at 100mA
On-state Leakage Current (max.)
10mA per output @ 276V ac
Off to On On to Off
13.2 Watts (max.), 1.2 Watts (min.)
Thermal Dissipation
45.1 BTU/hr (max.), 4.1 BTU/hr (min.)
Backplane Current
255mA @ 5V dc + 5%
Isolation Voltage
Isolation meets or exceeds UL Standard 508, and CSA Standard C22.2 No. 142.
Conductors
Wire Size Category
Keying
Fuse
Field Wiring Arm Wiring Arm Screw Torque Agency Certification (when product or packaging is marked)
Installation Instructions 1
0o to 60oC (32o to 140oF) -40o to 85oC (-40o to 185oF) 5 to 95% (without condensation) 14 gauge (2mm2) stranded maximum 3/64 inch (1.2mm) insulation maximum 11
12216-I
Sample Connection Diagram Driving a 1771-IM Module with a 1771-OR Module (220V) ac input module Cat. No. 1771-IM
Isolated (220V) ac output module Cat. No. 1771-OR L1 ac high
220V ac Supply
L2 ac low
Output 0A
1
Output 0B
2
A
Output 1A
3
O
Output 1B
4
1
5A, 250V 3AG Normal Blow (1 per output) Littelfuse 312005 Bussman Fuse AGC-5
Output 2A
5
2
Output 2B
6
3
Output 3A
7
4
Catalog Number 1771-WD
Output 3B
8
Output 4A
9
Between 4 and 6 Between 30 and 32 Between 34 and 36
7-9 inch-pounds • CSA certified • CSA Class I, Division 2, Groups A, B, C, D certified • UL listed • CE marked for all applicable directives
Output 4B 10 Output 5A 11
3.3K Ohms 20 Watt Resistor
5 6 7 B
Output 5B 12
1771-2.40
You use this conductor-category information for planning conductor routing as described in the system-level installation manual.
Publication 1771-2.182 - July 1996
Fuse Blown Indicators (clear)
1.0ms 8.3ms @ 60Hz
Power Dissipation
Environmental Conditions Operational Temperature Storage Temperature Relative Humidity
Output Status Indicators (red)
60mA per output @ 220V ac, 60Hz
On-state Voltage Drop (max.) Signal Delay
Status Indicators
11389
Page 58
1771 Digital I/O AC Input and Output Modules
57
Notes
Publication 1771-2.182 - July 1996
Page 59
58
1771 Digital I/O AC Input and Output Modules
Notes
Publication 1771-2.182 - July 1996
Page 60
Support Services
Support Services
59
At Allen-Bradley, customer service means experienced representatives at Customer Support Centers in key cities throughout the world for sales service and support. Our value-added services include:
Technical Support • • • •
SupportPlus programs telephone support and 24-hour emergency hotline software and documentation updates technical subscription services
Engineering and Field Services • • • • application engineering assistance integration and start-up assistance field service maintenance support
Technical Training • • • • lecture and lab courses self-paced computer and video-based training job aids and workstations training needs analysis
Repair and Exchange Services • • • • your only “authorized” source current revisions and enhancements worldwide exchange inventory local support
Publication 1771-2.182 - July 1996
Page 61
Allen-Bradley, a Rockwell Automation Business, has been helping its customers improve productivity and quality for more than 90 years. We design, manufacture and support a broad range of automation products worldwide. They include logic processors, power and motion control devices, operator interfaces, sensors and a variety of software. Rockwell is one of the world's leading technology companies.
Worldwide representation. Argentina • Australia • Austria • Bahrain • Belgium • Brazil • Bulgaria • Canada • Chile • China, PRC • Colombia • Costa Rica • Croatia • Cyprus • Czech Republic • Denmark • Ecuador • Egypt • El Salvador • Finland • France • Germany • Greece • Guatemala • Honduras • Hong Kong • Hungary • Iceland • India • Indonesia • Ireland • Israel • Italy • Jamaica • Japan • Jordan • Korea • Kuwait • Lebanon • Malaysia • Mexico • Netherlands • New Zealand • Norway • Pakistan • Peru • Philippines • Poland • Portugal • Puerto Rico • Qatar • Romania • Russia-CIS • Saudi Arabia • Singapore • Slovakia • Slovenia • South Africa, Republic • Spain • Sweden • Switzerland • Taiwan • Thailand • Turkey • United Arab Emirates • United Kingdom • United States • Uruguay • Venezuela • Yugoslavia
Allen-Bradley Headquarters, 1201 South Second Street, Milwaukee, WI 53204 USA, Tel: (1) 414 382-2000 Fax: (1) 414 382-4444
Publication 1771-2.182 - July 1996 Supersedes Publication 1771-2.182 - March 1994
Copyright 1996 Allen-Bradley Company, Inc. Printe