Page 1 of AC (120V) Isolated Output Module, 16 Outputs (Cat. No. 1771-OD16 Series B) Installation Instructions

Manual · Allen-Bradley

AC (120V) Isolated Output Module, 16 Outputs (Cat. No. 1771-OD16 Series B) Installation Instructions

Manual12 pagesPDF 197 KB

Installation instructions for the Allen-Bradley 1771-OD16 Series B AC (120V) isolated output module with 16 outputs.

Download the PDF197 KB

Covers · 2 models

The models it covers

Summary

What is in it

Allen-Bradley installation instructions for the 1771-OD16 Series B AC (120V) isolated output module with 16 outputs. They cover pre-installation considerations such as load and motor starter limits, leakage current and surge suppression, power supply requirements, module placement, setting the fuse-blown jumper (STD or CSI mode), keying the backplane, installing the module and field wiring arm, wiring, reading the status indicators, replacing a fuse and the module specifications.

Its parts

  1. To The Installer
  2. Preinstallation Considerations
  3. Power Supply Requirements
  4. Understand Compliance to European Union Directives
  5. Determining Module Placement in the I/O Chassis
  6. Setting the Mode of the Fuse-Blown Jumper
  7. Key the Backplane Connector
  8. Install the Module and Field Wiring Arm
  9. Connect the Wiring to the Module
  10. Interpreting the Status Indicators
  11. Replacing a Fuse
  12. Specifications

From the manual · read page by page

Key facts from this manual

Each line names its page in the PDF.

These Allen-Bradley installation instructions (publication 1771-5.21, February 1997) cover the 1771-OD16 Series B AC (120V) isolated output module with 16 outputs for 1771 I/O chassis. They explain power needs, placement and keying, the fuse-blown jumper, wiring through the 1771-WN field wiring arm, the status indicators and fuse replacement, and they list the specifications.

Outputs
16 isolated AC (120V) outputs p. 12
Voltage rating
74 to 138V ac, 47-63Hz p. 12
Current rating
5mA-2A continuous per channel; 8A continuous per module; 20A peak surge for 100ms, repeatable every 2 seconds p. 12
Output device
Solid-state triac with zero voltage turn-on p. 1
Fuses
3A 2AG Slo-Blo, 1 per output, Littelfuse P/N 229003; fuse kit 1771-FE holds 5 p. 12
Wiring arm
1771-WN field wiring arm, screw torque 7-9 inch-pounds p. 12
Backplane current
250mA maximum from the +5V dc supply p. 2
Leakage current
3mA maximum at 138V ac; nominal 1.5mA p. 1
Motor starters
16 size 3, 10 size 4 or 7 size 5 motor starters (1 per output) p. 1
Wiring
14 gauge (2mm2) stranded maximum, 3/64 inch (2mm) insulation maximum; cable up to 1000 ft (304.8 m) p. 12
Signal delay
8.3ms @ 60Hz max; 10ms @ 50Hz max (zero cross switching) p. 12
Temperature
Operating 0 to 60°C (32 to 140°F); storage -40 to 85°C (-40 to 185°F); 5 to 95% humidity without condensation p. 12
Keying
Keying bands between 22 and 24 and between 34 and 36 p. 5
Agency marks
The manual states CSA certified, CSA Class I, Division 2, Groups A, B, C, D certified, UL listed and CE marked, when the product or packaging is marked p. 12

What this manual walks you through

  • Fitting inductive loads with surge suppressors p. 2
  • Setting the fuse-blown jumper to STD or CSI mode p. 4, 5
  • Keying the backplane connector p. 5
  • Installing the module and the field wiring arm p. 6
  • Wiring loads to the field wiring arm p. 7
  • Driving a 120V ac input module from an output p. 8
  • Reading the ACTIVE, FUSE and output status indicators p. 9
  • Replacing a blown fuse p. 10

Good to know

  • Do not put the jumper in CSI mode when the module is used in complementary mode. p. 4
  • The wiring arm terminal number is not the number of the bit that controls that output. p. 7
  • Do not connect output channels in series; the output devices can chatter. p. 8
  • The module is not compatible with the 1771-AL local I/O adapter module. p. 2
  • The fuse-blown circuit does not work when the output load current is 5mA or less. p. 9

Questions this manual answers

What fuse does the 1771-OD16 take?

A 3A 2AG slo-blow fuse, Littelfuse part number 229003, one per output. p. 10

How much current can each 1771-OD16 output carry?

Up to 2A per channel, with no more than 8A total per module. p. 1

What voltage does the 1771-OD16/B switch?

74 to 138V ac at 47-63Hz. p. 12

Which wiring arm fits the 1771-OD16?

The 1771-WN field wiring arm, shipped with the module. p. 7

When does the FUSE indicator light on the 1771-OD16?

When a fuse has cleared or been removed and that fuse's channel is turned on. It resets after the fuse is replaced and chassis power is cycled. p. 9

Contents

Chapters and sections

Each line opens the PDF at its page.

  1. 1771-5.21,AC (120V) Isolated Output Module, 161
  2. To The Installer1
  3. Pre-installation Considerations1
  4. Power Supply Requirements2
  5. Understand Compliance to European Union Directives2
  6. Determining Module Placement in the I/O Chassis3
  7. Setting the Mode of the Fuse-Blown Jumper4
  8. Key the Backplane Connector5
  9. Install the Module and Field Wiring Arm6
  10. Connect the Wiring to the Module7
  11. Interpreting the Status Indicators9
  12. Replacing a Fuse10
  13. Specifications12
  14. Back Cover12

From the PDF’s own bookmarks.

The whole text · 2 parts

Read the manual here as text

Its text as extracted from the PDF, unedited, in parts; each page opens the PDF at that page.

  1. Pages 1 to 61-6
  2. Pages 7 to 127-12

The file

Revision and size

RevisionPublication 1771-5.21, February 1997
PublisherAllen-Bradley
Pages12
PDF197 KB
TextText from the PDF itself.

The first pages · 3 of 12

Look before you download

Each page opens the PDF at that page.

Page 1
Page 1of 12
Page 2
Page 2of 12
Page 3
Page 3of 12