Manual · Allen-Bradley
AC (120V) Isolated Output Module, 16 Outputs (Cat. No. 1771-OD16 Series B) Installation Instructions
Manual12 pagesPDF 197 KB
Installation instructions for the Allen-Bradley 1771-OD16 Series B AC (120V) isolated output module with 16 outputs.
Covers · 2 models
The models it covers
Summary
What is in it
Allen-Bradley installation instructions for the 1771-OD16 Series B AC (120V) isolated output module with 16 outputs. They cover pre-installation considerations such as load and motor starter limits, leakage current and surge suppression, power supply requirements, module placement, setting the fuse-blown jumper (STD or CSI mode), keying the backplane, installing the module and field wiring arm, wiring, reading the status indicators, replacing a fuse and the module specifications.
Its parts
- To The Installer
- Preinstallation Considerations
- Power Supply Requirements
- Understand Compliance to European Union Directives
- Determining Module Placement in the I/O Chassis
- Setting the Mode of the Fuse-Blown Jumper
- Key the Backplane Connector
- Install the Module and Field Wiring Arm
- Connect the Wiring to the Module
- Interpreting the Status Indicators
- Replacing a Fuse
- Specifications
From the manual · read page by page
Key facts from this manual
Each line names its page in the PDF.
These Allen-Bradley installation instructions (publication 1771-5.21, February 1997) cover the 1771-OD16 Series B AC (120V) isolated output module with 16 outputs for 1771 I/O chassis. They explain power needs, placement and keying, the fuse-blown jumper, wiring through the 1771-WN field wiring arm, the status indicators and fuse replacement, and they list the specifications.
- Outputs
- 16 isolated AC (120V) outputs p. 12
- Voltage rating
- 74 to 138V ac, 47-63Hz p. 12
- Current rating
- 5mA-2A continuous per channel; 8A continuous per module; 20A peak surge for 100ms, repeatable every 2 seconds p. 12
- Output device
- Solid-state triac with zero voltage turn-on p. 1
- Fuses
- 3A 2AG Slo-Blo, 1 per output, Littelfuse P/N 229003; fuse kit 1771-FE holds 5 p. 12
- Wiring arm
- 1771-WN field wiring arm, screw torque 7-9 inch-pounds p. 12
- Backplane current
- 250mA maximum from the +5V dc supply p. 2
- Leakage current
- 3mA maximum at 138V ac; nominal 1.5mA p. 1
- Motor starters
- 16 size 3, 10 size 4 or 7 size 5 motor starters (1 per output) p. 1
- Wiring
- 14 gauge (2mm2) stranded maximum, 3/64 inch (2mm) insulation maximum; cable up to 1000 ft (304.8 m) p. 12
- Signal delay
- 8.3ms @ 60Hz max; 10ms @ 50Hz max (zero cross switching) p. 12
- Temperature
- Operating 0 to 60°C (32 to 140°F); storage -40 to 85°C (-40 to 185°F); 5 to 95% humidity without condensation p. 12
- Keying
- Keying bands between 22 and 24 and between 34 and 36 p. 5
- Agency marks
- The manual states CSA certified, CSA Class I, Division 2, Groups A, B, C, D certified, UL listed and CE marked, when the product or packaging is marked p. 12
What this manual walks you through
- Fitting inductive loads with surge suppressors p. 2
- Setting the fuse-blown jumper to STD or CSI mode p. 4, 5
- Keying the backplane connector p. 5
- Installing the module and the field wiring arm p. 6
- Wiring loads to the field wiring arm p. 7
- Driving a 120V ac input module from an output p. 8
- Reading the ACTIVE, FUSE and output status indicators p. 9
- Replacing a blown fuse p. 10
Good to know
- Do not put the jumper in CSI mode when the module is used in complementary mode. p. 4
- The wiring arm terminal number is not the number of the bit that controls that output. p. 7
- Do not connect output channels in series; the output devices can chatter. p. 8
- The module is not compatible with the 1771-AL local I/O adapter module. p. 2
- The fuse-blown circuit does not work when the output load current is 5mA or less. p. 9
Questions this manual answers
What fuse does the 1771-OD16 take?
A 3A 2AG slo-blow fuse, Littelfuse part number 229003, one per output. p. 10
How much current can each 1771-OD16 output carry?
Up to 2A per channel, with no more than 8A total per module. p. 1
What voltage does the 1771-OD16/B switch?
74 to 138V ac at 47-63Hz. p. 12
Which wiring arm fits the 1771-OD16?
The 1771-WN field wiring arm, shipped with the module. p. 7
When does the FUSE indicator light on the 1771-OD16?
When a fuse has cleared or been removed and that fuse's channel is turned on. It resets after the fuse is replaced and chassis power is cycled. p. 9
Contents
Chapters and sections
Each line opens the PDF at its page.
- 1771-5.21,AC (120V) Isolated Output Module, 161
- To The Installer1
- Pre-installation Considerations1
- Power Supply Requirements2
- Understand Compliance to European Union Directives2
- Determining Module Placement in the I/O Chassis3
- Setting the Mode of the Fuse-Blown Jumper4
- Key the Backplane Connector5
- Install the Module and Field Wiring Arm6
- Connect the Wiring to the Module7
- Interpreting the Status Indicators9
- Replacing a Fuse10
- Specifications12
- Back Cover12