AC (120V) Isolated Output Module, 16 Outputs (Cat. No. 1771-OD16 Series B) Installation Instructions, pages 7 to 12

Pages 7 to 12 of 12

The original document is the PDF (197 KB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

For the Allen-Bradley 1771-OD16 and Allen-Bradley 1771-OD16/B

Page 7

AC (120V) Isolated Output Module, 16 Outputs

Connect the Wiring to the Module

7

You make connections to the module through the 1771-WN field wiring arm shipped with the module. The arm pivots on the chassis to connect with the terminals on the front of the module (as shown below). The wiring arm allows the module to be removed from the chassis without disconnecting wiring. 1. Make certain all power is removed from the module before making wiring connections. 2. Swing the wiring arm up into position on the front of the module. The locking tab on the module will secure it into place. 3. Make your connections to the field wiring arm as shown below. (Use the label on the front of the wiring arm to identify your wiring.)

Connecting Wiring for the 1771-OD16/B Isolated Output Module L1 ac High

Alternate Load Location

Load

L1 - 0 L1 - 1 L1 - 2 L1 - 3 Not Used L1 - 4 L1 - 5 L1 - 6 L1 - 7 Not used L1 - 10 L1 - 11

2

L1 - 12 L1 - 13 Not used L1 - 14 L1 - 15 L1 - 16

26

L1 - 17

38

Not used

40

4 6 8 10 12 14 16 18 20 22 24

28 30 32 34 36

Output 0 Output 1 Output 2 Output 3 Not used Output 4 Output 5 Output 6 Output 7

Load

Not used Output 10 Output 11 Output 12 Output 13 Not used Output 14 Output 15 Output 16 Output 17 Not used

L2 ac Low 120V ac Supply L1

10542-I

!

ATTENTION: The field wiring arm terminal identification number is not the same as the number of the bit which controls that output.

Publication 1771-5.21 -February 1997

Page 8

8

AC (120V) Isolated Output Module, 16 Outputs

Note: You can use the shorting bar to connect the L1-0 through L1-17 high side ac power connections together if no isolation is required. You can use an output of the 1771-OD16 module to drive an input of a 120V ac input module (1771-IA, -IA2, -IAD,-ID or ID16), as shown below, to indicate status of turning on a motor starter, for example. Inputs configured with the output module are not isolated from each other. ATTENTION: Do not connect the 1771-OD16 output channels in series. Doing so can result in distortion of the output waveform causing the output devices to chatter.

!

Examples of the 1771-OD16/B Driving Input Modules AC (120V) Isolated Output Module (Cat. No. 1771-OD16) L1 ac High L1 - 0 L1 - 1 L1 - 2 L1 - 3 Not Used L1 - 4 L1 - 5 L1 - 6 L1 - 7 Not used L1 - 10 L1 - 11 L1 - 12 L1 - 13 Not used L1 - 14 L1 - 15 L1 - 16 L1 - 17 Not used

AC/DC (120V) Input Module (Cat. No. 1771-IAD)

Output 0 Output 1 Output 2 Output 3 Not used Output 4 Output 5 Output 6 Output 7 Not used Output 10 Output 11 Output 12 Output 13 Not used Output 14 Output 15 Output 16 Output 17 Not used

2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40

L1

120V ac Supply

Publication 1771-5.21 -February 1997

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20

Input 00 Input 01 Input 02 Input 03 Input 04 Input 05 Input 06 Input 07 Input 10 Input 11 Input 12 Input 13 Input 14 Input 15 Input 16 Input 17

L2 ac Low L2

AC (120V) Isolated Output Module (Cat. No. 1771-OD16) L1 ac High L1 - 0 L1 - 1 L1 - 2 L1 - 3 Not Used L1 - 4 L1 - 5 L1 - 6 L1 - 7 Not used L1 - 10 L1 - 11 L1 - 12 L1 - 13 Not used L1 - 14 L1 - 15 L1 - 16 L1 - 17 Not used

40

Output 0 Output 1 Output 2 Output 3 Not used Output 4 Output 5 Output 6 Output 7 Not used Output 10 Output 11 Output 12 Output 13 Not used Output 14 Output 15 Output 16 Output 17 Not used

120V ac L1 Supply

L2

2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38

AC (120V) Isolated Input Module (Cat. No. 1771-ID16)

2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40

10543-I

Page 9

AC (120V) Isolated Output Module, 16 Outputs

Interpreting the Status Indicators

9

The module has 18 indicators (below), consisting of 16 output status indicators, an active indicator and a fuse blown indicator. The 16 status indicators will light when an ”on” signal has been communicated between the module and the system backplane.

ACTIVE

Output State Indicators (red)

00 01 02 03 04 05 06 07

10 11 12 13 14 15 16 17

FUSE

ACTIVE Indicator (green)

Fuse Blown Indicator (red)

10544-I

The ACTIVE indicator will light when the module has started up and successfully initialized.The FUSE blown indicator will light when the fuse has cleared or been removed and the channel associated with that fuse has been turned ”on.” The fuse-blown circuit will not operate if the applied voltage to that channel is above the specified minimum ”on-state” voltage, and the output load current is less than or equal to 5mA. The FUSE blown indicator will reset after the fuse has been replaced and chassis power has been cycled.

Publication 1771-5.21 -February 1997

Page 10

10

AC (120V) Isolated Output Module, 16 Outputs

Replacing a Fuse

Each module output is individually fused. You can easily access the module fuses through the access holes on the side cover. Follow the procedure below.

!

ATTENTION: Remove power from the 1771 I/O chassis backplane and wiring arm before removing or installing an I/O module.

• Failure to remove power from the backplane could cause injury or equipment damage due to possible unexpected operation. • Failure to remove power from the backplane or wiring arm could cause module damage, degradation of performance, or injury.

If a blown fuse occurs: 1. Turn off power to the I/O chassis backplane. 2. Pivot the wiring arm away from the module and pull the module from the I/O chassis. 3. Use a small common screwdriver to reach through the front of the module and carefully pry one end of the fuse out of its holder.

2. Reach through hole in side cover and twist and pull to remove fuse.

1. Pry up on one end of the fuse to remove it from the holder.

18532

4. Reach through the access hole on the side of the module and carefully twist and pull to remove the blown fuse. Replace it with a 3A 2AG slo-blow fuse (Littelfuse part number 229003). 5. Reinstall the module in the I/O chassis. 6. Reposition the wiring arm. 7. Restart system power.

Publication 1771-5.21 -February 1997

Page 11

AC (120V) Isolated Output Module, 16 Outputs

11

CSA Hazardous Location Approval

Approbation d'utilisation dans des emplacements dangereux par la CSA

CSA certifies products for general use as well as for use in hazardous locations. Actual CSA certification is indicated by the product label as shown below, and not by statements in any user documentation.

La CSA certifie les produits d'utilisation générale aussi bien que ceux qui s'utilisent dans des emplacements dangereux. La certification CSA en vigueur est indiquée par l'étiquette du produit et non par des affirmations dans la documentation à l'usage des utilisateurs.

Example of the CSA certification product label

Exemple d'étiquette de certification d'un produit par la CSA

To comply with CSA certification for use in hazardous locations, the following information becomes a part of the product literature for CSA-certified Allen-Bradley industrial control products. • This equipment is suitable for use in Class I, Division 2, Groups A, B, C, D, or non-hazardous locations only. • The products having the appropriate CSA markings (that is, Class I Division 2, Groups A, B, C, D), are certified for use in other equipment where the suitability of combination (that is, application or use) is determined by the CSA or the local inspection office having jurisdiction.

Pour satisfaire à la certification de la CSA dans des endroits dangereux, les informations suivantes font partie intégrante de la documentation des produits industriels de contrôle Allen-Bradley certifiés par la CSA. • Cet équipement convient à l'utilisation dans des emplacements de Classe 1, Division 2, Groupes A, B, C, D, ou ne convient qu'à l'utilisation dans des endroits non dangereux. • Les produits portant le marquage approprié de la CSA (c'est à dire, Classe 1, Division 2, Groupes A, B, C, D) sont certifiés à l'utilisation pour d'autres équipements où la convenance de combinaison (application ou utilisation) est déterminée par la CSA ou le bureau local d'inspection qualifié.

Important: Due to the modular nature of a PLC control system, the product with the highest temperature rating determines the overall temperature code rating of a PLC control system in a Class I, Division 2 location. The temperature code rating is marked on the product label as shown.

Important: Par suite de la nature modulaire du système de contrôle PLC, le produit ayant le taux le plus élevé de température détermine le taux d'ensemble du code de température du système de contrôle d'un PLC dans un emplacement de Classe 1, Division 2. Le taux du code de température est indiqué sur l'étiquette du produit.

Temperature code rating

Taux du code de température Look for temperature code rating here

The following warnings apply to products having CSA certification for use in hazardous locations.

!

ATTENTION: Explosion hazard • Substitution of components may impair suitability for Class I, Division 2. • Do not replace components unless power has been switched off or the area is known to be non-hazardous. • Do not disconnect equipment unless power has been switched off or the area is known to be non-hazardous. • Do not disconnect connectors unless power has been switched off or the area is known to be non-hazardous. Secure any user-supplied connectors that mate to external circuits on an Allen-Bradley product using screws, sliding latches, threaded connectors, or other means such that any connection can withstand a 15 Newton (3.4 lb.) separating force applied for a minimum of one minute.

Le taux du code de température est indiqué ici Les avertissements suivants s'appliquent aux produits ayant la certification CSA pour leur utilisation dans des emplacements dangereux.

!

AVERTISSEMENT: Risque d'explosion • La substitution de composants peut rendre ce matériel inacceptable pour lesemplacements de Classe I, Division 2. • Couper le courant ou s'assurer quel'emplacement est désigné non dangereux avant de remplacer lescomposants. • Avant de débrancher l'équipement, couper le courant ou s'assurer que l'emplacement est désigné non dangereux. • Avant de débrancher les connecteurs, couper le courant ou s'assurer que l'emplacement est reconnu non dangereux. Attacher tous connecteurs fournis par l'utilisateur et reliés aux circuits externes d'un appareil Allen-Bradley à l 'aide de vis, loquets coulissants, connecteurs filetés ou autres moyens permettant aux connexions de résister à une force de séparation de 15 newtons (3,4 lb. - 1,5 kg) appliquée pendant au moins une minute.

Le sigle CSA est la marque déposée de l'Association des Standards pour le Canada. PLC est une marque déposée de Allen-Bradley Company, Inc. CSA logo is a registered trademark of the Canadian Standards Association PLC is a registered trademark of Allen-Bradley Company, Inc.

Publication 1771-5.21 -February 1997

Page 12

12

AC (120V) Isolated Output Module, 16 Outputs

Specifications

Outputs per Module

16 isolated

Module Location

1771-A1B thru -A4B I/O Chassis

Voltage Rating

74 to 138V ac, 47-63Hz

Current Rating (per channel)

Power Rating

5mA-2A continuous (max) 20A peak surge for 100ms; repeatable every 2 seconds 8A continuous per module (maximum) 3 Watts per output (max) @ 2A

On-state Voltage Drop (each output) Off-state Leakage Current Signal Delay Times Off to On On to Off

5.8V rms (max.) @ load current <50mA 1.5V rms (max.) @ load current >50mA 3.0mA max. @ 138V ac 8.3ms @ 60Hz max; 10ms @ 50Hz max 8.3ms @ 60Hz max; 10ms @ 50Hz max (zero cross switching)

Power Dissipation

13.25 Watts (max); 1.25 Watts (min)

Thermal Dissipation

45.2 BTU/hr (max); 4.3 BTU/hr (min)

Backplane Current

250mA maximum

Isolation Voltage

Tested at 2500V dc for 1 second per UL508 & CSA C22.2 #142

Maximum Cable Length Conductors

Wire Size Category

Environmental Conditions Operational Temperature Storage Temperature Relative Humidity Keying

1000 ft (304.8 m) 14 gauge (2mm2) stranded maximum 3/64 inch (2mm) insulation maximum 11 0o to 60oC (32o to 140oF) -40o to 85oC (-40o to 185oF) 5 to 95% (without condensation) Between 22 and 24 Between 34 and 36

Field Wiring Arm Wiring Arm Screw Torque Fuses

Catalog Number 1771-WN 7-9 inch-pounds 3A 2AG Slo-Blo fuses (1 per output), Littelfuse P/N 229003 (Optional Fuse Kit, Cat. No. 1771-FE contains 5 fuses)

Agency Certification (when product or packaging is marked)

• CSA certified • CSA Class I, Division 2, Groups A, B, C, D certified • UL listed • CE marked for all applicable directives

1 Refer to publication 1770-4.1, Programmable Controller Wiring and Grounding Guidelines

Allen-Bradley, a Rockwell Automation Business, has been helping its customers improve productivity and quality for more than 90 years. We design, manufacture and support a broad range of automation products worldwide. They include logic processors, power and motion control devices, operator interfaces, sensors and a variety of software. Rockwell is one of the world's leading technology companies.

Worldwide representation. Argentina • Australia • Austria • Bahrain • Belgium • Brazil • Bulgaria • Canada • Chile • China, PRC • Colombia • Costa Rica • Croatia • Cyprus • Czech Republic • Denmark • Ecuador • Egypt • El Salvador • Finland • France • Germany • Greece • Guatemala • Honduras • Hong Kong • Hungary • Iceland • India • Indonesia • Ireland • Israel • Italy • Jamaica • Japan • Jordan • Korea • Kuwait • Lebanon • Malaysia • Mexico • Netherlands • New Zealand • Norway • Pakistan • Peru • Philippines • Poland • Portugal • Puerto Rico • Qatar • Romania • Russia-CIS • Saudi Arabia • Singapore • Slovakia • Slovenia • South Africa, Republic • Spain • Sweden • Switzerland • Taiwan • Thailand • Turkey • United Arab Emirates • United Kingdom • United States • Uruguay • Venezuela • Yugoslavia

Allen-Bradley Headquarters, 1201 South Second Street, Milwaukee, WI 53204 USA, Tel: (1) 414 382-2000 Fax: (1) 414 382-4444 Publication 1771-5.21 - February 1997 Publication 1771-5.21 -February 1997

PN 955123-04 Copyright 1997 Allen-Bradley Company, Inc. Printed in USA