AC (120V) Isolated Output Module, 16 Outputs (Cat. No. 1771-OD16 Series B) Installation Instructions, pages 1 to 6

Pages 1 to 6 of 12

The original document is the PDF (197 KB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

For the Allen-Bradley 1771-OD16 and Allen-Bradley 1771-OD16/B

Page 1

Installation Instructions

AC (120V) Isolated Output Module, 16 Outputs Cat. No. 1771-OD16 Series B To The Installer

This document provides information on:

• • • • • •

Pre-installation Considerations important pre-installation considerations power supply requirements installing the module using the module indicators for troubleshooting replacing a fuse module specifications

An output from this module can drive an Allen-Bradley Size 5 motor starter, provided its supply voltage does not drop below 92V ac. The maximum load current the module can deliver is 2A per channel, not to exceed 8A total per module. Your module’s outputs can drive the following motor starter combinations:

• 16 size 3 motor starters (1 per output) • 10 size 4 motor starters (1 per output) • 7 size 5 motor starters (1 per output) The switching device in the output circuit is a solid-state triac. There is a small leakage current in the off state due to both triac and capacitive characteristics. The maximum leakage current per output is 3mA at 138V ac. Nominal leakage current is 1.5mA. The on-state voltage drop across the output terminals will not exceed 1.5V ac at 2A. The 1771-OD16/B module is designed for a 5mA minimum current on each output circuit. The total continuous current the module supports is 8A (2A maximum per channel).

!

ATTENTION: If the 8A maximum per module (2A per module) rating is exceeded, the module overheats and damage may occur.

The module uses zero voltage turn-on to reduce the electromagnetic interference and high inrush currents during initial turn-on. This zero crossing feature switches line voltage only when it is close to zero. The typical value for zero crossing voltage is +15V ac.

Publication 1771-5.21 -February 1997

Page 2

2

AC (120V) Isolated Output Module, 16 Outputs

This module can be used in all 1771 I/O chassis except the 1771-A1, -A2 or -A4 chassis. It may also be used in a 1771-AM1 or 1771-AM2 chassis.This module is not compatible with the 1771-AL local I/O adapter module.

Suppression Surge suppression circuitry is provided for the output triacs in this module. To suppress high-voltage transients from the AC line, a metal-oxide varistor (MOV) is provided between each set of terminals on the module. In each output circuit an RC network limits the magnitude of voltage transients that may occur when a device is wired in parallel or series with hard contacts. Loads with inductive characteristics may require additional suppression devices. The impedance characteristic of the load is the most important factor in selecting a suppression device; thus no single suppression device can be recommended for every possible load. Acceptable suppression devices for typical loads are shown in the table below. Allen-Bradley Equipment

Suppressor Catalog Number

Motor Starter Bulletin 509

599-K041

Motor Starter Bulletin 709

1401-N101

Relay Bulletin 700 Type N or P

700N5/700N9

Miscellaneous

700-N242

1 For starters with 120V AC coils 2 Bulletin 700-N24 is a universal surge suppressor. You can use it on electromagnetic devices with the limitation of

35 sealed VA, 150V.

Power Supply Requirements

Understand Compliance to European Union Directives

Publication 1771-5.21 -February 1997

The isolated output module is powered by the power supply connected to the I/O chassis backplane. The module requires a maximum current of 250mA from the +5V dc output of this supply. Total the current requirements of this module with the other modules in the I/O chassis to avoid overloading the supply or the I/O chassis backplane.

If this product has the CE mark it is approved for installation within the European Union and EEA regions. It has been designed and tested to meet the following directives.

Page 3

AC (120V) Isolated Output Module, 16 Outputs

3

EMC Directive This product is tested to meet Council Directive 89/336/EEC Electromagnetic Compatibility (EMC) and the following standards, in whole or in part, documented in a technical construction file: • EN 50081-2EMC – Generic Emission Standard, Part 2 – Industrial Environment • EN 50082-2EMC – Generic Immunity Standard, Part 2 – Industrial Environment This product is intended for use in an industrial environment.

Low Voltage Directive This product is tested to meet Council Directive 73/23/EEC Low Voltage, by applying the safety requirements of EN 61131–2 Programmable Controllers, Part 2 – Equipment Requirements and Tests. For specific information required by EN 61131-2, see the appropriate sections in this publication, as well as these Allen-Bradley publications: • Industrial Automation Wiring and Grounding Guidelines For Noise Immunity, publication 1770-4.1 • Guidelines for Handling Lithium Batteries, publication AG-5.4 • Automation Systems Catalog, publication B111

Determining Module Placement in the I/O Chassis

You can place your module in any I/O module slot of the I/O chassis except for the left-most slot. The left-most slot is reserved for programmable controller processors or adapter modules. Group your modules to minimize adverse effects from radiated electrical noise and/or heat. We recommend the following:

!

ATTENTION: Remove power from the 1771 I/O chassis backplane and wiring arm before removing or installing an I/O module.

• Failure to remove power from the backplane or wiring arm could cause module damage, degradation of performance, or injury. • Failure to remove power from the backplane could cause injury or equipment damage due to possible unexpected operation.

• Group analog input and low voltage dc modules away from ac modules or high voltage dc modules to minimize electrical noise interference. • Place analog input modules and other I/O modules sensitive to heat away from slot power supplies to minimize adverse heat effects.

Publication 1771-5.21 -February 1997

Page 4

4

AC (120V) Isolated Output Module, 16 Outputs

Initial Handling Procedures

!

ATTENTION: Remove power from the 1771 I/O chassis backplane and wiring arm before removing or installing an I/O module.

• Failure to remove power from the backplane or wiring arm could cause module damage, degradation of performance, or injury. • Failure to remove power from the backplane could cause injury or equipment damage due to possible unexpected operation.

• Touch a grounded object to rid yourself of charge before handling the module. • Do not touch the backplane connector or connector pins. • When you configure or replace internal components, do not touch other circuit components inside the module. If available, use a static-safe work station. • When not in use, keep the module in its static-shield bag.

Setting the Mode of the Fuse-Blown Jumper

The fuse-blown jumper has two modes:

• the preset, standard (STD) mode – displays the fuse status on the red fuse-blown status indicator • the customer side indication (CSI) mode – displays the fuse status in the input image table and on the red fuse-blown status indicator. This mode configures the module as a 16 point output module that utilizes both the output and input image data tables of your controller. When a fuse blows, all 16 bits in the associated input image table will turn on (1). For example, if you install the module in a PLC-5 system and address the module as O:012, then the fuse status bits are in I:012.

To monitor the status of the module fuses, make certain that your user program monitors the module’s input image table for ‘‘on” bits.

!

Publication 1771-5.21 -February 1997

ATTENTION: Do not put the module jumper in CSI mode when you use this module in a complementary mode. Your system will not operate properly.

Page 5

AC (120V) Isolated Output Module, 16 Outputs

5

To change the fuse blown jumper to the CSI mode: 1. Locate the fuse-blown jumper at the top-right edge of the module circuit board, as shown in the following figure. Top-right edge of circuit board

STD

CSI

Fuse Blown Jumper (shown in preset STD position)

12636-I

2. Use your finger to slide the jumper off the STD position (the middle post and the left post). 3. Carefully reposition the jumper by sliding it onto the CSI position (the middle post and the right post).

Key the Backplane Connector

!

Place your module in any slot in the chassis except the leftmost slot which is reserved for processors or adapters.

!

ATTENTION: A module inserted into a wrong slot could be damaged by improper voltages connected through the wiring arm. Use keying bands to prevent damage to the module.

Position the keying bands in the backplane connectors to correspond to the key slots on the module. Place the keying bands: between 22 and 24 between 34 and 36

ATTENTION: Observe the following precautions when inserting or removing keys:

• insert or remove keys with your fingers • make sure that key placement is correct Incorrect keying or the use of a tool can result in damage to the backplane connector and possible system faults.

I/O chassis

Upper Connector You can change the position of these bands if subsequent system design and rewiring makes insertion of a different type of module necessary.

11022-I

Publication 1771-5.21 -February 1997

Page 6

6

AC (120V) Isolated Output Module, 16 Outputs

Install the Module and Field Wiring Arm

!

ATTENTION: Remove power from the 1771 I/O chassis backplane and field wiring arm before removing or installing an I/O module.

• Failure to remove power from the backplane or wiring arm could cause module damage, degradation of performance, or injury. • Failure to remove power from the backplane could cause injury or equipment damage due to possible unexpected operation.

1

1771-A1B, -A2B, -A3B, -A3B1, -A4B I/O chassis

1771-A1B, -A2B, -A3B1, -A4B Series B I/O chassis locking tab locking bar locking bar pin card guides card guides module

Snap the chassis latch over the top of the module to secure it.

2 module

Swing the chassis locking bar down into place to secure the modules. Make sure the locking pins engage.

19809 wiring arm

Attach the wiring arm (1771-WN) to the horizontal bar at the bottom of the I/O chassis. The wiring arm pivots upward and connects with the module so you can install or remove the module without disconnecting the wires.

1771-WN remove horizontal bar

Publication 1771-5.21 -February 1997 install

17643