Page 51

48

1771 Digital I/O DC Input and Output Modules

DC Output Module (Cat. No. 1771-OQ Series B)

Status Indicators

Specifications (Cat. No. 1771-OQ/B) Outputs per Module

8 (4 groups of 2, each group sharing a common dc supply)

Module Location

1771 I/O chassis

Output Voltage Range

24V dc (+10%,-15%) Peaks of modulated ripple must be between 17-34V dc

Maximum Output Current

2.25A per output 2.25A per group 9A per module

Maximum Surge Current

4.0A for 10ms per output

Maximum On-state Voltage Drop

2V dc @ 2.25A 1.0mA per output @ 34V dc, 25oC

Maximum Off-state Leakage Current

Status Indicators

4.5W per output

Thermal Dissipation

65.1 BTU/hr (max.), 4.1 BTU/hr (min.)

Backplane Current

225mA

Isolation Voltage

1500V ac rms

Environmental Conditions Operational Temperature Storage Temperature Relative Humidity

0o to 60oC (32o to 140oF) -40o to 85oC (-40o to 185oF) 5 to 95% (without condensation) 14 gauge (2mm2) stranded maximum 3/64 inch (1.2mm) insulation maximum 11

Conductors Wire Size Category Fuses

2.5A, 3AG (1 per output pair)

Keying

Between 2 and 4 Between 10 and 12

Field Wiring Arm

Catalog Number 1771-WF

Wiring Arm Screw Torque

7-9 inch-pounds • CSA certified • CSA Class I, Division 2 Groups A, B, C, D certified • UL listed • CE marked for all applicable directives

Installation Instructions

1771-2.92

1 You use this conductor-category for planning conductor routing as described in the system-level installation manual.

12260-I

Sample Connection Diagram Driving a 1771-IQ Module with a 1771-OQ Module DC Output Module Cat. No. 1771-OQ

DC Input Module Cat. No. 1771-IQ +24V dc

Not used +24V dc Output 0 Output 1 dc Common dc Common Output 2 Output 3 +24V dc +24V dc Output 4 Output 5 dc Common dc Common Output 6 Output 7 +24V dc Not used

1 2

19.1 Watts (max.), 1.1 Watts (min.)

3 4 5 6 7 8

10ms on or off

Power Dissipation

9 10 11 12

Output Signal Delay

13 14 15 16 17 18

Maximum Power Rating

Agency Certification (when product or packaging is marked)

Not used Output 0 Output 1 Output 2 Output 3 Output 4 Output 5 Output 6 Output 7

A dc+

O

Input 0

1

Input 1

2

Input 2

3

Input 3

4

Input 4

5

Input 5

6

Input 6

7

Input 7

8 dc Common dc Common (Actual wiring runs in this direction.)

Publication 1771-2.180 - July 1996

12261-I

Page 52

1771 Digital I/O DC Input and Output Modules

49

DC Input Module (Cat. No. 1771-OQ16 Series B)

Simplified Schematic

Fuse-blown Indication Circuitry Opto Isolation

3.8k

Input LED Indication dc Input (+)

3A System Circuitry

Opto Isolation

.0047µF

39V

10.0k dc Output (-) 12262-I

Application Notes

Connection Diagram

Device Compatibility. This module must be used in a series B I/O chassis. The 1771-OQ16 is not compatible with the 1771-AL local I/O adapter. This module is designed to operate with dc relays and other dc output devices Connection to Input Modules. You can use an output of the 1771-OQ16 module to drive an input of a dc input module (cat. no. 1771-IQ16) to indicate status of turning on a motor starter, for example. Status Indicators. The module has 18 indicators, consisting of 16 output status indicators, a fuse-blown indicator and an active indicator. The 16 status indicators are provided for system logic side indication of individual outputs. The active indicator lights when the module has successfully started up and initialized.The fuse-blown indicator lights when a fuse has cleared or been removed, the channel associated with that fuse has been turned the applied voltage to that channel is above the specified minimum voltage, and the load is less than or equal to the maximum specified for this module. The fuse-blown indicator will reset after the fuse has been replaced and chassis power has been cycled.

Alternate Load Location

Load

Output 0 Output 1 Output 2 Output 3 Not used Output 4 Output 5 Output 6 Output 7 Not used Output 10 Output 11 Output 12 Output 13 Not used Output 14 Output 15 Output 16 Output 17 Not used

+dc - 0 +dc - 1 +dc - 2 +dc - 3 Not Used +dc - 4 +dc - 5 +dc - 6 +dc - 7 Not used +dc - 10 +dc - 11 +dc - 12 +dc - 13 Not used +dc - 14 +dc - 15 +dc - 16 +dc - 17 Not used

Load

(Actual wiring runs in this direction.) dc High +

24V dc Power Supply dc Return 10565-I

Publication 1771-2.180 - July 1996

Page 53

50

1771 Digital I/O DC Input and Output Modules

DC Output Module (Cat. No. 1771-OQ16 Series B)

Status Indicators

Specifications (Cat. No. 1771-OQ16/B) Outputs per Module

16

Module Location

Series B 1771 I/O Chassis

Output Voltage Range

10 to 32V dc

Minimum Output Current

5mA

Maximum Output Current

2.0A per output; 32.0A per module

Maximum On-state Voltage Drop

0.34V dc @ 2A

Maximum Off-state Leakage Current

0.5mA per output @ 32V dc, 25oC

Maximum Surge Current Power Rating

4A for 10ms per output, repeatable every 2 sec.

Output State Indicators (red)

0.68 Watts per output (max) @ 2A

Output Signal Delay

Turn On: 100usec (max); Turn Off: 300usec (max)

Power Dissipation

13.0 Watts (max); 2.0 Watts (min)

Thermal Dissipation

44.3 BTU/hr (max); 6.8 BTU/hr (min)

Backplane Current

400mA maximum

Isolation Voltage

1500V channel-to-channel 1500V channel to backplane

Maximum Cable Length

1000 ft (304.8 m)

Conductors Wire Size

14 gauge (2mm2) stranded maximum2 3/64 inch (1.2mm) insulation maximum 11

Category Environmental Conditions Operational Temperature Storage Temperature Relative Humidity

0o to 60oC (32o to 140oF) -40o to 85oC (-40o to 185oF)

5 to 95% (without condensation)

Fuses

3A 2AG Fast Acting fuses (1 per output) Littelfuse P/N 225003

Keying

Between 22 and 24 Between 32 and 34

Field Wiring Arm

Catalog Number 1771-WN

Wiring Arm Screw Torque

7-9 inch-pounds

Agency Certification (when product or packaging is marked)

• CSA certified • CSA Class I, Division 2 Groups A, B, C, D certified • UL listed • CE marked for all applicable directives

Installation Instructions

1771-2.192

1You use this conductor-category information for planning conductor routing as described in the system-level installation manual. 2 14 gauge wire connected to all terminals may not allow the cover on the field wiring arm to close. A smaller gauge wire may be used.

Fuse Blown Indicator (red) 10567-I

Sample Connection Diagram Driving a 1771-IQ16 Module with a 1771-OQ16 Module DC (24V) Isolated Output Module Cat. No. 1771-OQ16 dc High +dc - 0 +dc - 1 +dc - 2 +dc - 3 Not Used +dc - 4 +dc - 5 +dc - 6 +dc - 7 Not used +dc - 10 +dc - 11 +dc - 12 +dc - 13 Not used +dc - 14 +dc - 15 +dc - 16 +dc - 17 Not used

+

Publication 1771-2.180 - July 1996

ACTIVE Indicator (green)

ACTIVE 00 10 01 11 02 12 03 13 04 14 05 15 06 16 07 17 FUSE

2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40

10-32V dc Power Supply

Output 0 Output 1 Output 2 Output 3 Not used Output 4 Output 5 Output 6 Output 7 Not used Output 10 Output 11 Output 12 Output 13 Not used Output 14 Output 15 Output 16 Output 17 Not used

DC (24V) Isolated Input Module Cat. No. 1771-IQ16

2 4 6 dc Return

8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40

Input 0 Input 1 Input 2 Input 3 Not used Input 4 Input 5 Input 6 Input 7 Not used Input 10 Input 11 Input 12 Input 13 Not used Input 14 Input 15 Input 16 Input 17 Not used

(Actual wiring runs in this direction.)

-

10566-I

Page 54

1771 Digital I/O DC Input and Output Modules

51

DC Output Module (Cat. No. 1771-OVN Series B)

Simplified Schematic

Fuse Blown Indication LED (logic) 1N4007

15k

+dc Common (1 of 4)

Output Indication LED (logic)

System Circuitry

Opto Isolation

1N4007

470

1N4007

Output

Opto Isolation dc Supply Common (1 of 4)

Fuse 4 Amp

18670

Application Notes Device Compatibility. The 1771-OVN dc output module has sinking outputs which can interface with sourcing inputs. You must use this module in a series B 1771 I/O chassis. Do not place this module in the same I/O chassis as the 1771-IX thermocouple module. You can use this module in the same chassis as the 1771-IXE thermocouple module as long as you use 1/2-slot addressing. Connection to Input Modules. A 1771-OVN module can directly drive terminals on a 1771-IVN input module. Use the same dc supply to power both modules to ensure that ground is at the same potential. Status Indicators. The module has 32 status indicators. These represent the control status of the outputs. These are provided for system logic side indication of individual outputs. An additional indicator is provided to indicate a blown fuse condition.

Connection Diagram Output 0 Output 2 Output 4 Output 6 Common 0 Output 10 Output 12 Output 14 Output 16 Common 1 Output 0 Output 2 Output 4 Output 6 Common 2 Output 10 Output 12 Output 14 Output 16 Common 3

2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40

Note: Terminals on the left are even numbered (2 thru 40) , and terminals on the right are odd numbered (1 thru 39).

+ dc Output 1 Output 3 Output 5 Output 7 + dc Output 11 Output 13 Output 15 Output 17 + dc Output 1 Output 3 Output 5 Output 7 + dc Output 11 Output 13 Output 15 Output 17 dc Output Device + + dc Supply -

(See applicable codes and laws.) (Actual wiring runs in this direction.)

12262-I

Publication 1771-2.180 - July 1996

Page 55

52

1771 Digital I/O DC Input and Output Modules

DC Output Module (Cat. No. 1771-OVN Series B)

Specifications (Cat. No. 1771-OVN/B) Outputs per module

32 (4 groups of 8)

Module Location

Series B 1771 I/O Chassis

Output Voltage Range

10 to 30V dc

Maximum Output Current

0.5A per output 2A per group 8A per module

Maximum Surge Current

2A per output for 10ms; repeatable every 2sec. 5A per output group for 10ms.; repeatable every 2sec. 20A per module for 10ms.; repeatable every 2sec.

00 10 00 10 01 11 01 11 02 12 02 12 03 13 03 13 04 14 04 14 05 15 05 15 06 16 06 16 07 17 07 17 FUSE

1.0mA per output @ 30V dc, 55oC

Maximum Off-state Leakage Current Maximum On-state Voltage Drop

Status Indicators (red)

Fuse Blown Indicator

1.5V dc at 2A

Maximum Power Rating

3W per output

Output Signal Delay

On to off propagation delay 2.0msec Off to on propagation delay 0.1msec

Power Dissipation

13.7W (max); 1.7W (min)

Thermal Dissipation

46.7 BTU/hr (max); 5.7 BTU/hr (min)

Backplane Current

330mA @ 5V dc maximum

Isolation Voltage

1500V ac rms

Environmental Conditions Operational Temperature Storage Temperature Relative Humidity

0o to 60oC (32o to 140oF) -40o to 85oC (-40o to 185oF) 5 to 95% (without condensation) 14 gauge (2mm2) stranded (max)2 3/64 inch (1.2mm) insulation (max) 11

Conductors Wire Size Category Fuses

Four 4.0A, 250V normal blow fuses (1 per group)

Keying

Between 14 and 16 Between 32 and 34

Field Wiring Arm

1771-WN

Wiring Arm Screw Torque Agency Certification (when product or packaging is marked)

Status Indicators

7-9 inch-pounds • CSA certified • CSA Class I, Division 2 Groups A, B, C, D certified • UL listed • CE marked for all applicable directives

Installation Instructions

1771-5.36

1You use this conductor-category information for planning conductor routing as described in the system-level installation manual. 2 14 gauge wire connected to all terminals may not allow the cover on the field wiring arm to close. A smaller gauge wire may be used.

12263-I

Sample Connection Diagram Driving a 1771-IVN Module with a 1771-OVN Module DC Output Module Cat. No. 1771-OVN

2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40

DC Input Module Cat. No. 1771-IVN +dc 10-30V dc dc Common

2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40

(Actual wiring runs in this direction.) 12264-I

Publication 1771-2.180 - July 1996

Page 56

Notes

53

Notes

Publication 1771-2.180 - July 1996

Page 57

54

Notes

Notes

Publication 1771-2.180 - July 1996

Page 58

Support Services

Support Services

55

At Allen-Bradley, customer service means experienced representatives at Customer Support Centers in key cities throughout the world for sales service and support. Our value-added services include:

Technical Support • • • •

SupportPlus programs telephone support and 24-hour emergency hotline software and documentation updates technical subscription services

Engineering and Field Services • • • • application engineering assistance integration and start-up assistance field service maintenance support

Technical Training • • • • lecture and lab courses self-paced computer and video-based training job aids and workstations training needs analysis

Repair and Exchange Services • • • • your only “authorized” source current revisions and enhancements worldwide exchange inventory local support

Publication 1771-2.180 - July 1996

Page 59

Allen-Bradley, a Rockwell Automation Business, has been helping its customers improve productivity and quality for more than 90 years. We design, manufacture and support a broad range of automation products worldwide. They include logic processors, power and motion control devices, operator interfaces, sensors and a variety of software. Rockwell is one of the world's leading technology companies.

Worldwide representation. Argentina • Australia • Austria • Bahrain • Belgium • Brazil • Bulgaria • Canada • Chile • China, PRC • Colombia • Costa Rica • Croatia • Cyprus • Czech Republic • Denmark • Ecuador • Egypt • El Salvador • Finland • France • Germany • Greece • Guatemala • Honduras • Hong Kong • Hungary • Iceland • India • Indonesia • Ireland • Israel • Italy • Jamaica • Japan • Jordan • Korea • Kuwait • Lebanon • Malaysia • Mexico • Netherlands • New Zealand • Norway • Pakistan • Peru • Philippines • Poland • Portugal • Puerto Rico • Qatar • Romania • Russia-CIS • Saudi Arabia • Singapore • Slovakia • Slovenia • South Africa, Republic • Spain • Sweden • Switzerland • Taiwan • Thailand • Turkey • United Arab Emirates • United Kingdom • United States • Uruguay • Venezuela • Yugoslavia

Allen-Bradley Headquarters, 1201 South Second Street, Milwaukee, WI 53204 USA, Tel: (1) 414 382-2000 Fax: (1) 414 382-4444

Publication 1771-2.180 - July 1996 Supersedes publication 1771-2.180 - July 1992

Copyright 1995 Allen-Bradley Company, Inc. Printed in USA