Manual · Allen-Bradley
Installation Instructions: DC (10-30V) Input Module, Cat. No. 1771-IBD Series B
Manual8 pagesPDF 124 KB
Installation instructions for the Allen-Bradley 1771-IBD Series B DC (10-30V) 16-input module, with wiring, filter setting and specifications.
Covers · 1 model
The models it covers
Summary
What is in it
Allen-Bradley installation instructions for the 1771-IBD Series B DC (10-30V) input module for 1771 I/O chassis. It covers handling to prevent electrostatic discharge, preinstallation considerations, EU directive compliance, power requirements, setting the 1 ms or 6 ms off-delay filter, keying the backplane connector, installing the module and 1771-WH field wiring arm, wiring 2-wire and 3-wire devices, status indicators, troubleshooting, CSA hazardous location notes and specifications.
Its parts
- Prevent Electrostatic Discharge
- Pre-installation Considerations
- Understand Compliance to European Union Directives
- Power Requirements
- Set the Filter Off Delay
- Key the Backplane Connector
- Install the Module and Field Wiring Arm
- Connect Wiring to the Field Wiring Arm
- Interpreting the Status Indicators
- Troubleshooting
- Specifications
From the manual · read page by page
Key facts from this manual
Each line names its page in the PDF.
Installation instructions (publication 1771-5.53, April 1999) for the Allen-Bradley 1771-IBD Series B DC (10-30V) input module, a 16-input module for the 1771 I/O chassis. They walk through handling, backplane power budgeting, the off-delay filter jumper, keying, installing the module and its 1771-WH field wiring arm, and wiring input devices, then give the status indicators, a troubleshooting table and the specifications.
- Module type
- 16-input DC (10-30V) input module, cat. no. 1771-IBD Series B p. 1, 8
- Input voltage
- 10 to 30V dc; on-state at 10V dc minimum, off-state at 5V dc maximum p. 8
- Compatible chassis
- All 1771 I/O chassis except 1771-A1, -A2 and -A4; any slot but the leftmost p. 2, 3
- Backplane current
- 130mA at 5V dc from the chassis power supply p. 3, 8
- Field wiring arm
- Cat. No. 1771-WH, shipped with the module; screw torque 7-9 inch-pounds p. 4, 5, 8
- Off-delay filter
- Jumper-selectable 1ms or 6ms, preset to 1ms; on-delay 1ms p. 2, 3, 8
- Terminals
- Inputs on terminals 00 to 17; terminal E to dc common; A to D unused p. 5
- Input current
- 4.5mA at 10V dc, 15mA at 30V dc; input impedance 2.2K ohms maximum p. 8
- Direct drive from outputs
- Can be driven directly from 1771-OBN, 1771-OBD, 1771-OB, 1771-OQ and 1771-OQ16 output modules p. 6
- Indicators
- One green module active indicator and 16 red input status indicators p. 6
- Keying
- Keying bands between 10 and 12 and between 16 and 18 p. 3, 8
- Wire size
- 14 gauge (2mm2) stranded maximum, 3/64 inch (1.2mm) insulation maximum p. 5, 8
- Temperature
- 0 to 60 °C (32 to 140 °F) operating, -40 to 85 °C storage, 5 to 95% humidity non-condensing p. 8
- Power dissipation
- 7.3 W maximum, 1.0 W minimum (24.7 BTU/hr maximum) p. 8
What this manual walks you through
- Handling the module without electrostatic damage p. 1
- Calculating the chassis backplane power budget p. 3
- Changing the off-delay filter from 1ms to 6ms p. 3
- Keying the backplane connector p. 3
- Installing the module and the field wiring arm p. 4
- Wiring two-wire and three-wire input devices p. 5, 6
- Reading the status indicators and troubleshooting faults p. 6
- The manual states its CSA hazardous location conditions and warnings p. 7
Good to know
- Reverse polarity or applying ac voltage could damage the module. p. 5
- With 2-slot addressing, no other input module or single card block transfer module may share the module group; any discrete output module may. p. 2
- Remove power from the chassis backplane and the wiring arm before installing or removing the module. p. 4
- When driving the inputs directly from a 1771 dc output module, power both modules from the same dc source. p. 6
- The module's plastic cover belongs only to assembly numbers 960364-05 and 961344-01 and must not be fitted to any other module. p. 2
Questions this manual answers
Which chassis does the 1771-IBD Series B fit?
Any 1771 I/O chassis except the 1771-A1, -A2 and -A4, in any slot except the leftmost, which is kept for processors or adapters. p. 3, 8
How do I set the 1771-IBD filter time to 6 ms?
Turn off chassis power, find the jumper on the top-left edge of the board, and slide it from the middle and right posts onto the middle and left posts. p. 3
How much backplane current does the 1771-IBD draw?
130mA from the chassis power supply; add this to the other modules when sizing the supply. p. 3
How do I wire a three-wire proximity switch to a 1771-IBD?
Wire it to operate in current source mode: its output to an input terminal 00 to 17, its supply to +dc, and terminal E to dc common. p. 5
The green light is on but an input light stays off. What is wrong?
Either the input device is not working or the module's input circuit is faulty. Check the input devices first; if they are fine, replace the module. p. 6
Contents
Chapters and sections
Each line opens the PDF at its page.
- 1771-5.53, DC (10-30V) Input Module, Installation Instructions1
- Prevent Electrostatic Discharge1
- Pre-installation Considerations2
- Understand Compliance to European Union Directives2
- Power Requirements3
- Set the Filter Off Delay3
- Key the Backplane Connector3
- Install the Module and Field Wiring Arm4
- Connect Wiring to the Field Wiring Arm5
- Interpreting the Status Indicators6
- Troubleshooting6
- Specifications8
- Back Cover8
The whole text · 1 part