Page 1

Installation Instructions

Cat. No. 1771-ID16 Series B

Use this document as a guide when installing the ac Isolated Input module.

-

%$

%$

$ *

*

, (

, ( *%

%$)

%$)

-

This module must be used in a series B or later 1771 I/O chassis. The 1771-ID16 is not compatible with the 1771-AL local I/O adapter. This module contains customer-selectable input filtering to limit the effects of voltage transients caused by contact bounce and/or radiated electrical noise. The delay due to filtering is 9.0 or 18.0ms for turning ac inputs on to off, and 0.57ms for turning ac inputs off to on: 9.0ms for turning dc inputs on to off, and 0.57ms for turning dc inputs off to on. The filter time is factory set to 9.0ms. The module is designed to operate with limit switches, float switches, selector switches, and pushbutton switches.

%$

Page 2

2 ac/dc (120V) Isolated Input Module

-

Because of the variety of uses for the products described in this publication, those responsible for the application and use of these products must satisfy themselves that all necessary steps have been taken to assure that each application and use meets all performance and safety requirements, including any applicable laws, regulations, codes and standards. In no event will Rockwell Automation be responsible or liable for indirect or consequential damage resulting from the use or application of these products. Any illustrations, charts, sample programs, and layout examples shown in this publication are intended solely for purposes of example. Since there are many variables and requirements associated with any particular installation, Rockwell Automation does not assume responsibility or liability (to include intellectual property liability) for actual use based upon the examples shown in this publication. Allen–Bradley publication SGI–1.1, Safety Guidelines for Application, Installation, and Maintenance of Solid–State Control (available from your local Rockwell Automation office), describes some important differences between solid–state equipment and electromechanical devices that should be taken into consideration when applying products such as those described in this publication. Reproduction of the contents of this copyrighted publication, in whole or part, without written permission of Rockwell Automation, is prohibited. Throughout this publication, notes may be used to make you aware of safety considerations. The following annotations and their accompanying statements help you to identify a potential hazard, avoid a potential hazard, and recognize the consequences of a potential hazard. WARNING

! ATTENTION

!

Identifies information about practices or circumstances that can cause an explosion in a hazardous environment, which may lead to personal injury or death, property damage, or economic loss.

Identifies information about practices or circumstances that may lead to personal injury or death, property damage, or economic loss.

Page 3

ac/dc (120V) Isolated Input Module

3

Identifies information that is critical for IMPORTANT successful application and understanding of the product.

ATTENTION

!

- -

This equipment is intended for use in a Pollution Degree 2 industrial environment, in overvoltage Category II applications (as defined in IEC publication 60664–1), at altitudes up to 2000 meters without derating. This equipment is considered Group 1, Class A industrial equipment according to IEC/CISPR Publication 11. Without appropriate precautions, there may be potential difficulties ensuring electromagnetic compatibility in other environments due to conducted as well as radiated disturbance. This equipment is supplied as “open type” equipment. It must be mounted within an enclosure that is suitably designed for those specific environmental conditions that will be present, and appropriately designed to prevent personal injury resulting from accessibility to live parts. The interior of the enclosure must be accessible only by the use of a tool. Subsequent sections of this publication may contain additional information regarding specific enclosure type ratings that are required to comply with certain product safety certifications. See NEMA Standards publication 250 and IEC publication 60529, as applicable, for explanations of the degrees of protection provided by different types of enclosures. Also, see the appropriate sections in this publication, as well as the Allen–Bradley publication 1770–4.1, (“Industrial Automation Wiring and Grounding Guidelines”), for additional installation requirements pertaining to this equipment.

Page 4

4 ac/dc (120V) Isolated Input Module

Initial Handling

The isolated input module is shipped in a static-shielded packaging to guard against electrostatic discharge damage. Observe the following precautions when handling the module. ATTENTION

!

Calculate Power Requirements

Preventing Electrostatic Discharge This equipment is sensitive to electrostatic discharge, which can cause internal damage and affect normal operation. Follow these guidelines when you handle this equipment: • Touch a grounded object to discharge potential static. • Wear an approved grounding wriststrap. • Do not touch connectors or pins on component boards. • Do not touch circuit components inside the equipment. • If available, use a static–safe workstation. • When not in use, keep modules in appropriate static–safe packaging.

Your module receives its power through the 1771 I/O chassis backplane from the chassis power supply. The module requires 75mA from the output of this supply. Add this to the requirements of all other modules in the I/O chassis to prevent overloading the chassis backplane and/or backplane power supply.

Set the Filter Time

The input module has 2 customer-selectable input filter time jumpers. Jumper JPR 1 sets the input filter time for inputs 00 through 07, and jumper JPR 2 sets the input filter time for inputs 10 through 17. These filter times apply when the input is cycling from ON to OFF. The OFF to ON filter time is fixed at 0.57ms. Refer to Table A for filter times and jumper settings. Half cycle dropout protection is dependent upon IMPORTANT the position of the jumpers. With the jumpers at the 9.0ms position (Fast), half cycle protection may not be guaranteed. If half cycle dropout protection is required, position the jumpers in the 18.0ms position (Norm). Maximum and minimum filter times are shown in Table A.

Page 5

ac/dc (120V) Isolated Input Module

5

To set the filtering time, proceed as follows: 1. Remove the side covers from the module circuit board by removing the four screws securing the covers to the module and remove the circuit board. 2. Position the jumpers as required to provide the filter time you require (see below). Use your fingers to pull the jumper up and position over the 2 pins corresponding to your selection (Fast or Norm). Setting the Filter Time Jumpers

Jumper Position Fast (factory default)

9.0 (ac/dc)

Norm

18.0 (ac only)

FAST

E2 FAST

NORM

CH0-7 CH10-17

NORM E1

Time Constant (ms)

Filter Time Jumpers

E1 = Jumper for inputs 00 through 07 E2 = Jumper for inputs 10 through 17

10557-I

3. Reinstall the covers on the module circuit board and secure with 4 screws. Table A Minimum and Maximum Filter Times Input Voltage

Filter Time (msec)

Off to On (ms) Minimum Maximum ac

9.0

0.5

7.0

2.0

7.0

33

20 ac

18.0

0.5

8.1

2.0

14.0

42

29 dc

9.0

0.7

2.2

1.3

8.3

25

13

Typical

On to Off (ms) Minimum Maximum Typical

Publication 1771-IN070B-EN-P - August 2002

Page 6

6 ac/dc (120V) Isolated Input Module

Key the Backplane Connector

- - &! &! ! - 22 24 26 28

Place your module in any slot in the chassis except the leftmost slot which is reserved for processors or adapters. ATTENTION Observe the following precautions when inserting or removing keys:

!

• insert or remove keys with your fingers • make sure that key placement is correct Incorrect keying or the use of a tool can result in damage to the backplane connector and possible system faults.

Install the Module and Field Wiring Arm

ATTENTION

!

! - & &

Remove power from the 1771 I/O chassis backplane before you install the module. Failure to remove power from the backplane could cause:

• module damage • degradation of performance • injury or equipment damage due to possible unexpected operation

WARNING

!

When you insert or remove the module with field power applied, or connect or disconnect the field wiring arm with field side power applied, an electrical arc can occur. This could cause an explosion in hazardous location installations.Be sure that power is removed or the area is nonhazardous before proceeding.

Page 7

ac/dc (120V) Isolated Input Module

1771-A1B, ĆA2B, ĆA3B, ĆA3B1, ĆA4B I/O chassis

7

1771-A1B, ĆA2B, ĆA3B1, ĆA4B Series B I/O chassis locking tab locking bar locking bar pin card guides card guides

Module

Snap the chassis latch over the top of the module to secure it.

Module

Swing the chassis locking bar down into place to secure the modules. Make sure the locking pins engage. 19809 wiring arm

Attach the wiring arm (1771-WN) to the horizontal bar at the bottom of the I/O chassis. The wiring arm pivots upward and connects with the module so you can install or remove the module without disconnecting the wires.

1771-WN remove horizontal bar

17643

The 1771–ID16/B module is a modular component of the 1771 I/O system requiring a properly installed system chassis. Refer to publication 1771–IN075 for detailed information on acceptable chassis, proper installation and grounding requirements. Limit the maximum adjacent slot power dissipation to 10W maximum.

Publication 1771-IN070B-EN-P - August 2002

Page 8

8 ac/dc (120V) Isolated Input Module

Connections to the input module are made to the 40 terminal field wiring arm (cat. no. 1771-WN) shipped with the module. Attach the wiring arm to the pivot bar on the bottom of the I/O chassis. The wiring arm pivots upward and connects with the module so you can install or remove the module without disconnecting the wires. 1. Make certain all power is removed from the module before making wiring connections. 2. Swing the wiring arm up into position on the front of the module. The locking tab on the module will secure it into place. WARNING

!

When you connect or disconnect the field wiring arm with field power applied, or remove the module while backplane power is on, an electrical arc can occur. This could cause an explosion in hazardous location installations. Be sure that power is removed or the area is nonhazardous before proceeding.

ATTENTION

!

Remove power from the 1771 I/O chassis backplane and field wiring arm before removing or installing an I/O module.

• Failure to remove power from the backplane or wiring arm could cause module damage, degradation of performance, or injury. • Failure to remove power from the backplane could cause injury or equipment damage due to possible unexpected operation.

3. Make your connections to the field wiring arm as shown in the following figure. (Use the label on the front of the wiring arm to identify your wiring.) Note: A shorting bar may be used to connect the commons if channel-to-channel isolation is not required. The field wiring arm terminal identification IMPORTANT number is not the same as the number of the bit which controls that output.