Page 1 of ac/dc (120V) Isolated Input Module Installation Instructions, Cat. No. 1771-ID16 Series B

Manual · Allen-Bradley

ac/dc (120V) Isolated Input Module Installation Instructions, Cat. No. 1771-ID16 Series B

Manual16 pagesPDF 256 KB

Installation instructions for the Allen-Bradley 1771-ID16 Series B ac/dc (120V) isolated input module for 1771 I/O chassis.

Download the PDF256 KB

Filed with · 1 model

Also filed with these models on the old site

Summary

What is in it

Allen-Bradley installation instructions for the 1771-ID16 Series B ac/dc (120V) isolated input module, used with limit, float, selector and pushbutton switches in a 1771 I/O chassis. They cover handling and static precautions, power requirements, setting the input filter time jumpers, keying the backplane connector, installing the module and the 1771-WN field wiring arm, wiring connections, reading the status indicators and the module specifications.

From the manual · read page by page

Key facts from this manual

Some pages are scans or cannot be read; this says only what the readable text supports. Each line names its page in the PDF.

Allen-Bradley installation instructions (publication 1771-IN070B-EN-P, August 2002) for the 1771-ID16 Series B ac/dc (120V) isolated input module, a 16-input module for 1771 I/O chassis. It covers power planning, setting the input filter jumpers, keying, installing the module and its wiring arm, field wiring, the status indicators and specifications.

Device
16-input 120V ac/dc isolated input module for the 1771 I/O system p. 7, 13
Input voltage
74-138V ac, 47-63Hz; 105-138V dc; 120V ac/dc nominal p. 13
Chassis
Series B or later 1771 I/O chassis (1771-A1B thru -A4B), 1771-AM1, -AM2; not with the 1771-AL adapter p. 1, 13
Input current
120V ac: 12.4mA at 50Hz, 14.9mA at 60Hz; 120V dc: 2.5mA p. 13
On and off levels
On at 74V ac or 105V dc minimum; off at 45V ac or 66V dc maximum p. 13
Input delay
Off to on 0.57ms; on to off 9ms or 18.0ms selectable for ac, fixed 9ms for dc p. 13
Backplane current
75mA maximum p. 4, 13
Power dissipation
7.0 W maximum, 0.3 W minimum (23.8 BTU/hr maximum) p. 13
Isolation
Tested to 1500V ac channel to channel and channel to backplane for 1s p. 13
Wiring arm
40-terminal 1771-WN field wiring arm, screw torque 9 pound-inches (1.0Nm) p. 8, 14
Wiring
14 to 22 gauge copper wire; cable up to 1000ft (304.8m) p. 13
Keying
Between 22 and 24, and between 26 and 28 p. 14
Temperature
Operating 32 to 140°F (0 to 60°C); storage -40 to 185°F (-40 to 85°C) p. 13
Indicators
16 input status indicators and one active indicator p. 11

What this manual walks you through

  • Setting the input filter time jumpers p. 4, 5
  • Adding up backplane power for the chassis p. 4
  • Choosing a slot and keying the backplane connector p. 6
  • Installing the module and locking it in the chassis p. 7
  • Wiring field devices to the wiring arm p. 8
  • Reading the status and active indicators p. 11

Good to know

  • At the 9.0ms (Fast) filter setting half cycle dropout protection may not hold; use 18.0ms (Norm) when it is needed. p. 4
  • Driving the inputs from a 1771-OA, 1771-OD or 1771-OP output module needs a 2.5K, 10W resistor to L2. p. 10
  • Limit power dissipation in adjacent slots to 10W. p. 7
  • Wiring arm terminal numbers are not the same as the bit numbers. p. 8
  • 14 gauge wire on every terminal may keep the wiring arm cover from closing. p. 14

Questions this manual answers

What voltage does the 1771-ID16 accept?

74-138V ac at 47-63Hz, or 105-138V dc; nominal 120V ac/dc. p. 13

How much backplane current does the 1771-ID16 draw?

75mA from the chassis power supply. p. 4

How do I change the 1771-ID16 input filter time?

Take off the side covers and circuit board and move the jumpers: Fast is 9.0ms (factory default), Norm is 18.0ms for ac only. p. 5

Which wiring arm does the 1771-ID16 use?

The 40-terminal 1771-WN field wiring arm, shipped with the module. p. 8

Does the 1771-ID16 work with a 1771-AL adapter?

No. It needs a series B or later 1771 I/O chassis and is not compatible with the 1771-AL local I/O adapter. p. 1

The whole text · 2 parts

Read the manual here as text

Its text as extracted from the PDF, unedited, in parts; each page opens the PDF at that page.

  1. Pages 1 to 81-8
  2. Pages 9 to 169-16

The file

Revision and size

Part no.1771-IN070B-EN-P
RevisionAugust 2002
PublisherRockwell Automation
Pages16
PDF256 KB
TextText from the PDF itself; pages 9 and 15 are scans, read by OCR, which may hold reading errors.
1771-IN070B-EN-P

The first pages · 3 of 16

Look before you download

Each page opens the PDF at that page.

Page 1
Page 1of 16
Page 2
Page 2of 16
Page 3
Page 3of 16

More documents · 1

For the same models