Browse
(440) 299-7778
Menu
(440) 299-7778
One-year parts and labor warranty30-day money-back guaranteeContact
Page 1 of AC/DC (120V) Isolated Input Module, Cat. No. 1771-ID16, Installation Data

Manual · Allen-Bradley

AC/DC (120V) Isolated Input Module, Cat. No. 1771-ID16, Installation Data

Manual8 pagesPDF 113 KB

Installation data for the Allen-Bradley 1771-ID16 AC/DC (120V) isolated input module with 16 inputs for 1771 I/O chassis.

Download the PDF113 KB

Covers · 1 model

The models it covers

Summary

What is in it

Allen-Bradley's installation data for the 1771-ID16 AC/DC (120V) Isolated Input Module. It covers pre-installation considerations and power requirements, handling to avoid electrostatic damage, setting the input filter time jumpers, keying the I/O chassis, installing the module and wiring the 1771-WN field wiring arm for ac or dc inputs, driving an input from an output module, reading the status indicators, and full specifications.

Its parts

  1. To The Installer
  2. Pre-installation Considerations
  3. Power Requirements
  4. Initial Handling
  5. Installing Your Module
  6. Interpreting the Status Indicators
  7. Specifications

From the manual · read page by page

Key facts from this manual

Each line names its page in the PDF.

Allen-Bradley installation data (publication 1771-2.189, April 1992) for the 1771-ID16 ac/dc (120V) isolated input module, a 16-input module for 1771 I/O chassis. It explains power needs, setting the input filter jumpers, keying, installing and wiring the module, reading the status indicators, and lists the specifications.

Device
16-input 120V ac/dc isolated input module for 1771 I/O chassis p. 1, 8
Input voltage
74-138V ac, 47-63Hz; 105-138V dc; 120V ac/dc nominal p. 8
Chassis
Series B 1771 I/O chassis (1771-A1B thru -A4B); not with the 1771-AL local I/O adapter p. 1, 8
Input delay
On to off: 9ms or 18.0ms selectable for ac, 9.0ms for dc; factory set to 9.0ms p. 1, 8
On and off levels
On at 74V ac or 105V dc minimum; off at 45V ac or 66V dc maximum p. 8
Backplane current
75mA maximum p. 1, 8
Power dissipation
7.0 W maximum, 0.3 W minimum (23.8 BTU/hr maximum) p. 8
Isolation
1500V ac (rms) channel to channel and channel to backplane p. 8
Input impedance
ac: 9.3Kohm at 47Hz, 6.9Kohms at 63Hz; dc: 75Kohm off, 48Kohms on p. 8
Wiring arm
40-terminal 1771-WN field wiring arm, screw torque 9 pound-inches p. 4, 8
Wiring
Two wires per input, one wire per terminal; stranded 14 or 16 gauge on long runs; cable up to 1000ft (304.8m) p. 5, 8
Keying
Between 22 and 24, and between 26 and 28 p. 3
Temperature
Operating 0 to 60°C (32 to 140°F); storage -40 to 85°C (-40 to 185°F) p. 8
Indicators
16 red input status indicators and a green ACTIVE indicator p. 7

What this manual walks you through

  • Setting the input filter time jumpers p. 2, 3
  • Keying the I/O chassis slot for this module p. 3
  • Installing the module in a 1771 I/O chassis p. 4
  • Wiring ac or dc inputs to the field wiring arm p. 4, 5
  • Driving an input directly from an output module p. 6
  • Reading the status indicators p. 7
  • Handling the module to avoid static damage p. 2

Good to know

  • At the 9.0ms (Fast) filter setting half cycle dropout protection may not hold; use 18.0ms (Norm) when it is needed. p. 2
  • A 1771-OA, 1771-OD or 1771-OP output driving these inputs needs a 2.5K ohm, 10W resistor; a 1771-OD16 needs none. p. 6
  • Wiring arm terminal numbers are not the same as the input bit numbers. p. 5
  • All indicators light for about a second at power up as a self-test; the inputs are not on then. p. 7
  • 14 gauge wire may keep the wiring arm cover from closing. p. 8

Questions this manual answers

What voltage does the 1771-ID16 accept?

74-138V ac at 47-63Hz, or 105-138V dc; nominal 120V ac/dc. p. 8

How much backplane current does the 1771-ID16 need?

75mA from the chassis power supply. p. 1

How do I set the 1771-ID16 filter time?

Remove the side covers and circuit board and place the jumpers on Fast (9.0ms, factory default) or Norm (18.0ms, ac only). p. 3

Can a 1771 output module drive the 1771-ID16 inputs?

Yes. A 1771-OA, 1771-OD or 1771-OP needs a 2.5K ohm, 10W resistor to L2; a 1771-OD16 works without one. p. 6

Why do all 1771-ID16 lights come on at power up?

It is a self-test that lasts about one second; the inputs are not on during it. p. 7

Contents

Chapters and sections

Each line opens the PDF at its page.

  1. 1771-2.189, AC/DC (120V) Isolated Input Module, Installation Data1
  2. To The Installer1
  3. Pre-installation Considerations1
  4. Power Requirements1
  5. Initial Handling2
  6. Installing Your Module2
  7. Interpreting the Status Indicators7
  8. Specifications8
  9. Back Cover8

From the PDF’s own bookmarks.

The whole text · 1 part

Read the manual here as text

Its text as extracted from the PDF, unedited, in parts; each page opens the PDF at that page.

  1. Pages 1 to 81-8

The file

Revision and size

RevisionPublication 1771-2.189, April 1992
PublisherAllen-Bradley
Pages8
PDF113 KB
TextText from the PDF itself.

The first pages · 3 of 8

Look before you download

Each page opens the PDF at that page.

Page 1
Page 1of 8
Page 2
Page 2of 8
Page 3
Page 3of 8

More documents · 1

For the same models