The text of a manual · part 5 of 14
Analog Input Module, Cat. No. 1771-IFE, User Manual: 2 - Installing the Input Module
Pages 13 to 24 of 63, from Analog Input Module, Cat. No. 1771-IFE, User Manual
The original document is the PDF (516 KB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
For the Allen-Bradley 1771-IFE
Page 13
Chapter
2
Installing the Input Module
Chapter Objectives
This chapter gives you information on: calculating the chassis power requirement choosing the module’s location in the I/O chassis keying a chassis slot for your module wiring the input module’s field wiring arm configuring your module configuration plugs installing the input module
Before You Install Your Input Module
Electrostatic Damage
Before installing your input module in the I/O chassis: You need to:
As described under:
Calculate the power requirements of all modules in each chassis.
Power Requirements, page 2-2.
Determine where to place the module in the I/O chassis.
Module Location in the I/O Chassis, page 2-2.
Key the backplane connector in the I/O chassis.
Module Keying, page 2-2.
Make connections to the wiring arm.
Wiring Your Input Module, page 2-3 and Grounding, page 2-8.
Electrostatic discharge can damage semiconductor devices inside this module if you touch backplane connector pins. Guard against electrostatic damage by observing the following precautions:
ATTENTION: Electrostatic discharge can degrade performance or cause permanent damage. Handle the module as stated below.
Wear an approved wrist strap grounding device, or touch a grounded object to rid yourself of electrostatic charge before handling the module. Handle the module from the front, away from the backplane connector. Do not touch backplane connector pins. Keep the module in its static-shield bag when not in use. 2-1
Page 14
Chapter 2 Installing the Input Module
Power Requirements
Your module receives its power through the 1771 I/O power supply. The module requires 750mA from the backplane. Add this current to the requirements of all other modules in the I/O chassis to prevent overloading the chassis backplane and/or backplane power supply.
Module Location in the I/O Chassis
Place your module in any I/O module slot of the I/O chassis except for the extreme left slot. This slot is reserved for PC processors or adapter modules. Group your modules to minimize adverse affects from radiated electrical noise and heat. We recommend the following. Group analog input and low voltage dc modules away from ac modules or high voltage dc modules to minimize electrical noise interference. Do not place this module in the same I/O group with a discrete high-density I/O module when using 2-slot addressing. This module uses a byte in both the input and output image tables for block transfer. After determining the module’s location in the I/O chassis, connect the wiring arm to the pivot bar at the module’s location.
Module Keying
Use the plastic keying bands, shipped with each I/O chassis, for keying I/O slots to accept only one type of module. The module is slotted in two places on the edge of the rear circuit board. The position of the keying bands on the backplane connector must correspond to these slots to allow insertion of the module. You can key any connector in an I/O chassis to receive this module except for the leftmost connector reserved for adapter or processor modules. Place keying bands between the following numbers labeled on the backplane connector (Figure 2.1): between 10 and 12 between 24 and 26
2-2
Page 15
Chapter 2 Installing the Input Module
Figure 2.1 Keying Positions
Keying Bands
2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36
1771-IFE
Wiring Your Input Module
12676
Connect your I/O devices to the cat. no. 1771-WG wiring arm shipped with the module. Attach the wiring arm to the pivot bar at the bottom of the I/O chassis. It pivots upward and connects with the module so you can install or remove the module without disconnecting the wires. Input connections for the 1771-IFE with single-ended inputs are shown in Figure 2.2 and Figure 2.3. Input connections for the 1771-IFE with differential inputs are shown in Figure 2.4 and Figure 2.5. Recommended maximum cable length for voltage-mode input devices is 50 feet. This recommendation is based on considerations of signal degradation and electrical noise immunity in typical industrial environments. Cable length for current-mode input devices need not be as restrictive because analog signals from these devices are less sensitive to electrical noise interference. The 1771-IFE module is shipped from the factory set for a 1 to 5V DC voltage input. Refer to “Changing Your Module’s Configuration”on page 2-9 for other combinations of current and voltage inputs.
2-3
Page 16
Chapter 2 Installing the Input Module
Figure 2.2 Connection Diagram for 16 Single-ended Inputs and Two-Wire Transmitters
Channel 1
1
Channel 2
2
2Channel 3
2-Wire Transmitter
3
Channel 4
+
1Module Common
–
Channel 5 Channel 7
–
Channel 8
7 8
1Module Common
Channel 9
13
Channel 12 Channel 13
2 Jumper all unused channels to module common to reduce noise.
Attention: Analog input signals must be within +14.25V referenced to module common. This input signal includes any common mode voltage present between either input terminal and module common. If an input terminal exceeds this range, channel-to-channel crosstalk can cause invalid input readings and invalid underrange or overrange bits. The 1771-IFE module does not supply loop power for the input device. The user must supply loop power for loop-powered input devices.
2-4
14 15 16
Channel 14 together inside the module.
10 12
Channel 11 1Module Common
1 All commons are electrically tied
9 11
Channel 10
Source Ground
5 6
Channel 6 +
4
17
Channel 15
18
Channel 16 1Module Common 1Module Common
19 20 21
1771-WG Field Wiring Arm
10948-I
Page 17
Chapter 2 Installing the Input Module
Figure 2.3 Connection Diagram for 16 Single-ended Inputs and Four-Wire Transmitters
Channel 1
1
Channel 2
2
2Channel 3
–
+
4-Wire Transmitter
3
Channel 4
+
1Module Common
–
Channel 5 Channel 7
–
Channel 8
7 8
1Module Common
Channel 9
13
Channel 12 Channel 13
2 Jumper all unused channels to module common to reduce noise.
Attention: Analog input signals must be within +14.25V referenced to module common. This input signal includes any common mode voltage present between either input terminal and module common. If an input terminal exceeds this range, channel-to-channel crosstalk can cause invalid input readings and invalid underrange or overrange bits. The 1771-IFE module does not supply loop power for the input device. The user must supply loop power for loop-powered input devices.
14 15 16
Channel 14 together inside the module.
10 12
Channel 11 1Module Common
1 All commons are electrically tied
9 11
Channel 10
Source Ground
5 6
Channel 6 +
4
17
Channel 15
18
Channel 16 1Module Common 1Module Common
19 20 21
1771-WG Field Wiring Arm
10948-I
2-5
Page 18
Chapter 2 Installing the Input Module
Figure 2.4 Connection Diagram for 8 Differential Inputs and Two-Wire Transmitters
Channel 1+
1
Channel 1-
2
Channel 2+ 2-Wire Transmitter
+
Channel 2-
–
Not used
3 4 5
Channel 3+ Channel 3-
+
6 7
Channel 4+
–
8
Channel 4-
9
Not used
10
Channel 5+
11
Channel 5-
Source Ground
12
Channel 6+
13
Channel 6-
14
Not used
15
Channel 7+
16
NOTE: 1. Unused channels must have their + and - inputs jumpered together and tied to module common to reduce noise.
Channel 7-
Attention: Analog input signals must be within +14.25V referenced to module common. If an input channel exceeds this range, channel-to-channel crosstalk can cause invalid input readings and invalid underrange or overrange bits.
Module Common
17
Channel 8+
18
Channel 8- Module Common
19 20 21
The 1771-IFE module does not supply loop power for the input device. The user must supply loop power for loop-powered input devices. Configuring the module for differential inputs does not provide isolation.
1771-WG Field Wiring Arm 10949-I
2-6
Page 19
Chapter 2 Installing the Input Module
Figure 2.5 Connection Diagram for 8 Differential Inputs and Four-Wire Transmitters
Channel 1+ 1
Channel 1-
2
Channel 2+ –
+
4-Wire Transmitter
+
Channel 2-
–
Not used
3 4 5
Channel 3+
6
Channel 3-
+
7
Channel 4+
–
8
Channel 4-
9
Not used
10
Channel 5+
11
Channel 5-
Source Ground
12
Channel 6+
13
Channel 6-
14
Not used NOTE: 1. Unused channels must have their + and - inputs jumpered together and tied to module common to reduce noise.
Channel 7+
Attention: Analog input signals must be within +14.25V referenced to module common. If an input channel exceeds this range, channel-to-channel crosstalk can cause invalid input readings and invalid underrange or overrange bits.
Channel 8-
15 16
Channel 7-
17
Channel 8+
18
Module Common Module Common
19 20 21
The 1771-IFE module does not supply loop power for the input device. The user must supply loop power for loop-powered input devices. Configuring the module for differential inputs does not provide isolation. 1771-WG Field Wiring Arm 10949-I
2-7
Page 20
Chapter 2 Installing the Input Module
Grounding
When using shielded cable wire, ground the foil shield and drain wire only at one end of the cable. We recommend that you wrap the foil shield and drain wire together and connect them to a chassis mounting bolt (Figure 2.6). At the opposite end of the cable, tape exposed shield and drain wire with electrical tape to insulate it from electrical contact. Figure 2.6 Cable Grounding
Remove a length of cable jacket from the Belden 8761 cable.
Pull the foil shield and bare drain wire from the insulated wires.
Twist the foil shield and drain wire together to form a single strand.
Attach a ground lug.
Bare drain wire Belden 8761 Cable Insulated wires 20104
Foil shield
Chassis Ground
Single-point Grounding
When you connect grounding conductors to the I/O chassis grounding stud, place a star washer under the first lug, then place a nut with captive lock washer on top of each ground lug.
Ground Lug Nut Grounding Stud
Star Washer I/O Chassis Side Plate
Nut and Captive Washer
Ground Lug1 Shield and Drain twisted together
Shield and Drain twisted together 19923
1Use the cup washer if crimp-on lugs are not used.
19480
#10 Thread-forming screw
External-tooth Washers
Refer to Wiring and Grounding Guidelines, publication 1770-4.1 for additional information.
2-8
Page 21
Chapter 2 Installing the Input Module
Changing the Module's Configuration
The analog input module (1771-IFE) has configuration plugs for determining the input type (voltage or current) desired for each input. The module comes from the factory with the plugs positioned for voltage inputs. To set the configuration plugs for your desired inputs, proceed as follows: 1.
Remove the module’s covers by removing the four screws securing the covers to the module.
2.
Locate the selection plugs (Figure 2.7).
Figure 2.7 Configuration Plug Locations
Selection Plugs (refer to Figures 2.8, 2.9 and 2.10)
10950-I
3.
Position the plugs as shown in the Figures for your particular module (Figures 2.8, 2.9 and 2.10).
4.
Reassemble the module after you have finished checking and/or setting the selection plugs.
2-9
Page 22
Chapter 2 Installing the Input Module
Figure 2.8 Selection Plug Settings for Differential or Single-ended Voltage or Differential or Single-ended Current Inputs Voltage Differential or Single-ended
Current Single-ended Current
Differential Current storage positions storage positions
[1] 1
[1] 1
5
5
9
9
13
13
17
17
21
21
25
25
29
29
33
33 storage positions [1] 1 channel 1 channel 2
5 9 13 channel 3 channel 4
17 21 25 channel 5
29 33 channel 6 37
37
41
41
45
45
37 channel 7
41 45 channel 8 49
12677
49
12678
49 channel 1 channel 2 channel 3 channel 4 channel 5 channel 6 channel 7 channel 8 channel 9 channel 10 channel 11 channel 12 channel 13 channel 14 channel 15 channel 16
[1] Positions 1 and 2 are not used. Note: Plugs are not needed for operation in the voltage mode.
2-10
10951-I
Page 23
Chapter 2 Installing the Input Module
Figure 2.9 Configuration Plug Settings for Single-ended Voltage and Current Inputs on Adjacent Channels [1] 1 5 9 13 channel 1 (single-ended voltage) channel 2 (single-ended current) channel 3 (single-ended current) channel 4 (single-ended voltage)
[1] positions 1 and 2 are not used
10952-I
Figure 2.10 Configuration Plug Settings for Differential Voltage and Current Inputs on Adjacent Channels [1] 1 5 9 channel 1 (differential current)
channel 2 (differential voltage)
13
[1] positions 1 and 2 are not used
10953-I
Note: Either differential and single-ended configurations must be selected for the entire module.
2-11
Page 24
Chapter 2 Installing the Input Module
Module Installation
When installing your module in an I/O chassis: 1.
First, turn off power to the I/O chassis.
ATTENTION: Remove power from the 1771 I/O chassis backplane and wiring arm before removing or installing an I/O module. Failure to remove power from the backplane could cause injury or equipment damage due to possible unexpected operation. Failure to remove power from the backplane or wiring arm could cause module damage, degradation of performance, or injury.
Indicator Lights
2.
Place the module in the plastic tracks on the top and bottom of the slot that guides the module into position.
3.
Do not force the module into its backplane connector. Apply firm even pressure on the module to seat it properly.
4.
Snap the chassis latch over the top of the module to secure it.
5.
Connect the wiring arm to the module.
The front panel of the input module contains a green RUN and a red FLT (fault) indicator (Figure 2.11). At power-up an initial module self-check occurs. If there is no fault, the red indicator turns off. The green indicator will be on when the module is powered. If a fault is found initially or occurs later, the red FLT indicator lights. Possible module fault causes and corrective action is discussed in Chapter 7, Troubleshooting. Figure 2.11 Diagnostic Indicators
ANALOG IN (12 BIT)
RUN
Green RUN indicator
FLT
Red FLT indicator 10528-I
Chapter Summary
2-12
In this chapter you learned how to install your input module in an existing programmable controller system and how to wire to the field wiring arm.