Page 1 of Analog Input Module, Cat. No. 1771-IFE, User Manual

Manual · Allen-Bradley

Analog Input Module, Cat. No. 1771-IFE, User Manual

Manual63 pagesPDF 516 KB

User manual for the Allen-Bradley 1771-IFE analog input module: installation, block transfer programming, configuration and calibration.

Download the PDF516 KB

Covers · 1 model

The models it covers

Summary

What is in it

Allen-Bradley user manual for the 1771-IFE analog input module, an intelligent block transfer module for 1771 I/O chassis. It explains how the module communicates with the processor, how to install, key and wire it, how to program block transfers on PLC-2, PLC-3 and PLC-5 processors, how to configure input ranges, data format, filtering, sampling and scaling, how to read status and input data, and how to calibrate and troubleshoot it. Appendices give specifications, sample programs and data table forms.

Its parts

  1. Using This Manual
  2. Overview of the Analog Input Module
  3. Installing the Input Module
  4. Module Programming
  5. Configuring Your Module
  6. Module Status and Input Data
  7. Calibrating Your Module
  8. Troubleshooting Your Input Module

From the manual

Key facts from this manual

Some pages are scans or cannot be read; this says only what the readable text supports. Each line names its page in the PDF.

Allen-Bradley user manual for the 1771-IFE analog input module, a block transfer module for the 1771 I/O chassis with 16 single-ended or 8 differential inputs. It covers installing and wiring the module, configuring ranges, input type, data format, filtering, real time sampling and scaling, reading its status data, and troubleshooting, with specifications.

Read for this summary: pages 1 to 3, 10 to 20, 30 to 35, 39 to 40 and 44 to 47 of 63.

Device
Intelligent block transfer analog input module; single slot, needs no external power supply p. 10
Inputs
16 single-ended or 8 differential p. 47
Input ranges
1 to 5, 0 to 5, -5 to +5, -10 to +10 and 0 to 10V dc; 4 to 20, 0 to 20 and -20 to +20mA p. 10, 11
Resolution
12-bit binary (12 bits plus sign on bipolar ranges) or four-digit BCD p. 10, 47
Accuracy
0.1% of full scale range at 25 °C p. 47
Backplane current
750mA (0.75A at +5V) from the I/O chassis backplane p. 14, 47
Scan rate
12.5 ms for 8 differential, 25 ms for 16 single-ended inputs without filtering; filtering adds 2.12 ms or 4.24 p. 47
Input impedance
100 Megohms on voltage ranges; 250 ohms on current ranges p. 47
Wiring arm
1771-WG field wiring arm; screw torque 7-9 inch-pounds; 14 gauge stranded wire max. p. 47
Keying
Keying bands between 10 and 12 and between 24 and 26 p. 14
Input protection
Overvoltage 200V in voltage mode, 8V in current mode; overcurrent 30mA on current ranges p. 47
Data format
BCD, two's complement binary or signed magnitude binary; BCD typical with PLC-2, two's complement with PLC-3 and PLC-5 p. 32
Real time sampling
Sample periods from 100 ms to 3.1 seconds p. 34
Cable
Belden 8761 shielded cable, shield and drain grounded at one end only p. 20

What this manual walks you through

  • Checking the power budget, choosing a chassis slot and keying it p. 13, 14
  • Wiring 16 single-ended inputs with two-wire or four-wire transmitters p. 15, 16, 17
  • Wiring 8 differential inputs p. 18, 19
  • Grounding shielded input cable p. 20
  • Selecting the input range of each channel p. 31
  • Choosing single-ended or differential inputs and the data format p. 32
  • Setting the digital filter p. 33
  • Setting real time sampling p. 34
  • Scaling inputs to engineering units p. 35
  • Reading status bits and troubleshooting with the RUN and FLT indicators p. 39, 40, 44, 45, 46

Good to know

  • Input signals must stay within +14.25V referenced to module common; beyond that, crosstalk can give invalid readings and range bits. p. 16
  • The module does not supply loop power; loop-powered input devices need a user supply. p. 16
  • Configuring the module for differential inputs does not provide isolation. p. 18
  • The recommended maximum cable length for voltage-mode input devices is 50 feet. p. 15
  • If one channel is scaled, all channels must be scaled and all 37 configuration words written. p. 35

Questions this manual answers

How many inputs does the 1771-IFE have?

16 single-ended inputs or 8 differential inputs; all inputs on one module must be the same type. p. 32, 47

What signal ranges does the 1771-IFE accept?

Five voltage ranges (1 to 5, 0 to 5, -5 to +5, -10 to +10 and 0 to 10V dc) and three current ranges (4 to 20, 0 to 20 and -20 to +20mA), chosen per channel. p. 11, 31

What input range is the 1771-IFE set to from the factory?

A 1 to 5V DC voltage input. p. 15

Which wiring arm does the 1771-IFE use?

The 1771-WG field wiring arm shipped with the module; its screws take 7-9 inch-pounds. p. 15, 47

What does it mean when neither LED lights on a 1771-IFE?

A hardware failure, or no power or a bad PICO fuse. Turn power off, remove and reinsert the module, and restore power; if the problem stays with a working chassis supply, return the module for repair. p. 46

Contents

Chapters and sections

Each line opens the PDF at its page.

  1. 1771-6.5.90, Analog Input Module, User Manual1
  2. Important User Information2
  3. Summary of Changes3
  4. Preface - Using This Manual7
  5. 1 - Overview of the Analog Input Module10
  6. 2 - Installing the Input Module13
  7. 3 - Module Programming25
  8. 4 - Configuring Your Module30
  9. 5 - Module Status and Input Data39
  10. 6 - Calibrating Your Module41
  11. 7 - Troubleshooting Your Input Module44
  12. A - Specifications47
  13. B - Programming Examples48
  14. C - Data Table Formats52
  15. D - Block Transfer (Mini-PLC-2 and PLC-2/20 Processors)55
  16. E - Forms58
  17. Index61
  18. Back Cover63

From the PDF’s own bookmarks.

The whole text · 14 parts

Read the manual here as text

Its text as extracted from the PDF, unedited, in parts; each page opens the PDF at that page.

  1. Pages 1 to 31-3
  2. Table of Contents4-6
  3. Preface - Using This Manual7-9
  4. 1 - Overview of the Analog Input Module10-12
  5. 2 - Installing the Input Module13-24
  6. 3 - Module Programming25-29
  7. 4 - Configuring Your Module30-38
  8. Pages 39 to 4339-43
  9. 7 - Troubleshooting Your Input Module44-46
  10. Pages 47 to 5147-51
  11. C - Data Table Formats52-54
  12. D - Block Transfer (Mini-PLC-2 and PLC-2/20 Processors)55-57
  13. E - Forms58-60
  14. Pages 61 to 6361-63

The file

Revision and size

Part no.1771-6.5.90
RevisionMay 1994
PublisherAllen-Bradley Company
Pages63
PDF516 KB
TextText from the PDF itself; page 1 is a scan, read by OCR, which may hold reading errors.
1771-6.5.90