Analog Input Module, Cat. No. 1771-IFE, User Manual, pages 47 to 51

Pages 47 to 51 of 63: A - Specifications; B - Programming Examples

The original document is the PDF (516 KB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

For the Allen-Bradley 1771-IFE

Page 47

Appendix

A

Specifications Inputs per module

16 single-ended; 8 differential low level

Module Location

1771 I/O rack - 1 slot

Input voltage ranges (nominal)

+1 to +5V dc 0 to 5V dc -5 to +5V dc -10 to +10V dc 0 to +10V dc

Input current ranges (nominal)

+4 to +20mA 0 to +20mA -20 to +20mA

Resolution

12-bit binary 12 bits plus sign on bipolar ranges

Accuracy

0.1% of full scale range @ 25oC

Linearity

+1 LSB

Repeatability

+1 LSB

Isolation Voltage

+1500V, (transient)

Input overvoltage protection

200V (voltage mode)1 8V (current mode)2

Input overcurrent protection (current ranges)

30mA

Common mode voltage

+14.25 Volts

Input impedance

100 Megohms for voltage ranges; 250 ohms for current ranges

Common mode rejection

80 db, DC-120 Hz

Current Requirements

0.75A @ +5V from I/O chassis backplane

Power Dissipation

3.75 Watts (maximum)

Thermal Dissipation

12.8 BTU/hr (maximum)

Unscaled BCD and binary output to processor

0000 to +409510 for polar ranges (0 to 5V, +1 to +5V, 0 to +20mA, and +4 to +20mA) -409510 to 409510 for bipolar ranges ( +5V, +10V, +20mA)

Engineering units sent to processor

+999910 with selectable scaling

Internal scan rate

12.5 ms for 8 differential inputs (no digital filtering) -add 2.12ms for filtering 25 ms for 16 single-ended input (no digital filtering) -add 4.24 for filtering

Environmental conditions operational temperature: storage temperature: relative humidity:

0 to 600C (32 to 1400F) -40 to 850C (-40 to 1850F) 5 to 95% (without condensation)

Conductors

Wiring Category

14 gauge stranded (max.) 3/64 inch insulation (max.) Category 23

Keying between 10 and 12 between 24 and 26

Wiring Arm

Catalog Number 1771-WG

Field Wiring Arm Screw Torque

7-9 inch-pounds

1 The inputs are protected to 200V. However, if an input terminal's voltage exceeds +14.25V as referenced to module common, channel-to-channel crosstalk can cause invalid input readings and invalid underrange/overrange bits. 2 Only 8 volts can be placed directly across the input when configured in the current mode. 3 Refer to publication 1770-4.1, "Programmable Controller Wiring and Grounding Guidelines."

A-1

Page 48

Appendix

B

Programming Examples

Sample Programs for the Analog Input Module

The following are sample programs for entering data in the configuration words of the write block transfer instruction when using the PLC-2, PLC-3 or PLC-5 family processors.

PLC-2 Family Processors

To enter data in the configuration words, follow these steps: Example: Enter the following rung for a write block transfer:

BLOCK XFER WRITE DATA ADDR: 030 MODULE ADDR: 110 BLOCK LENGTH: 19 FILE: 400 - 437

011 EN 06 111 DN 06

400 is the address of the write block transfer data file. You want to examine configuration word 1. Step

Action

Description

1.

Press [SEARCH]8<data address>

Finds the block transfer instruction

2.

Press CANCEL COMMAND

Removes preceding command

3.

Press [DISPLAY]0 or 1

Displays the file in binary or BCD

4.

Move cursor to data to be modified

5.

Enter new data

6.

Press [INSERT]

Writes data to file element

Use the above procedure to enter the required words of the write block transfer instruction. Be aware that the block length will depend on the number of channels selected and whether scaling is or is not performed; for example, the block may contain only 3 words if no scaling is performed but may contain 37 words if using 16 inputs with scaling. The PLC-2 family write block transfer data file should look like Figure B.1.

B-1

Page 49

Appendix B Programming Examples

Figure B.1 Write Block Transfer Data Transfer for a PLC-2 Family Processor DATA ADDR: 030

POSITION 001 002 003 004 005 006 007 008 009 010 011 012 013 014 015 DATA

PLC-3 Family Processor

BINARY DATA MONITOR BLOCK TRANSFER WRITE MODULE ADDR: 110 FILE: 400-444

BLOCK LENGTH: 37

FILE DATA 00000000 00000000 00000000 00000000 00000000 00000000 00000000 00000000 00000000 00000000 00000000 00000000 00000000 00000000 00000000 00000000 00000000 00000000 00000000 00000000 00000000 00000000 00000000 00000000 00000000 00000000 00000000 00000000 00000000 00000000 00000000

00000000

Following is a sample procedure for entering data in the configuration words of the write block transfer instruction when using a PLC-3 processor. To enter data in the configuration words, follow these steps:

Example: Enter the following rung for a write block transfer: BLOCK XFER WRITE RACK : 001 GROUP : 1 1 = HIGH MODULE: F0003:0000 DATA: LENGTH = 37 CNTL: FB004:0000

CNTL EN 12 CNTL DN 15 CNTL ER 13

F0003:0000 is the address of the write block transfer data file. You want to enter/examine word 1. B-2

Page 50

Appendix B Programming Examples

1.

Press [SHIFT][MODE] to display your ladder diagram on the industrial terminal.

2.

Press DD, 03:0[ENTER] to display the block transfer write file.

The industrial terminal screen should look like Figure B.2. Notice the highlighted block of zeroes. This highlighted block is the cursor. It should be in the same place as it appears in Figure B.2. If it is not, you can move it to the desired position with the cursor control keys. Once you have the highlighted cursor in the right place as shown above, you can go on to step 3. Figure B.2 Write Block Transfer for a PLC-3 Processor

START - W0003 : 0000

WORD

000000 000004 000010 000014 000020

DATA MONITOR

00000000 00000000 00000000 00000000 00000000

00000000 00000000 00000000 00000000 00000000

00000000 00000000 00000000 00000000 00000000

00000000 00000000 00000000 00000000 00000000

$ W0310- [ ]

PROG : I/O OFF : NO FORCES : NO EDITS : RUNG # [RM000000 : MEM PORT OFF

3.

Enter the data corresponding to your bit selection in word 0 through 4.

4.

When you have entered your data, press [ENTER]. If you make a mistake, make sure the cursor is over the word you desire to change. Enter the correct data and press [ENTER].

5.

Press [CANCEL COMMAND]. This returns you to the ladder diagram.

B-3

Page 51

Appendix B Programming Examples

PLC-5 Family Processors

The following is a sample procedure for entering data in the configuration words of the block transfer write instruction when using a PLC-5 processor and 6200 programming software. 1.

Enter the following rung: BTW ENABLE

BLOCK XFER WRITE RACK : X GROUP : X X MODULE: XX:XX CONTROL: N7:60 DATA FILE: 37 LENGTH: N CONTINUOUS:

EN DN ER

N7:60 is the address of the BTW transfer file 2.

Press [F8] (data monitor),[F5] (change address) and enter N7:60 to display the configuration block.

The industrial terminal screen should look like Figure B.3. Figure B.3 Sample PLC-5 Data File (Hexadecimal Data)

ADDRESS 0 N7:60 N7:70 N7:80 N7:90

B-4

5003 0085 0000 0000

1

2

3

4

5

00FF 0040 0000 0000

00FF 0085 0000 0000

0040 0040 0000 0000

0085 0085 0000 0000

0040 0040 0000 0000

6

7

8

9

0085 0040 0085 0040 0085 0040 0085 0000 0000 0000 0000 0000 0000

3.

Enter the data corresponding to your bit selections and add scaling values, if scaling is desired.

4.

[ESC] returns you to the ladder program.