Analog Input Module, Cat. No. 1771-IFE, User Manual: 7 - Troubleshooting Your Input Module
Pages 44 to 46 of 63, from Analog Input Module, Cat. No. 1771-IFE, User Manual
The original document is the PDF (516 KB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
For the Allen-Bradley 1771-IFE
Page 44
Chapter
7
Troubleshooting Your Input Module
Chapter Objective
In this chapter, we describe how to troubleshoot your module by observing the indicators and by monitoring status bits reported to the processor.
Diagnostics Reported by the Module
At power-up, the module momentarily turns on the red indicator as a lamp test, then checks for: correct RAM operation firmware errors Thereafter, the module lights the green RUN indicator when operating without fault, or lights the red FAULT indicator when it detects fault conditions. The module also reports status and specific faults (if they occur) in every transfer of data (BTR) to the PC processor. Monitor the green and red indicators and status bits in word 1 of the BTR file when troubleshooting your module. Figure 7.1 Diagnostic Indicators
ANALOG IN (12 BIT)
RUN FLT 10528-I
Diagnostic Bits Reported By the Analog Input Module Diagnostic bits in the read block transfer status words provide diagnostic capabilities. Word 1 provides power-up and valid data status. Words 2, 3 and 4 provide channel data status. If a module on-board self test fault occurs, block transfers will be inhibited, the red fault (FLT) will light, and the green run (RUN) light will go out. 7-1
Page 45
Chapter 7 Troubleshooting Your Input Module
Word 1 Diagnostics word 1 is the first data word in the read block transfer file for transfer to the central processor. It contains a power-up bit (bit 00) that is set (1) when the module is first powered up. It is reset (0) after a write block transfer. It also contains an under-range or over-range bit (bit 01) that is set when any input is under or over-range. An invalid scaling data bit (bit 02) will be set if invalid scaling data is entered into any of the minimum/maximum scaling value words. Note that minimum equal to maximum is an invalid value. If invalid values are entered into the minimum or maximum scaling words the corresponding read block transfer input channel word will be set to 0000. Bit 02 will also be set if an invalid digital filter value is entered (e.g., 1F). If an invalid digital filter value is entered, the module will not perform digital filtering. The real time sample (RTS) fault bit (bit 03) is set if the module is configured for RTS and a block transfer read has not occurred within the user-programmed period. Word 2 Word 2 provides for under-range conditions. When a particular channel input is under-range, the associated bit will be set. As long as inputs are under range the associated bit will remain set. Bit 00 corresponds to channel 1, bit 01 to channel 2, etc. Word 3 Word 3 provides for over-range conditions. When a particular channel input is over-range, the associated bit will be set. As long as inputs are in range the associated bit will remain reset. Bit 00 corresponds to channel 1, bit 01 to channel 2, etc. Word 4 Word 4 provides an indication of a particular channel’s input polarity (set, or 1 = negative; reset, or 0 = positive). Bit 00 corresponds to channel 1, bit 01 to channel 2, etc. Table 7.A lists the probable cause and recommended actions for a number of common trouble indications.
7-2
Page 46
Chapter 7 Troubleshooting Your Input Module
Table 7.A Troubleshooting Chart for Analog Input Module (1771-IFE) Legend Off
Indicators
Probable Cause
RUN (green) FLT (red)
On RUN (green) FLT (red)
Recommended Action
Normal operation
None
If out-of-range bit is set (BTR word 1, bit 02) and all 8 under-range bits are set (BTR word 2, bits 00 through 07).
Return module for repair
If incorrect data in final storage word locations in processor's data table, possible severed or disconnected input cable associated with the affected channels.
Repair/replace cable.
or Input module is conditioned for BCD instead of binary or the reverse, incorrect scaling, sign bits missing, wrong range.
Condition module for desired format (BCD or binary), enter correct data and initiate another write block transfer. If module connections are intact and configuration data is correct check calibration procedure.
RUN FLT
Chapter Summary
Neither LED comes on
Hardware failure in module
Return module for repair.
No power PICO fuse is bad.
Turn off power. Remove and reinsert module into chassis. Return power. If problem still exists, and chassis power supply is functioning properly, return the module for repair.
In this chapter you learned how to interpret the indicator lights, and troubleshoot your input module.