Analog Input Module, Cat. No. 1771-IFE, User Manual, pages 39 to 43

Pages 39 to 43 of 63: 5 - Module Status and Input Data; 6 - Calibrating Your Module

The original document is the PDF (516 KB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

For the Allen-Bradley 1771-IFE

Page 39

Chapter

5

Module Status and Input Data

Chapter Objectives

In this chapter you will read about: reading data from your module block transfer read block format

Reading Data From Your Module

Block transfer read programming moves status and data from the input module to the processor’s data table in one I/O scan (Figure 5.1). The processor’s user program initiates the request to transfer data from the input module to the processor. Figure 5.1 Word Assignments for Analog Input Module (1771-IFE) Block Transfer Read

Decimal Bits

15

14

13

12

11

10

09

08

07

06

05

04

03

02

01

00

Octal Bits

17

16

15

14

13

12

11

10

07

06

05

04

03

02

01

00

Word 1

Not Used

Diagnostic Bits

Description Diagnostics

2

16

15

14

13

12

11

10

9

8

7

6

5

4

3

2

1

Data underrange for channels 1-161

3

16

15

14

13

12

11

10

9

8

7

6

5

4

3

2

1

Data overrange for channels 1-161

4

16

15

14

13

12

11

10

9

8

7

6

5

4

3

2

1

Data polarity for channels 1-16

5

Channel 1 Input

Channel 1 Input

6

Channel 2 Input

Channel 2 Input

7

Channel 3 Input

Channel 3 Input

8

Channel 4 Input

Channel 4 Input

⇓ 20

⇓ Channel 16 Input

⇓

⇓ Channel 16 Input

1 These bits are set (1) at approximately the input range limits selected (Table 5.B).

5-1

Page 40

Chapter 5 Module Status and Input Data

Block Transfer Read Format

The bit/word description for the block transfer read of the Analog Input Module is described below in Table 5.A. Table 5.A BTR Word Format for the Analog Input Module Decimal Bit (Octal Bit)

Description

Bit 00

Power up bit is used by the module to tell the processor that it is alive but not yet configured. It is a key element in the application program.

Bit 01

Out of range bit is sent to tell the processor that one or more channels are either over or under range.1

Bit 02

Invalid scaling bit reports that the scaling is somehow invalid. Usually, both values are equal or minimum is greater than maximum when this bit comes on. Can also be an invalid filter value.

Bit 03

Real time sample fault bit. This bit is set if the module is configured for RTS and a block transfer read has not occurred within the user-programmed period.

Word 2

Bits 00-15 (00-17)

Individual underrange bits for each channel. Bit 00 for channel 1, bit 01 for channel 2, etc.1 These bits are set (1) at approximately the input range limits selected from Table 5.B.

Word 3

Bits 00-15 (00-17)

Individual overrange bits for each channel. Bit 00 for channel 1, bit 01 for channel 2, etc.1 These bits are set (1) at approximately the input range limits selected from Table 5.B.

Word 4

Bits 00-15 (00-17)

Polarity bits are set when input is less than zero. Bit 00 for channel 1, bit 01 for channel 2, etc.

Word

Word 1

Word 5 thru 20

Input values. Word 5 for channel 1, word 6 for channel 2, etc.

1 Attention: If an input terminal's voltage exceeds +14.25V as referenced to module common, channel-to-channel crosstalk can cause invalid input readings and invalid underrange/overrange bits.

Table 5.B Input Range Selection Voltage input

Current input1

1 to 5V dc

4 to 20mA

0 to 5V dc

0 to 20mA1

-5 to +5V dc

-20 to +20mA2

-10 to +10V dc2 0 to 10V dc 1 Current input mode selected by configuration plug. 2 Configurable using bi-polar scaling.

Chapter Summary

5-2

In this chapter you learned the meaning of the status information that the input module sends to the processor.

Page 41

Chapter

6

Calibrating Your Module

Chapter Objectives

In this chapter we tell you what tools you need and how to calibrate your module.

Tools and Equipment

In order to calibrate your input module you will need the following tools and equipment: Equipment

Calibration Procedure

Description

Digital voltmeter

5-1/2 digit, 0.01% accuracy minimum: Keithley191 or Fluke 8300A or equivalent

Alignment tool

P/n 35F616, for pot adjustment: Newark Electronics, 500 N.Pulaski Rd., Chicago, IL

Potentiometer sealant

Torque Seal: Organic Products, P.O. Box 928, Irving, TX

Industrial terminal

Cat. no. 1770-T3 and program panel interconnect cable (cat. no. 1772-TC) for PLC-2 family processors: Allen-Bradley,Highland Hts., OH

Backplane extender card

Cat. no. 1771-EZ

The analog input module is shipped from the factory already calibrated. If necessary to recalibrate the module, you must calibrate the module in an I/O chassis. The module must communicate with the processor and industrial terminal. Calibration consists of adjusting the 10V reference and nulling the input offset. Important: The module must be powered up for at least 30 minutes before attempting to calibrate.

ATTENTION: Do not attempt to calibrate your module until you have read and thoroughly understand this procedure. Also, do not attempt to calibrate this module in an operating system. Damage to the equipment or personal injury may result.

6-1

Page 42

Chapter 6 Calibrating Your Module

Adjusting the 10V Reference 1.

Turn off power to your processor and I/O chassis.

2.

Swing the field wiring arm out of the way.

3.

Remove the module from the I/O chassis.

4.

Plug the module into the extender card, and insert the extender card into the I/O chassis.

5.

Attach the negative lead to an analog common (pin 5, 10, 15, 20 or 21) of the wiring arm.

6.

Attach the positive lead of your voltmeter to TP1.

7.

To set the on-board +10V reference, adjust potentiometer R64 (Figure 6.1) until the value at TP1 = 10.0000V (+.0002V maximum).

Figure 6.1 Test Points and Potentiometers for Analog Input Module (1771-IFE) 1

3

E1

E1 Jumper in calibration position

1

3

E1

Left Side of Module

R63 6-2

R64 TP2

TP1

10956-I

Page 43

Chapter 6 Calibrating Your Module

Nulling the Input Offset After completing the 10V reference adjustment, turn off power to your processor and I/O chassis and complete the following steps.

Chapter Summary

1.

Move jumper E1 (Figure 6.1) from the default position (connecting the center and right posts) to the calibration position (connecting the center and left posts).

2.

Attach the negative lead of your voltmeter to an analog common (pin 5, 10, 15, 20 or 21) of the field wiring arm.

3.

Attach the positive lead of your voltmeter to TP2.

4.

Turn on power to your processor and I/O chassis. Check to make sure the red FLT indicator is lit and the green RUN indicator is off. If the red indicator is off, check the position of E1.

5.

Adjust potentiometer R63 (Figure 6.1) until the value at TP2 = 0.0000V (+0.0002V maximum).

6.

After completing the adjustment, remove power from the I/O chassis and return jumper E1 to the default position.

In this chapter you learned how to calibrate your module. This included the necessary tools, adjusting the 10V reference, and nulling the offset.

6-3