For the Allen-Bradley 1771-IQ

Page 1

Installation Instructions DC (5-30V) Selectable Input Module Cat. No. 1771-IQ To The Installer

This document provides information on:

• • • • • •

Pre-installation Considerations important pre-installation considerations power supply requirements initial handling procedures installing the module using the indicators for troubleshooting module specifications

Each of the eight inputs to this module are switch selectable for current sourcing or current sinking of your device. The module can be set for either high true or low true logic. In addition, the module has selectable delay times of 12ms nominal (5ms minimum; 26ms maximum) in normal or 1ms (maximum) in fast position. Set these switches before you install your module. The dc selectable input module can be installed in either a Series A or B 1771 I/O chassis.

European Union Directive Compliance If this product has the CE mark it is approved for installation within the European Union and EEA regions. It has been designed and tested to meet the following directives.

EMC Directive This product is tested to meet Council Directive 89/336/EEC Electromagnetic Compatibility (EMC) and the following standards, in whole or in part, documented in a technical construction file: • EN 50081-2EMC – Generic Emission Standard, Part 2 – Industrial Environment • EN 50082-2EMC – Generic Immunity Standard, Part 2 – Industrial Environment This product is intended for use in an industrial environment.

Publication 1771-2.24

Page 2

2

DC (5-30V) Selectable Input Module Cat. No. 1771-IQ

Low Voltage Directive This product is tested to meet Council Directive 73/23/EEC Low Voltage, by applying the safety requirements of EN 61131–2 Programmable Controllers, Part 2 – Equipment Requirements and Tests. For specific information required by EN 61131-2, see the appropriate sections in this publication, as well as the following Allen-Bradley publications: • Industrial Automation Wiring and Grounding Guidelines For Noise Immunity, publication 1770-4.1 • Guidelines for Handling Lithium Batteries, publication AG-5.4 • Automation Systems Catalog, publication B111

Power Requirements

Initial Handling

The logic circuitry of this module receives its power through the 1771 I/O chassis backplane from the chassis power supply. The module requires 150mA from the output of this supply. Add this to the requirements of all other modules in the I/O chassis to prevent overloading the chassis backplane and/or backplane power supply.

The input module is shipped in a static-shielded bag to guard against electrostatic discharge damage. Observe the following precautions when handling the module.

Electrostatic Discharge Damage

!

ATTENTION: Under some conditions, electrostatic discharge can degrade performance or damage the module. Observe the following precautions to guard against electrostatic damage.

• Wear an approved wrist strap grounding device, or touch a grounded object to discharge yourself before handling the module. • Do not touch the backplane connector or connector pins. • If you configure or replace internal components, do not touch other circuit components inside the module. If available, use a static-free work station. • When not in use, keep the module in a static-shielded bag.

Installing Your Module

Publication 1771-2.24

In this section we tell you how to set the logic level switch, the input sink switch, the input source switch, key your I/O chassis, install your module and make your wiring connections.

Page 3

DC (5-30V) Selectable Input Module Cat. No. 1771-IQ

3

Selecting the Logic Level SW-1

You can select one of two logic conditions:

OFF ON 1 2

If you choose:

Then:

Set Switch SW:

HIGH = TRUE logic

ON > 40% of customer supply voltage OFF < 20% of customer supply voltage

SW1 position 2 ON

LOW = TRUE logic

ON < 20% of customer supply voltage OFF > 40% of customer supply voltage

SW1 position 2 OFF

Selecting the Input Delay

Input Module (cover removed)

You can select one of two input delay times: If you choose:

Then the delay time is:

Set Switch SW1:

Typical

12ms (5ms min.; 26ms max.)

SW1 position 1 ON

Fast

1ms maximum

SW1 position 1 OFF

The input delay time applies to all eight inputs. They are not individually selectable.

Selecting Sinking or Sourcing for Inputs Two switches (SW2 and SW3) are provided for determining source or sink capability for each input. SW2 selects sink capability, and SW3 selects source capability. To set the switches, follow the procedure below.

SW-1 OFF ON 1 2

SW-2 OFF ON

Input Module (cover removed)

1. Remove the side cover from the module by removing the screws at the four corners.

SW-3 1 2 3 4 5 6 7 8 11905-I

OFF ON

1 2 3 4 5 6 7 8

2. Set the switches as needed for your application. 3. Reinstall the cover and secure with the four screws. Sink

Source

Input

Switch Position

SW-2

SW-3

SW-2

SW-3

0

1

On

Off

Off

On

1

2

On

Off

Off

On

2

3

On

Off

Off

On

3

4

On

Off

Off

On

4

5

On

Off

Off

On

5

6

On

Off

Off

On

6

7

On

Off

Off

On

7

8

On

Off

Off

On

Publication 1771-2.24

Page 4

4

DC (5-30V) Selectable Input Module Cat. No. 1771-IQ

Keying Your I/O Chassis Use the plastic keying bands, shipped with each I/O chassis, to key the I/O slots to accept only this type of module. The module circuit board is slotted in two places on the rear edge. The position of the keying bands on the backplane connector must correspond to these slots to allow insertion of the module. You can key any connector in an I/O chassis to receive this module except for the left-most connector reserved for adapter or processor modules. Place keying bands between the following numbers labeled on the backplane connector: Between 6 and 8 Between 24 and 26 You can change the position of these keys if system redesign and rewiring makes insertion of a different module necessary.

Installing the Input Module To install the input module in your 1771 I/O chassis, follow the steps listed below. ATTENTION: Remove power from the 1771 I/O chassis backplane and wiring arm before removing or installing an I/O module. Failure to remove power from the backplane or wiring arm could cause module damage, degradation of performance, or injury. Failure to remove power from the backplane could cause injury or equipment damage due to possible unexpected operation. locking-bar pins front of chassis 12453-I

1. Remove power from the I/O chassis before inserting (or removing) the module. 2. On chassis equipped with a chassis locking bar, pull the locking-bar pins to release the locking bar and swing it up. If installing in an earlier chassis, lift the module locking latch up. 3. Insert the module into slot. 4. Place the module in the plastic tracks on the top and bottom of the leftmost slot. These slots guide the module into position. 5. Press firmly and evenly to seat the module in its backplane connectors.

Publication 1771-2.24

Page 5

DC (5-30V) Selectable Input Module Cat. No. 1771-IQ

!

5

ATTENTION: Do not force the module into the backplane connector. If you cannot seat the module with firm pressure, check the alignment and keying. Forcing the module can damage the backplane connector or the module.

6. Snap the chassis locking bar (or locking latch on earlier chassis) over the top of the module to secure it. Make sure the locking pins on the locking bar are fully engaged. Note: The chassis locking bar will not close if all modules are not properly seated. 7. Connect the field wiring arm to the module. 8. Make wiring connections to the field wiring arm as indicated below.

Connecting Wiring to the Input Module Connections to the input module are made to the field wiring arm (cat. no. 1771-WC) shipped with the module. Attach the wiring arm to the pivot bar on the bottom of the I/O chassis. The wiring arm pivots upward and connects with the module so you can install or remove the module without disconnecting the wires.

!

ATTENTION: Do not apply ac or reverse dc voltage to module terminals. Circuitry at the input of module may be damaged.

Connection Diagram (See applicable codes and laws.) (+) 5-30V dc

A

Input 0

O

Input 1

1

Input 2

2

Input 3

3

Input 4

4

Input 5

5

Input 6

6

Input 7

7 dc Common

8

Module Input Sink dc Current Source Device +

Module Input Source Module Input Source

3-Wire Current Sink Proximity Switch dc Current Sink Device

Power Supply (Customer Supplied) -

Conventional current flow

11906-I

(Actual wiring runs in this direction.)

Publication 1771-2.24

Page 6

6

DC (5-30V) Selectable Input Module Cat. No. 1771-IQ

1. Separate the shielded cables from wiring that radiates electrical noise. Refer to publication 1770-4.1, “Wiring and Grounding Guidelines” for more information. 2. Connect each user input device using shielded cable such as Belden 8761. Prepare the shielded cable as shown below. Do not exceed 50 cable feet for any output device. Connect the insulated wires to their respective terminals on the wiring arm. Remove a length of cable jacket from the Belden 8761 cable.

Pull the foil shield and bare drain wire from the insulated wires. Bare drain wire

Twist the foil shield and drain wire together to form a single strand.

Attach a ground lug.

Belden 8761 Cable Insulated wires

20104

Foil shield

Important: Connect the insulated signal return wire in each transmission cable to the dc common terminal of your +5V dc power supply at one end, and to the dc common terminal of the wiring arm at the other end. Do not confuse the signal return lead with the shield/drain wire. 3. Ground the single strand (foil shield and drain wire) to the grounding stud on the I/O chassis or by using single-point grounding (below). Chassis Ground When you connect grounding conductors to the I/O chassis grounding stud, place a star washer under the first lug, then place a nut with captive lock washer on top of each ground lug.

Single-point Grounding

Ground Lug Nut Grounding Stud

Nut and Captive Washer

Star Washer I/O Chassis Side Plate

Ground Lug1 19480

1Use the cup washer if crimp-on lugs are not used.

Publication 1771-2.24

Twisted foil shield and drain wire #10 Thread-forming screw

19923

External-tooth Washers

Page 7

DC (5-30V) Selectable Input Module Cat. No. 1771-IQ

Interpreting the Status Indicators

7

The front panel of your module contains eight status indicators.. Each of the eight red indicators light when their corresponding input terminal is in the true state, regardless of whether the module is selected for High True or Low True logic.

Note: Indicators may appear dim during rapid pulsing of input signals. Empty Input 0 Input 1 Input 2 Input 3 Input 4 Input 5 Input 6 Input 7

Status Indicators

11907-I

Publication 1771-2.24

Page 8

8

DC (5-30V) Selectable Input Module Cat. No. 1771-IQ

Specifications

Inputs per Module

8

Module Location

1771 I/O chassis

Nominal Input Current Input Voltage Range HIGH = TRUE

5mA @ 5V dc; 25mA @ 30V dc ON: > 40% of customer supply voltage OFF: < 20% of customer supply voltage ON: < 20% of customer supply voltage OFF: > 40% of customer supply voltage

LOW = TRUE Customer Supply Voltage Customer Supply Current per Module

5V dc to 30Vdc All inputs ON and connected for source capability: 100mA per module @ 5V dc 350mA per module @ 30V dc

Input Impedance

1.2K ohms nominal

Input Signal Delay

Fast: Less than 1ms Normal: 12ms typical (-7ms, +14ms)

Power Dissipation

6.8 Watts (max.), 0.8 Watts (min.)

Thermal Dissipation

23.2 BTU/hr (max.), 2.7 BTU/hr (min.)

Backplane Current

150mA max.

Isolation Voltage

1500V ac rms

Environmental Conditions Operational Temperature Storage Temperature Relative Humidity Conductors

Wire Size Category

Keying

0o to 60oC (32o to 140oF) -40o to 85oC (-40o to 185oF) 5 to 95% (without condensation) 14 gauge (2mm2) stranded maximum 3/64 inch (1.2mm) insulation maximum 21 Between 6 and 8 Between 24 and 26

Wiring Arm

Catalog Number 1771-WC

Wiring Arm Screw Torque Agency Certification (when product or packaging is marked)

7-9 inch-pounds • CSA certified • CSA Class I, Division 2, Groups A, B, C, D certified • UL listed • CE marked for all applicable directives

1 You use this conductor-category for planning conductor routing as described in the system-level installation manual.

Allen-Bradley, a Rockwell Automation Business, has been helping its customers improve productivity and quality for more than 90 years. We design, manufacture and support a broad range of automation products worldwide. They include logic processors, power and motion control devices, operator interfaces, sensors and a variety of software. Rockwell is one of the world's leading technology companies.

Worldwide representation. Argentina • Australia • Austria • Bahrain • Belgium • Brazil • Bulgaria • Canada • Chile • China, PRC • Colombia • Costa Rica • Croatia • Cyprus • Czech Republic • Denmark • Ecuador • Egypt • El Salvador • Finland • France • Germany • Greece • Guatemala • Honduras • Hong Kong • Hungary • Iceland • India • Indonesia • Ireland • Israel • Italy • Jamaica • Japan • Jordan • Korea • Kuwait • Lebanon • Malaysia • Mexico • Netherlands • New Zealand • Norway • Pakistan • Peru • Philippines • Poland • Portugal • Puerto Rico • Qatar • Romania • Russia-CIS • Saudi Arabia • Singapore • Slovakia • Slovenia • South Africa, Republic • Spain • Sweden • Switzerland • Taiwan • Thailand • Turkey • United Arab Emirates • United Kingdom • United States • Uruguay • Venezuela • Yugoslavia

Allen-Bradley Headquarters, 1201 South Second Street, Milwaukee, WI 53204 USA, Tel: (1) 414 382-2000 Fax: (1) 414 382-4444

Publication 1771-2.24 - April 1994 Supersedes publication 1771-2.24 - July 1990

Publication 1771-2.24

PN 955112-77