The text of a manual · part 6 of 6
1771 Digital I/O DC Input and Output Modules Product Data, pages 51 to 59
Pages 51 to 59 of 59
The original document is the PDF (1.0 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
For the Allen-Bradley 1771-IQ
Page 51
48
1771 Digital I/O DC Input and Output Modules
DC Output Module (Cat. No. 1771-OQ Series B)
Status Indicators
Specifications (Cat. No. 1771-OQ/B) Outputs per Module
8 (4 groups of 2, each group sharing a common dc supply)
Module Location
1771 I/O chassis
Output Voltage Range
24V dc (+10%,-15%) Peaks of modulated ripple must be between 17-34V dc
Maximum Output Current
2.25A per output 2.25A per group 9A per module
Maximum Surge Current
4.0A for 10ms per output
Maximum On-state Voltage Drop
2V dc @ 2.25A 1.0mA per output @ 34V dc, 25oC
Maximum Off-state Leakage Current
Status Indicators
4.5W per output
Thermal Dissipation
65.1 BTU/hr (max.), 4.1 BTU/hr (min.)
Backplane Current
225mA
Isolation Voltage
1500V ac rms
Environmental Conditions Operational Temperature Storage Temperature Relative Humidity
0o to 60oC (32o to 140oF) -40o to 85oC (-40o to 185oF) 5 to 95% (without condensation) 14 gauge (2mm2) stranded maximum 3/64 inch (1.2mm) insulation maximum 11
Conductors Wire Size Category Fuses
2.5A, 3AG (1 per output pair)
Keying
Between 2 and 4 Between 10 and 12
Field Wiring Arm
Catalog Number 1771-WF
Wiring Arm Screw Torque
7-9 inch-pounds • CSA certified • CSA Class I, Division 2 Groups A, B, C, D certified • UL listed • CE marked for all applicable directives
Installation Instructions
1771-2.92
1 You use this conductor-category for planning conductor routing as described in the system-level installation manual.
12260-I
Sample Connection Diagram Driving a 1771-IQ Module with a 1771-OQ Module DC Output Module Cat. No. 1771-OQ
DC Input Module Cat. No. 1771-IQ +24V dc
Not used +24V dc Output 0 Output 1 dc Common dc Common Output 2 Output 3 +24V dc +24V dc Output 4 Output 5 dc Common dc Common Output 6 Output 7 +24V dc Not used
1 2
19.1 Watts (max.), 1.1 Watts (min.)
3 4 5 6 7 8
10ms on or off
Power Dissipation
9 10 11 12
Output Signal Delay
13 14 15 16 17 18
Maximum Power Rating
Agency Certification (when product or packaging is marked)
Not used Output 0 Output 1 Output 2 Output 3 Output 4 Output 5 Output 6 Output 7
A dc+
O
Input 0
1
Input 1
2
Input 2
3
Input 3
4
Input 4
5
Input 5
6
Input 6
7
Input 7
8 dc Common dc Common (Actual wiring runs in this direction.)
Publication 1771-2.180 - July 1996
12261-I
Page 52
1771 Digital I/O DC Input and Output Modules
49
DC Input Module (Cat. No. 1771-OQ16 Series B)
Simplified Schematic
Fuse-blown Indication Circuitry Opto Isolation
3.8k
Input LED Indication dc Input (+)
3A System Circuitry
Opto Isolation
.0047µF
39V
10.0k dc Output (-) 12262-I
Application Notes
Connection Diagram
Device Compatibility. This module must be used in a series B I/O chassis. The 1771-OQ16 is not compatible with the 1771-AL local I/O adapter. This module is designed to operate with dc relays and other dc output devices Connection to Input Modules. You can use an output of the 1771-OQ16 module to drive an input of a dc input module (cat. no. 1771-IQ16) to indicate status of turning on a motor starter, for example. Status Indicators. The module has 18 indicators, consisting of 16 output status indicators, a fuse-blown indicator and an active indicator. The 16 status indicators are provided for system logic side indication of individual outputs. The active indicator lights when the module has successfully started up and initialized.The fuse-blown indicator lights when a fuse has cleared or been removed, the channel associated with that fuse has been turned the applied voltage to that channel is above the specified minimum voltage, and the load is less than or equal to the maximum specified for this module. The fuse-blown indicator will reset after the fuse has been replaced and chassis power has been cycled.
Alternate Load Location
Load
Output 0 Output 1 Output 2 Output 3 Not used Output 4 Output 5 Output 6 Output 7 Not used Output 10 Output 11 Output 12 Output 13 Not used Output 14 Output 15 Output 16 Output 17 Not used
+dc - 0 +dc - 1 +dc - 2 +dc - 3 Not Used +dc - 4 +dc - 5 +dc - 6 +dc - 7 Not used +dc - 10 +dc - 11 +dc - 12 +dc - 13 Not used +dc - 14 +dc - 15 +dc - 16 +dc - 17 Not used
Load
(Actual wiring runs in this direction.) dc High +
24V dc Power Supply dc Return 10565-I
Publication 1771-2.180 - July 1996
Page 53
50
1771 Digital I/O DC Input and Output Modules
DC Output Module (Cat. No. 1771-OQ16 Series B)
Status Indicators
Specifications (Cat. No. 1771-OQ16/B) Outputs per Module
16
Module Location
Series B 1771 I/O Chassis
Output Voltage Range
10 to 32V dc
Minimum Output Current
5mA
Maximum Output Current
2.0A per output; 32.0A per module
Maximum On-state Voltage Drop
0.34V dc @ 2A
Maximum Off-state Leakage Current
0.5mA per output @ 32V dc, 25oC
Maximum Surge Current Power Rating
4A for 10ms per output, repeatable every 2 sec.
Output State Indicators (red)
0.68 Watts per output (max) @ 2A
Output Signal Delay
Turn On: 100usec (max); Turn Off: 300usec (max)
Power Dissipation
13.0 Watts (max); 2.0 Watts (min)
Thermal Dissipation
44.3 BTU/hr (max); 6.8 BTU/hr (min)
Backplane Current
400mA maximum
Isolation Voltage
1500V channel-to-channel 1500V channel to backplane
Maximum Cable Length
1000 ft (304.8 m)
Conductors Wire Size
14 gauge (2mm2) stranded maximum2 3/64 inch (1.2mm) insulation maximum 11
Category Environmental Conditions Operational Temperature Storage Temperature Relative Humidity
0o to 60oC (32o to 140oF) -40o to 85oC (-40o to 185oF)
5 to 95% (without condensation)
Fuses
3A 2AG Fast Acting fuses (1 per output) Littelfuse P/N 225003
Keying
Between 22 and 24 Between 32 and 34
Field Wiring Arm
Catalog Number 1771-WN
Wiring Arm Screw Torque
7-9 inch-pounds
Agency Certification (when product or packaging is marked)
• CSA certified • CSA Class I, Division 2 Groups A, B, C, D certified • UL listed • CE marked for all applicable directives
Installation Instructions
1771-2.192
1You use this conductor-category information for planning conductor routing as described in the system-level installation manual. 2 14 gauge wire connected to all terminals may not allow the cover on the field wiring arm to close. A smaller gauge wire may be used.
Fuse Blown Indicator (red) 10567-I
Sample Connection Diagram Driving a 1771-IQ16 Module with a 1771-OQ16 Module DC (24V) Isolated Output Module Cat. No. 1771-OQ16 dc High +dc - 0 +dc - 1 +dc - 2 +dc - 3 Not Used +dc - 4 +dc - 5 +dc - 6 +dc - 7 Not used +dc - 10 +dc - 11 +dc - 12 +dc - 13 Not used +dc - 14 +dc - 15 +dc - 16 +dc - 17 Not used
+
Publication 1771-2.180 - July 1996
ACTIVE Indicator (green)
ACTIVE 00 10 01 11 02 12 03 13 04 14 05 15 06 16 07 17 FUSE
2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40
10-32V dc Power Supply
Output 0 Output 1 Output 2 Output 3 Not used Output 4 Output 5 Output 6 Output 7 Not used Output 10 Output 11 Output 12 Output 13 Not used Output 14 Output 15 Output 16 Output 17 Not used
DC (24V) Isolated Input Module Cat. No. 1771-IQ16
2 4 6 dc Return
8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40
Input 0 Input 1 Input 2 Input 3 Not used Input 4 Input 5 Input 6 Input 7 Not used Input 10 Input 11 Input 12 Input 13 Not used Input 14 Input 15 Input 16 Input 17 Not used
(Actual wiring runs in this direction.)
-
10566-I
Page 54
1771 Digital I/O DC Input and Output Modules
51
DC Output Module (Cat. No. 1771-OVN Series B)
Simplified Schematic
Fuse Blown Indication LED (logic) 1N4007
15k
+dc Common (1 of 4)
Output Indication LED (logic)
System Circuitry
Opto Isolation
1N4007
470
1N4007
Output
Opto Isolation dc Supply Common (1 of 4)
Fuse 4 Amp
18670
Application Notes Device Compatibility. The 1771-OVN dc output module has sinking outputs which can interface with sourcing inputs. You must use this module in a series B 1771 I/O chassis. Do not place this module in the same I/O chassis as the 1771-IX thermocouple module. You can use this module in the same chassis as the 1771-IXE thermocouple module as long as you use 1/2-slot addressing. Connection to Input Modules. A 1771-OVN module can directly drive terminals on a 1771-IVN input module. Use the same dc supply to power both modules to ensure that ground is at the same potential. Status Indicators. The module has 32 status indicators. These represent the control status of the outputs. These are provided for system logic side indication of individual outputs. An additional indicator is provided to indicate a blown fuse condition.
Connection Diagram Output 0 Output 2 Output 4 Output 6 Common 0 Output 10 Output 12 Output 14 Output 16 Common 1 Output 0 Output 2 Output 4 Output 6 Common 2 Output 10 Output 12 Output 14 Output 16 Common 3
2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40
Note: Terminals on the left are even numbered (2 thru 40) , and terminals on the right are odd numbered (1 thru 39).
+ dc Output 1 Output 3 Output 5 Output 7 + dc Output 11 Output 13 Output 15 Output 17 + dc Output 1 Output 3 Output 5 Output 7 + dc Output 11 Output 13 Output 15 Output 17 dc Output Device + + dc Supply -
(See applicable codes and laws.) (Actual wiring runs in this direction.)
12262-I
Publication 1771-2.180 - July 1996
Page 55
52
1771 Digital I/O DC Input and Output Modules
DC Output Module (Cat. No. 1771-OVN Series B)
Specifications (Cat. No. 1771-OVN/B) Outputs per module
32 (4 groups of 8)
Module Location
Series B 1771 I/O Chassis
Output Voltage Range
10 to 30V dc
Maximum Output Current
0.5A per output 2A per group 8A per module
Maximum Surge Current
2A per output for 10ms; repeatable every 2sec. 5A per output group for 10ms.; repeatable every 2sec. 20A per module for 10ms.; repeatable every 2sec.
00 10 00 10 01 11 01 11 02 12 02 12 03 13 03 13 04 14 04 14 05 15 05 15 06 16 06 16 07 17 07 17 FUSE
1.0mA per output @ 30V dc, 55oC
Maximum Off-state Leakage Current Maximum On-state Voltage Drop
Status Indicators (red)
Fuse Blown Indicator
1.5V dc at 2A
Maximum Power Rating
3W per output
Output Signal Delay
On to off propagation delay 2.0msec Off to on propagation delay 0.1msec
Power Dissipation
13.7W (max); 1.7W (min)
Thermal Dissipation
46.7 BTU/hr (max); 5.7 BTU/hr (min)
Backplane Current
330mA @ 5V dc maximum
Isolation Voltage
1500V ac rms
Environmental Conditions Operational Temperature Storage Temperature Relative Humidity
0o to 60oC (32o to 140oF) -40o to 85oC (-40o to 185oF) 5 to 95% (without condensation) 14 gauge (2mm2) stranded (max)2 3/64 inch (1.2mm) insulation (max) 11
Conductors Wire Size Category Fuses
Four 4.0A, 250V normal blow fuses (1 per group)
Keying
Between 14 and 16 Between 32 and 34
Field Wiring Arm
1771-WN
Wiring Arm Screw Torque Agency Certification (when product or packaging is marked)
Status Indicators
7-9 inch-pounds • CSA certified • CSA Class I, Division 2 Groups A, B, C, D certified • UL listed • CE marked for all applicable directives
Installation Instructions
1771-5.36
1You use this conductor-category information for planning conductor routing as described in the system-level installation manual. 2 14 gauge wire connected to all terminals may not allow the cover on the field wiring arm to close. A smaller gauge wire may be used.
12263-I
Sample Connection Diagram Driving a 1771-IVN Module with a 1771-OVN Module DC Output Module Cat. No. 1771-OVN
2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40
DC Input Module Cat. No. 1771-IVN +dc 10-30V dc dc Common
2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40
(Actual wiring runs in this direction.) 12264-I
Publication 1771-2.180 - July 1996
Page 56
Notes
53
Notes
Publication 1771-2.180 - July 1996
Page 57
54
Notes
Notes
Publication 1771-2.180 - July 1996
Page 58
Support Services
Support Services
55
At Allen-Bradley, customer service means experienced representatives at Customer Support Centers in key cities throughout the world for sales service and support. Our value-added services include:
Technical Support • • • •
SupportPlus programs telephone support and 24-hour emergency hotline software and documentation updates technical subscription services
Engineering and Field Services • • • • application engineering assistance integration and start-up assistance field service maintenance support
Technical Training • • • • lecture and lab courses self-paced computer and video-based training job aids and workstations training needs analysis
Repair and Exchange Services • • • • your only “authorized” source current revisions and enhancements worldwide exchange inventory local support
Publication 1771-2.180 - July 1996
Page 59
Allen-Bradley, a Rockwell Automation Business, has been helping its customers improve productivity and quality for more than 90 years. We design, manufacture and support a broad range of automation products worldwide. They include logic processors, power and motion control devices, operator interfaces, sensors and a variety of software. Rockwell is one of the world's leading technology companies.
Worldwide representation. Argentina • Australia • Austria • Bahrain • Belgium • Brazil • Bulgaria • Canada • Chile • China, PRC • Colombia • Costa Rica • Croatia • Cyprus • Czech Republic • Denmark • Ecuador • Egypt • El Salvador • Finland • France • Germany • Greece • Guatemala • Honduras • Hong Kong • Hungary • Iceland • India • Indonesia • Ireland • Israel • Italy • Jamaica • Japan • Jordan • Korea • Kuwait • Lebanon • Malaysia • Mexico • Netherlands • New Zealand • Norway • Pakistan • Peru • Philippines • Poland • Portugal • Puerto Rico • Qatar • Romania • Russia-CIS • Saudi Arabia • Singapore • Slovakia • Slovenia • South Africa, Republic • Spain • Sweden • Switzerland • Taiwan • Thailand • Turkey • United Arab Emirates • United Kingdom • United States • Uruguay • Venezuela • Yugoslavia
Allen-Bradley Headquarters, 1201 South Second Street, Milwaukee, WI 53204 USA, Tel: (1) 414 382-2000 Fax: (1) 414 382-4444
Publication 1771-2.180 - July 1996 Supersedes publication 1771-2.180 - July 1992
Copyright 1995 Allen-Bradley Company, Inc. Printed in USA