Page 61

Chapter

7

1756 ControlLogix I/O Modules

1756-CFM - Standard Flowmeter Wiring 2

1756-CFM - Standard Prover/Detector Wiring

1

12-24V dc

Z0 12-24V dc

Z1 12-24V dc 4

3

6

5

8

7

–

F1 10

9

12

11

14

13

16

15

18

17

F0 Return

Input Device

F1 Return

Not used

Shield ground

Shield ground

Z1 RET

F0

+

+ –

20

7

10

9

12

11

14

13

16

15

18

17

20

19

Z1 RET F1 F1 Return Not used

Not used

Not used

Output 0

Output 1 Customer Common

Customer VCC

Customer Common

Customer VCC

8

Z1 5V dc

Not used

Customer Common

19

5

F0 Return

Output 1

Customer VCC

6

F0

Not used

Output 0

3

Z0 Return

Shield ground

Not used

Not used

Z1 1224V dc 4

Z0 5V dc

Z1 5V dc

Z0 Return

1

Z0 12-24V dc

–

Z0 5V dc

Input Device

2

+

Customer Common

Customer VCC

NOTES: 1. This wiring diagram can be used in applications with 50mV (magnetic pickup), 1.3V (TTL), and 4V (preamp level) thresholds. You must use RSLogix 5000 to choose the appropriate threshhold level for your application. 2. Do not connect more than 2 wires to any single terminal.

NOTE: 1. The wiring example above shows a 12-24V dc standard prover connected to the module. If you use a 5V dc standard prover, make sure the positive wire is connected to the 5V terminal (e.g. Z0 5V dc). 2. Do not connect more than 2 wires to any terminal.

1756-CFM - Standard Output

1756-HSC - 845 Incremental Encoder

2

1

Z0 12-24V dc

Z1 12-24V dc 4

3

6

5

8

7

Z0 5V dc

Z1 5V dc

Z0 Return

Z1 RET

F0

F1 10

9

12

11

F0 Return

F1 Return

Not used

Not used 14

16

15

18

17

20

19

Output 0

+ Load

–

Customer VCC Customer VCC

2

1

Z1 (12-24V)

Z0 (5V)

4

3

Z1 (5V)

Z0 (RET)

6

5

Z1 (RET)

B0 (12-24V)

8

7

B1 (12-24V)

B0 (5V)

10

9

B1 (5V)

B0 (RET) A0 (12-24V)

12

11

14

13

B1 (RET) A1 (12-24V)

A0 (5V)

16

15

A1 (5V)

A0 (RET)

18

17

A1 (RET)

Not used

20

19

Not used

Not used

Not used

22

21

Not used

24

23

Output 1

Not used Out 0

26

25

Not used Out 2

Out 1

28

27

Out 3

COMMON 0

30

29

COMMON 1

COMMON 0

32

31

COMMON 1

COMMON 0

34

33

COMMON 1

DC-0(+)

36

35

DC-1(+)

13

Not used

Z0 (12-24V)

Customer Common Customer Common

+

+ Load

–

Allen-Bradley Bulletin 845 Incremental Encoder

Green Black Blue Black White

Differential Line Driver Output

Black

–

NOTES: 1. If separate power sources are used, do not exceed the specified isolation voltage.

2. Do not connect more than 2 wires to any single terminal.

Appl ic ation :

A1 Co nne cti ons:

B 1 Co nne cti ons:

Z1 Con nect ions :

Differential Line Driver Output (40mA)

White - A1 (5V) Black of white - A1 (RET)

Blue - B1 (RET) Black of blue - B1 (5V)

Green - Z1 (5V) Black of green - Z1 (RET)

NOTE: Do not connect more than 2 wires to any single terminal.

1

Publication CIG-WD001B-EN-P - May 2005

Page 62

7-2

1756 ControlLogix I/O Modules

1756-HSC - 872 3-Wire DC Proximity Sensor

Allen-Bradley Bulletin 872 3-Wire DC Proximity Sensor

Z0 (12-24V)

Jumpers

Black

12-24V dc

Blue 12-24V dc Return

2

1756-HSC - Photoswitch Series 10,000 Photoelectric Sensor

Z1 (12-24V)

1

Z0 (5V)

4

3

Z1 (5V)

Z0 (RET)

6

5

Z1 (RET)

Z0 (12-24V)

2

1

Z1 (12-24V)

Z0 (5V)

4

3

Z1 (5V)

Z0 (RET)

6

5

Z1 (RET)

Photoswitch Series 10,000 Photoelectric Sensor

White Blue

B0 (12-24V)

8

7

B1 (12-24V)

B0 (12-24V)

9

7

10-30V dc

10

8

B1 (12-24V)

B0 (5V)

B1 (5V)

B0 (5V)

10

9

B1 (5V)

Not used

12 11

B0 (RET) A0 (12-24V)

12

11

14

13

B1 (RET) A1 (12-24V)

B0 (RET) A0 (12-24V)

A0 (5V)

16

15

A1 (5V)

14 13

B1 (RET) A1 (12-24V)

A0 (5V)

18

17

16 15

A1 (5V)

A0 (RET)

A1 (RET)

A0 (RET)

A1 (RET)

Not used

18 17

20

19

Not used

Not used

22

21

20 19

Not used

Not used

Not used

Not used

22 21

Not used

Not used Out 0

24

23

26

25

Not used Out 2

Not used Out 0

24 23 26 25

Not used Out 2

Out 1

28

27

Out 3

Out 1

28 27

Out 3

COMMON 0

30

29

COMMON 1

COMMON 0

COMMON 1

COMMON 0

30 29

32

31

COMMON 1

COMMON 0

32 31

COMMON 1

COMMON 0

34

33

COMMON 1

COMMON 0

DC-0(+)

36

35

DC-1(+)

34 33

DC-0(+)

36 35

Black

Jumper 12-24V dc Return

COMMON 1 DC-1(+)

Appl ic ation :

A0 Co nne cti ons:

B 0 Co nne cti ons:

Z0 Con nect ions :

Appl ic ation :

A1 Co nne cti ons:

B 1 Co nne cti ons:

Z1 Con nect ions :

PNP (Sourcing) N.O.

Black - A0 (12-24V) Blue, PS(-)- A0 (RET)

Jumper B0 (12-24V) to B0 (RET)

Jumper Z0 (12-24V) to Z0 (RET)

Any

Black - A1 (12-24V) Blue - A1 (RET)

Jumper B1 (12-24V) to B1 (RET)

White - Z1 (12-24V) Blue - Z1 (RET)

NOTE: Do not connect more than 2 wires to any single terminal.

NOTE: Do not connect more than 2 wires to any single terminal.

1756-HYD02

+O UT-0

+O UT-1

-OU T-0

-OUT -1

+E NABL E-0

+EN ABLE- 1

-ENA BL E-0

-ENABLE-1

DR VF LT-0

DR VF LT-1

CH AS SIS

CH AS SIS

IN _COM

IN _COM

HO ME -0

HO ME -1

RE G2 4V-0

REG 24V-1

RE G5 V-0

REG 5V-1

+O K

1756-HYD02 - Wiring 5V Sensors

General cable CO720

To valve driver/amplifier

General cable CO721

To hydraulic control unit or To valve or pump

General cable CO720

To home limit switch

General cable CO720

To registration sensor

5V dc Field Power Supply + –

5 Volt Registration Sensor Supply

From 1756-HYD02

General cable C0720

REG5V IN_COM

Output Common

-O K

CH AS SIS

CH AS SIS

+IN T-0

+INT-1

-INT-0

-INT-1

+R ET-0

+RE T-1

-R ET-0

-R ET-1

LD T C MN

LD T CMN

CH AS SIS

CH AS SIS

1756-HYD02 - Wiring 24V Sensors General cable CO722

To L D T

24V dc Field Power Supply + – General cable CO720

To E-stop relay coil

24 Volt Registration Sensor Supply

NOTES: 1. This is a general wiring example illustrating Axis 1 wiring only. Other configurations are possible with Axis wiring identical to Axis 1. 2. Make sure that any transducer connected t othe 1756-HYD02 module uses an external interrogation signal. 3. Do exceed the specified isolation voltage between power sources.

Publication CIG-WD001B-EN-P - May 2005

From 1756-HYD02

General cable C0720

REG24V IN_COM

Output Common

Page 63

1756 ControlLogix I/O Modules

1756-HYD02 - Wiring Home Limit Switch

7-3

1756-HYD02 - Wiring OK Contacts 24V dc Field Power Supply

24V dc Field Power Supply + –

+

–

OK Pilot Relay From 1756-HYD02

HOME IN_COM

General cable C0720

+OK -OK

General cable C0720

From 1756-HYD02

OK Pilot Relay Contacts

CR1

Start

Stop

CR1 M1

24V AC/DC or 120VAC typical

CR1

1756-IA16 2

1

4

3

IN-1

IN-0

Group 0 Daisy chain to other RTBs

L2-0

2

1

IN-0

L2-1

4

3

IN-1

L2-2

6

5

IN-2

L2-3

8

7

IN-3

L2-4

10

9

IN-4

L2-5

12 11

IN-5

L2-6

14 13

IN-6

L2-7

16 15

IN-7

L2-8

18 17

IN-8

L2-9

20 19

IN-9

L2-10

22 21

IN-10

L2-11

24 23

IN-11

L2-12

26 25

IN-12

L2-13 L2-14

28 27

IN-13

30 29

IN-14

L2-15

32 31

IN-15

L2-15 Not used

34 33

Not used Not used

L2-0

IN-3

IN-2 6

5

8

7

10

9

12

11

14

13

IN-5

IN-4

IN-7

Group 0

L2-2 L2-4

IN-6

L2-0

L2-0

IN-9

Jumper bar - Cut to length

IN-8

(Part number 97739201)

IN-11

IN-10 16

Group 1

1756-IA16I Isolated wiring

15

IN-13

IN-12 18

17

20

19

IN-15

Group 1

IN-14

L2-1

Non-isolated wiring

L2-1

L2

L1

NOTES: 1. All terminals with the same name are connected together on the module. For example, L2 can be connected to any terminal marked L2-0. 2. When you daisy chain from a group to another RTB, always connect the daisy chain as shown above. Do not connect more than 2 wires to any single terminal. 3. This wiring example shows a single voltage source.

L2

36 35

L1-0 L1-2 L1-4

L1

Daisy chain to other RTBs NOTES

1. All terminals with the same name are connected together on the module. For example, L2 can be connected to either terminal marked L2-15. 2. When you use the second L2-15 terminal to daisy chain to other RTBs, always connect the daisy chain to the terminal directly connected to the supply wire, as shown in the example above. Do not connect more than 2 wires to any single terminal.

Publication CIG-WD001B-EN-P - May 2005

Page 64

7-4

1756 ControlLogix I/O Modules

1756-IA32 IN-1 IN-3 IN-5 IN-7 IN-9 IN-11 IN-13 IN-15 L2-0 IN-17 IN-19 IN-21 IN-23 IN-25 IN-27 IN-29 IN-31 L2-1

Group 0 Daisy chain to other RTBs

Group 1

2

IN-0 IN-2 IN-4 IN-6 IN-8 IN-10 IN-12 IN-14

1

4

3

6

5

8

7

10

1756-IA8D

9

12 11 14 13 16 15 18 17

L2-0 IN-16 IN-18 IN-20 IN-22 IN-24 IN-26 IN-28 IN-30 L2-1

20 19 22 21 24 23 26 25 28 27 30 29 32 31 34 33 36 35

Daisy chain to other RTBs

Group 0 Group 0

1

Daisy chain to other RTBs

Group 1

IN-4

9

L1

13

Group 0

Group 2

15

IN-12

IN-13 18

17

20

19

Group 1

IN-14

IN-15

GND-1

GND-1 –

16

15

IN-4 IN-5 IN-6

L2-1 18

17

20

19

47kΩ, 1/2W, 5% resistor

Group 1

IN-7 L1-1 Loss of Field Power

To Determine Leakage Resistor (P/S = Field side power supply) RLEAKMaximum = (P/S Voltage-19V ac)/1.5mA RLEAKMinimum = (P/S Voltage-20V ac)/2.5mA

Group 0

IN-10

IN-11 16

13

Resistors are not necessary if Wire Off diagnostic is not used.

IN-8

IN-9

Group 1

14

L1

GND-0 11

11

NOTES: 1. All terminals with the same name are connected together on the module. For example, L2 can be connected to any terminal marked L2-0. 2. This wiring example shows a single voltage source. 3. When you daisy chain from a group to other RTBs, alway connect the daisy chain to the terminal directly connected to the supply wire, as shown above. Do not connect more than 2 wires to any single terminal. 4. If separate power sources are used, do not exceed the specified isolation voltage.

Group 1

GND-0

14

12

L2

IN-6

IN-7

12

47kΩ, 1/2W, 5% resistor

IN-3

L2-1

Group 1

Group 0

IN-2

L2-1

5

IN-5 7

9

L2-1

IN-2

10

10

IN-1

Recommended Values P/S Voltage

RLEAK, 1/2W, 5%

100V ac +/-10%

43k Ω

110V ac +/-10%

47k Ω

115V ac +/-10%

47k Ω

120V ac +/-10%

51k Ω

Daisy chain to other RTBs

IN-3

8

7

L2-1

IN-0

6

8

IN-0

1756-IB16D

IN-1 Group 0

5

L2-0

1756-IB16

3

6

L1-0 Loss of Field Power

L2-0

L2-0

NOTES: 1. All terminals with the same name are connected together on the module. For example, L2 can be connected to any terminal marked L2-0. 2. When you daisy chain from a group to another RTB, always connect the daisy chain as shown above. Do not connect more than 2 wires to any single terminal. 3. This wiring example shows a single voltage source. 4. If separate power sources are used, do not exceed the specified isolation voltage.

2

1 3

L2-0

L2

4

2 4

Not used

Group 3

+

GND-0

2

1

IN-0

GND-0 GND-0

4

3

6

5

IN-1 IN-2

GND-0

8

7

IN-3

GND-1 GND-1

10

9

12 11

IN-4 IN-5

GND-1

14 13

IN-6

GND-1

16 15

IN-7

GND-2

18 17

IN-8

GND-2 GND-2

20 19

IN-9 IN-10

GND-2 GND-3

24 23 26 25

IN-11 IN-12

GND-3

28 27

IN-13

GND-3 GND-3 GND-3

30 29 34 33

IN-14 IN-15 Not used

Not used

36

Not used

22 21

32 31 35

14.3kΩ, 1/4W, 2% resistor

Group 0

Group 1

14.3kΩ, 1/4W, 2% resistor

Group 2

Group 3

DC COM NOTES: 1. All terminals with the same name are connected together on the module. For example, DC COM can be connected to either terminal marked GND-0. 2. When you daisy chain from a group to another RTB, always connect the daisy chain as shown above. Do not connect more than 2 wires to any single terminal. 3. This wiring example shows a single voltage source. 4. If separate power sources are used, do not exceed the specified isolation voltage.

–

+

DC COM NOTES:

1. All terminals with the same name are connected together on the module. 2. This wiring example shows a single voltage source. 3. When you daisy chain from a group to other RTBs, alway connect the daisy chain to the terminal directly connected to the supply wire, as shown above. Do not connect more than 2 wires to any single terminal. 4. Resistors are not necessary if Wire Off diagnostic is not used. 5. If separate power sources are used, do not exceed the specified isolation voltage.

To Determine Leakage Resistor (P/S = Field side power supply) RLEAKMaximum = (P/S Voltage- 4.6V dc)/1.21mA RLEAKMinimum = (P/S Voltage- 5V dc)/1.5mA

Publication CIG-WD001B-EN-P - May 2005

Recommended Values P /S Voltage

R LE AK, 1/4W, 2%

12V dc +/-5%

5.23k Ω

24V dc +/-5%

14.3k Ω

Page 65

1756 ControlLogix I/O Modules

1756-IB16I

1756-IB16ISOE

Isolated wiring

Sink input wiring

DC-0 (-)

DC-5 (-)

–

+

Jumper bar (Part number 97739201)

Non-isolated wiring DC (-)

DC-0 (+)

GND-0

2

1

IN-0

GND-1

4

3

IN-1

GND-2

6

5

IN-2

GND-3

8

7

IN-3

GND-4

10

9

IN-4

Source input wiring

GND-5

12 11

IN-5

(+) DC-5 (+)

GND-6

14 13

IN-6

GND-7

16 15

IN-7

GND-8

18 17

IN-8

GND-9

20 19

IN-9

GND-10

22 21

IN-10

GND-11

24 23

IN-11

GND-12

26 25

IN-12

GND-13 GND-14

28 27

IN-13

30 29

IN-14

GND-15

32 31

IN-15

GND-15 Not used

34 33

Not used Not used

36 35

Non-isolated wiring

DC (+)

Sink input wiring

Isolated wiring

GND-0 DC-0 (-) GND-1 GND-2 GND-3 GND-4 Source input wiring GND-5 GND-6 DC-6 (-) GND-7 GND-8 GND-9 GND-10 Jumper bar GND-11 (Part number 97739201) GND-12 GND-13 Non-isolated GND-14 wiring GND-15 GND-15 DC (-) Not used

Daisy chain to other RTBs

NOTES:

Daisy chain to other RTBs

Group 1

4

3

6

5

8

7

IN-0 DC-0 (+) IN-1 IN-2 IN-3 IN-4 Source input wiring IN-5 IN-6 DC-6 (+) IN-7 IN-8 IN-9 IN-10 IN-11 Sink input wiring IN-12 IN-13 IN-14 IN-15 Not used Not used DC (+)

10 9 12 11 14 13 16 15 18 17 20 19 22 21 24 23 26 25 28 27 30 29 32 31 34 33 36 35

2

1

4

3

6

5

8

7

10

9

1756-IC16

IN-21 IN-23 IN-25 IN-27 IN-29 IN-31

24 23

34 33

IN-0 IN-2 IN-4 IN-6 IN-8 IN-10 IN-12 IN-14 GND-0 IN-16 IN-18 IN-20 IN-22 IN-24 IN-26 IN-28 IN-30

GND-1

36 35

GND-1

DC COM –

1

1. All terminals with the same name are connected together on the module. For example, DC (-) can be connected to either terminal marked GND-15. 2. When you use the second GND-15 terminal to daisy chain to other RTBs, always connect the daisy chain to the terminal directly connected to the supply wire, as shown in the example above. 3. If separate power sources are used, do not exceed the specified isolation voltage. 4. Do not connect more than 2 wires to any single terminal. 5. The jumper bar is part number 97739201; use this number to order additional bars.

1756-IB32/B

Group 0

2

Daisy chain to other RTBs

NOTES: 1. All terminals with the same name are connected together on the module. For example, DC (-) can be connected to either terminal marked GND-15. 2. When you use the second GND-15 terminal to daisy chain to other RTBs, always connect the daisy chain to the terminal directly connected to the supply wire, as shown in the example above. Do not connect more than 2 wires to any single terminal. 3. Each input can be wired in a sink or source configuration, as shown above. 4. If separate power sources are used, do not exceed the specified isolation voltage.

IN-1 IN-3 IN-5 IN-7 IN-9 IN-11 IN-13 IN-15 GND-0 IN-17 IN-19

7-5

12 11 14 13 16 15 18 17 20 19 22 21

26 25 28 27 30 29 32 31

2

1

4

3

6

5

8

7

IN-1

IN-0

IN-3

Group 0 Group 0

IN-2

IN-5

IN-4

IN-7 10

9

12

11

14

13

16

15

18

17

20

19

GND-0

GND-0

IN-9

IN-8

IN-11

Group 1 Group 1

IN-10

IN-13

IN-11

IN-15

GND-1

Daisy chain to other RTBs

–

+

DC COM

NOTES: 1. All terminals with the same name are connected together on the module. For example, DC COM can be connected to either terminal marked GND-1. 2. When you daisy chain to other RTBs, always connect the daisy chain as shown above. Do not connect more than 2 wires to any single terminal at any time. 3. This wiring example shows a single voltage source. 4. If separate power sources are used, do not exceed the specified isolation voltage.

Group 1

IN-14

GND-1

+

Group 0

IN-6

NOTES:

1. All terminals with the same name are connected together on the module. For example, DC COM can be connected to any terminal marked GND-1. 2. When you daisy chain from a group to another RTB, always connect the daisy chain to the terminal directly connected to the supply wire, as shown above. Do not connect more than 2 wires to any single terminal. 3. This wiring example shows a single voltage source. 4. If separate power sources are used, do not exceed the specified isolation voltage.

Publication CIG-WD001B-EN-P - May 2005

Page 66

7-6

1756 ControlLogix I/O Modules

1756-IF16 – Differential Current Applications

Channel 0 i

Channel 0

A

Shield ground Channel 3 2-Wire Transmitter

Channel 6 i A i +

+

A

4-Wire Transmitter

24V dc

–

–

1756-IF16 – Differential Voltage Applications

IN-0 IN-1 IN-2 IN-3 RTN IN-4 IN-5 IN-6 IN-7 IN-8 IN-9 IN-10 IN-11 RTN IN-12 IN-13 IN-14 IN-15

2

1

4

3

6

5

8

7

10

9 i RTN-0 i RTN-1 i RTN-2 i RTN-3 RTN i RTN-4 i RTN-5 i RTN-6 i RTN-7 i RTN-8 i RTN-9 i RTN-10 i RTN-11 RTN i RTN-12 i RTN-13 i RTN-14 i RTN-15

12 11 14 13 16 15 18 17 20 19 22 21 24 23 26 25 28 27 30 29 32 31 34 33 36 35

Jumper wires

+ –

Shield ground

Channel 3

+ –

Shield ground

Shield ground

IN-0 IN-1

2

1

4

3 i RTN-0 i RTN-1

IN-2

6

5 i RTN-2

IN-3

8

7 i RTN-3

RTN IN-4 IN-5 IN-6 IN-7 IN-8 IN-9

10

9

RTN i RTN-4 i RTN-5 i RTN-6 i RTN-7 i RTN-8 i RTN-9

IN-10 IN-11 RTN IN-12 IN-13

24 23

32 31 i RTN-10 i RTN-11 RTN i RTN-12 i RTN-13

IN-14

34 33 i RTN-14

IN-15

36 35 i RTN-15

12 11 14 13 16 15 18 17 20 19 22 21

26 25 28 27 30 29

NOTES: 1. Use the table below when wiring your module in differential current mode.

Th is c han nel :

Uses t hese terminal s:

Th is ch ann el :

NOTES: 1. Use the following chart when wiring your module in differential mode

Uses t hese t erm inal s:

This channel :

Uses these terminals:

This channel:

Uses these terminals:

Channel 0

IN-0 (+) & IN-1 (-)

Channel 4

IN-8 (+) & IN-9 (-)

Channel 1

IN-2 (+) & IN-3 (-)

Channel 5

IN-10 (+) & IN-11 (-)

Channel 0

IN-0 (+), IN-1 (-) & i RTN-0

Channel 4

IN-8 (+), IN-9 (-) & i RTN-8

Channel 2

IN-4 (+) & IN-5 (-)

Channel 6

IN-12 (+) & IN-13 (-)

Channel 1

IN-2 (+), IN-3 (-) & i RTN-2

Channel 5

IN-10 (+), IN-11 (-) & i RTN-10

Channel 3

IN-6 (+) & IN-7 (-)

Channel 7

IN-14 (+) & IN-15 (-)

Channel 2

IN-4 (+), IN-5 (-) & i RTN-4

Channel 6

IN-12 (+), IN-13 (-) & i RTN-12

Channel 3

IN-6 (+), IN-7 (-) & i RTN-6

Channel 7

IN-14 (+), IN-15 (-) & i RTN-14

2. All terminals marked RTN are connected internally. 3. A 249 current loop resistor is located between IN-x and i RTN-x terminals. 4. If multiple (+) or multiple (-) terminals are tied together, connect that tie point to a RTN terminal to maintain the module’s accuracy.

2. When operating in 4 channel, high speed mode, only use channels 0, 2, 4 and 6 3. All terminals marked RTN are connected internally. 4. If multiple (+) or multiple (-) terminals are tied together, connect that tie point to terminal to maintain the module’s accuracy. 5. Terminals marked RTN and i RTN are not used for differential voltage wiring. 6. Do not connect more than 2 wires to any single terminal.

5. Place additional loop devices (e.g. strip chart recorders, etc.) at the A location in the current loop. 6. Do not connect more than two wires to any single terminal. IMP ORTANT: When operating in 4 ch annel, high sp eed mo de, only use channels 0, 2, 4 and 6.

1756-IF16 – Single-Ended Current Applications

1756-IF16 – Single-Ended Voltage Applications i 2

1

4

3 i RTN-0 i RTN-1

IN-2

6

5 i RTN-2

IN-3

8

7 i RTN-3

RTN IN-4 IN-5 IN-6 IN-7 IN-8 IN-9

10

9

RTN i RTN-4 i RTN-5 i RTN-6 i RTN-7 i RTN-8 i RTN-9

IN-10 IN-11 RTN IN-12 IN-13

24 23

32 31 i RTN-10 i RTN-11 RTN i RTN-12 i RTN-13

IN-14

34 33

IN-15

36 35

IN-0 IN-1 Shield ground 2-Wire Transmitter i A

12 11 14 13 16 15 18 17 20 19 22 21

26 25 28 27 30 29

+

2

1

4

3 i RTN-0 i RTN-1

IN-2

6

5 i RTN-2

IN-3

8

7 i RTN-3

RTN IN-4 IN-5 IN-6 IN-7 IN-8 IN-9

10

9

RTN i RTN-4 i RTN-5 i RTN-6 i RTN-7 i RTN-8 i RTN-9

24 23 i RTN-14

IN-10 IN-11 RTN IN-12 IN-13

32 31 i RTN-10 i RTN-11 RTN i RTN-12 i RTN-13 i RTN-15

IN-14

34 33 i RTN-14

IN-15

36 35 i RTN-15

Jumper wires

NOTES: 1. All terminals marked RTN are connected internally. 2. A 249Ω current loop resistor is located between IN-x and i RTN-x terminals. 3. For current applications, all terminals marked i RTN must be wired to terminals marked RTN. 4. Place additional loop devices (e.g. strip chart recorders, etc.) at the A location. 5. Do not connect more than 2 wires to any single terminal.

Publication CIG-WD001B-EN-P - May 2005

– Shield ground

+ –

Shield ground

IN-0 IN-1

12 11 14 13 16 15 18 17 20 19 22 21

26 25 28 27 30 29

NOTES: 1. All terminals marked RTN are connected internally. 2. Terminals marked i RTN are not used for single-ended voltage wiring. 3. Do not connect more than 2 wires to any single terminal.

Page 67

1756 ControlLogix I/O Modules

1756-IF4FXOF2F Current Mode (+)

(-)

1756-IF4FXOF2F Voltage Mode

A

(+)

(+)

i

2-Wire A Transmitter

+IN-1/V IN-1/I -IN-1

2

1

4

3

6

5

+IN-0/V IN-0/I -IN-0

+IN-3/V

8

7

+IN-2/V

User Analog Input Device (-)

+IN-1/V IN-1/I -IN-1

2

1

4

3

6

5

+IN-0/V IN-0/I -IN-0

+IN-3/V

8

7

+IN-2/V

IN-3/I -IN-3 Not used Not used V OUT-1

10 9

I OUT-1 RTN-1

20 19

Not used Not used

24 23

Not used Not used

28 27 30 29

Not used Not used

IN-3/I

10 9

-IN-3 Not used Not used V OUT-1

12 11

I OUT-1 RTN-1

20 19

Not used Not used

24 23

Not used Not used

28 27 30 29

Not used Not used

Not used

32 31

Not used

Not used

32 31

Not used

Not used

34 33

Not used

Not used

34 33

Not used

36 35

Not used

Not used

36 35

Not used Not used

14 13 16 15 18 17 22 21

26 25

IN-2/I -IN-2 Not used Not used V OUT-0 I OUT-0 RTN-0

Shield ground i Current Output Load

A

Not used Not used

7-7

Shield ground

12 11 14 13 16 15 18 17 22 21

26 25

IN-2/I -IN-2 Not used Not used

(+)

V OUT-0 I OUT-0 RTN-0 Not used (-) Not used

Shield ground

NOTE: Place additional loop devices (e.g. strip chart recorders) at any A location.

1756-IF6CIS - 2-Wire transmitter connected to the module and the module providing 24V dc loop power 1

2

VOUT-1

VOUT-0 4

3

6

5

IN-1/I

IN-0/I

RTN-1

RTN-0 8

A

+ 2-Wire Transmitter –

10

14

13

16

15

18

17

20

19

RTN-3 i

Shield ground

VOUT-4

IN-5/I

IN-4/I RTN-4

5

RTN-0 7

NOT ES: 1. Do not connect more than 2 wires to any single terminal.

A

24V dc – +

2-Wire Transmitter

VOUT-2 10

9

12

11

14

13

16

15

18

17

20

19

IN-3/I

IN-2/I

RTN-3

RTN-2

Not used

Shield ground

Not used

VOUT-5

VOUT-4

IN-5/I RTN-5

A IN-0/I

VOUT-3

Not used

VOUT-5

VOUT-0 i

RTN-1

RTN-2

Not used

3

8

IN-2/I 11

4

IN-1/I

9

12

1

6

VOUT-2

IN-3/I

2

VOUT-1

7

VOUT-3

RTN-5

A

1756-IF6CIS - 2-Wire transmitter connected to the module and an external, user-provided power supply providing 24V dc loop power

IN-4/I RTN-4

NOTES: 1. If separate power sources are used, do not exceed the specified isolation voltage. 2. Place additional loop devices (e.g. strip chart recorders) at either A location in the current loop.

2. Do not connect more than 2 wires to any single terminal. 3. Place additional loop devices (e.g. strip chart recorders) at either A location in the current loop.

Publication CIG-WD001B-EN-P - May 2005

Page 68

7-8

1756 ControlLogix I/O Modules

1756-IF6CIS - 4-Wire transmitter connected to the module and an external, user-provided power supply providing 24V dc loop power

1756-IF6I - Current Application with 2-Wire Transmitter

1

2

VOUT-0 i 3

4

IN-1/V A

IN-1/I

IN-0/I 6

5

RTN-1

RTN-0 8

7

10

9

VOUT-3

A

4-Wire Transmitter –

16

15

Not used

8

Shield ground

18

10

9

12

11

14

13

16

15

18

17

20

19

IN-2/I

RET-3

RET-2 Not used

Not used IN-4/I

20

A

7

IN-3/I

17 19

RTN-5

IN-4/V

IN-5/V

RTN-4

IN-4/I

IN-5/I NO TE S: 1. If separate power sources are used, do not exceed the

RET-4

RET-5 specified isolation voltage.

A

IN-2/V

VOUT-4

IN-5/I

2-Wire Transmitter i

RET-0

IN-3/V

Not used

VOUT-5

5

RET-1

RTN-2 13

6

IN-0/I

–

11

14

3

IN-1/I

24V dc

IN-2/I

RTN-3

4

+

–

IN-0/V

+

+

VOUT-2

IN-3/I 12

1

2

VOUT-1

2. Do not connect more than 2 wires to any single terminal. 3. Place additional loop devices (e.g. strip chart recorders) at either A location in the current loop.

NOTES:

1. Place additional loop devices (e.g. strip chart recorders, etc.) at either A location. 2. If separate power sources are used, do not exceed the specified isolation voltage.

1756-IF6I - Current Application with 4-Wire Transmitter 2

IN-0/V 4

3

6

5

8

7

IN-1/I

RET-0

IN-3/V

12

A A i

4-Wire Transmitter

IN-1/I

–

RET-1

IN-2/V

IN-3/V

IN-2/I

IN-3/I

11

RET-3

RET-2 14

13

16

15

18

17

Not used

Shield Ground

Not used

IN-5/V

IN-4/V

IN-5/I

IN-4/I 20

User Analog Input Device

IN-0/I 6

5

8

7

RET-0

– Device External Power

IN-2/V 10

9

12

11

14

13

16

15

18

17

20

19

IN-2/I RET-2 Not used

Not used IN-5/V

IN-4/V

IN-5/I RET-5

+

3

RET-3

19

RET-4

IN-0/V 4

9

IN-3/I

1

IN-1/V

+ IN-0/I

RET-1

RET-5

Voltage Input

1

2

IN-1/V

10

1756-IF6I - Voltage Application

IN-4/I

Shield Ground

RET-4

NOTES: Do not connect more than 2 wires to any single terminal. NOTES: 1. Place additional loop devices (e.g. strip chart recorders, etc.) at either A location. 2. Do not connect more than 2 wires to any single terminal.

Publication CIG-WD001B-EN-P - May 2005