Page 77

1756 ControlLogix I/O Modules

1756-OB16IS

1756-OB32

Isolated wiring DC-0 (+) DC-1 (+) DC-2 (+) DC-2 (+) DC-3 (+) DC-4 (+) Sinking output wiring DC-5 (+) DC-6 (+) DC-6 (+) + – DC-7 (+) Jumper bar DC-8 (+) (Cut to length) DC-9 (+) DC-10 (+) DC-11 (+) Non-isolated DC-12 (+) wiring DC-13 (+) DC-14 (+) DC-15 (+) DC(+) DC-15 (+) Not used DC-0 (+)

2

1

4

3

6

5

8

7

10

9

12

11

14

13

16

15

18

17

20

19

22

21

24

23

26

25

28

27

30

29

32

31

34

33

36

35

7-17

OUT-0 OUT-1 OUT-2 OUT-3 OUT-4 OUT-5 OUT-6 OUT-7 OUT-8 OUT-9 OUT-10 OUT-11 OUT-12 OUT-13 OUT-14 OUT-15

Isolated sourcing output wiring DC-0 (-) DC-2 (-)

Group 0

Daisy chain to other RTBs

DC-6 (-)

Non-isolated sourcing output wiring

Group 1

Not used Not used

OUT-1 OUT-3 OUT-5

2

1

4

3

6

5

OUT-7 OUT-9 OUT-11

8

7

10

9

OUT-0 OUT-2 OUT-4 OUT-6 OUT-8 OUT-10

12 11

OUT-13 OUT-15 DC-0(+)

14 13

OUT-17 OUT-19 OUT-21

20 19

OUT-23 OUT-25 OUT-27

26 25

OUT-29 OUT-31 DC-1(+)

32 31

Group 0

OUT-12 OUT-14 RTN OUT-0

16 15 18 17

OUT-16 OUT-18 OUT-20 OUT-22 OUT-24 OUT-26

22 21 24 23

28 27 30 29

Group 1

OUT-28 OUT-30 RTN OUT-1

34 33 36 35

DC(-)

_

+

Daisy chain to other RTBs NOTES: 1. All terminals with the same name are connected together on the module. For example, DC (+) can be connected to either terminal marked DC-15. 2. When you use the second DC-15 (+) terminal to daisy chain to other RTBs, always connect the daisy chain as shown in the example above. Do not connect more than 2 wires to any single terminal. 3. Outputs can be wired in a sink or source configuration as shown above. 4. If separate power sources are used, do not exceed the specified isolation voltages.

DC COM

NOTES: 1. When you daisy chain from a group to another RTB, always connect the daisy chain as shown above. Do not connect more than 2 wires to any single terminal. 2. This wiring example uses a single voltage source. 3. If separate power sources are used, do not exceed the specified isolation voltage.

1756-OB8

1756-OB8EI

Daisy chain to other RTBs 2

+

1

DC-0 (+)

OUT-0 4

Group 0

3

DC-0 (+)

OUT-1 6

Group 0

5

DC-0 (+)

+

OUT-2 8

-

Isolated Wi ring

-

7

DC-0 (+)

OUT-3 10

Non -Isolat ed Wi ri ng

RTN OUT-0 11

DC-1 (+)

OUT-4 14

13

16

15

DC-1 (+)

OUT-5

Group 1

Group 1

DC-1 (+)

OUT-6 18

17

20

19

DC-1 (+)

Daisy chain to other RTBs

OUT-7

RTN OUT-1

RTN OUT-1

Daisy chain to other RTBs

+

2

1

OUT-0

4

3

OUT-0

DC-1 (+)

6

5

OUT-1

RTN OUT-1

8

7

OUT-1

DC-2 (+)

10

9

OUT-2

RTN OUT-2

12

11

OUT-2

DC-3 (+)

14

13

OUT-3

RTN OUT-3

16

15

OUT-3

DC-4 (+)

18

17

OUT-4

RTN OUT-4 DC-5 (+)

20

19

22

21

OUT-4 OUT-5

RTN OUT-5

24

23

OUT-5

DC-6 (+)

26

25

OUT-6

RTN OUT-6

28

27

OUT-6

DC-7 (+)

30

29

OUT-7

RTN OUT-7

32

31

OUT-7

Not used

34

33

Not used

Not used

36

35

Not used

9

RTN OUT-0 12

DC-0 (+) RTN OUT-0

Daisy chain to other RTBs

+

–

DC COM

– DC COM

NOTES: 1. All terminals with the same name are connected on the module. For example, DC COM can be connected to either terminal marked RTN OUT-1. 2. When you daisy chain from a group to another RTB, always connect the daisy chain to the terminal directly connected to the supply wire, as shown. Do not connect more than 2 wires to any single terminal. 3. This wiring example shows a single voltage source. 4. If separate power sources are used, do not exceed the specified isolation voltage.

NOTES 1. All terminals with the same name are connected together on the module. For example, the load can be connected to either terminal marked OUT-0. 2. When you daisy chain to other RTBs, always connect the daisy chain to the terminal directly connected to the supply wire, as shown in the example above. Do not connect more than 2 wires to any single terminal. 3. If separate power sources are used, do not exceed the specified isolation voltage.

Publication CIG-WD001B-EN-P - May 2005

Page 78

7-18

1756 ControlLogix I/O Modules

1756-OC8

1756-OF4 – Current Applications

Daisy chain to other RTBs 2

1

4

3

DC-0 (+)

OUT-0

DC-0 (+)

OUT-1

Group 0

6

13

Group 1

15

DC-1(+)

11

14

13

16

15

DC-1(+)

18

17

20

19

Not used

IOUT-2

RTN

OUT-7

RTN OUT-1

RTN

Not used

RTN OUT-1

Shield ground VOUT-2

OUT-6

19

12

IOUT-1

OUT-5

20

9

Not used

DC-1(+)

17

10

VOUT-1

OUT-4

18

7

Not used

11

DC-1(+)

16

8

Current output load

A RTN

RTN OUT-0

Group 1

5

Not used

9

RTN OUT-0

14

6 i

IOUT-0

OUT-3

12

3

RTN

7

DC-0 (+) 10

4

VOUT-0

OUT-2 8

1

Not used

Group 0

5

DC-0 (+)

2

Not used

VOUT-3

Not used

IOUT-3

Daisy chain to other RTBs

–

+

DC COM NOTES:

1. All terminals with the same name are connected together on the module. For example, DC COM can be connected to either terminal marked RTN OUT-1. 2. When you daisy chain from a group to another RTB, always connect the daisy chain to the terminal directly connected to the supply wire, as shown above. Do not connect more than 2 wires to any single terminal.

NOTES: 1. Place additional loop devices (e.g strip chart recorders) at the A location shown above. 2. Do not connect more than 2 wires to any single terminal. 3. All RTN terminals are connected internally.

3. This wiring example shows a single voltage source. 4. If separate power sources are used, do not exceed the specified isolation voltage.

1756-OF4 – Voltage Applications 2

2

3

Not used 6

RTN 7

10

9

12

11

14

13

Not used

IOUT-1

Not used

VOUT-2

Not used 16

18

17

20

19

Not used

Not used

RTN

OUT-5

IOUT-3

NOTES: 1. Do not connect more than 2 wires to any single terminal. 2. All RTN terminals are connected internally.

Publication CIG-WD001B-EN-P - May 2005

8

7

10

9

12

11

14

13

OUT-2

ALT-2 RTN-2 Not used 16

15

18

17

20

19

OUT-4

ALT-5 RTN-5

NOTES:

User Analog Output Device

RTN-0

RTN-3

IOUT-2

VOUT-3

5

ALT-3

15

RTN

6

OUT-3

Shield ground i

ALT-0

RTN-1

VOUT-1

Not used

3

ALT-1

–

5

8

OUT-0 4

IOUT-0

RTN

1

OUT-1

VOUT-0 4

Not used

+

1

Not used

1756-OF6CI – 0 - 550Ω Applications

ALT-4 RTN-4

1. Place additional devices anywhere in the loop. 2. Do not connect more than 2 wires to any single terminal.

Shield Ground

Page 79

1756 ControlLogix I/O Modules

1756-OF6VI

1756-OF6CI – 551 - 1000Ω Applications 2

1

OUT-1

2 OUT-0

4

User Analog Output Device

ALT-0 6

OUT-0 4

RTN-0 8

10

9

12

11

14

13

ALT-3

18

ALT-4 20

12

11

14

13

Not used RTN-2

16

15

18

17

20

19

OUT-4 Not used

RTN-4

RTN-5 NOTES:

RTN-4

1. Place additional devices anywhere in the loop. 2. Do not connect more than 2 wires to any single terminal.

NO TE S: Do not connect more than 2 wires to any single terminal.

1756-OF8 – Voltage Applications

1756-OF8 – Current Applications 2

2

1

VOUT-0

VOUT-4 4

IOUT-0 6

A

5

RTN

Current output load

RTN 8

VOUT-1 10

9

12

11

14

13

16

15

IOUT-6

RTN 18

5

IOUT-0

– RTN

8

7

10

9

VOUT-1 Shield ground IOUT-1 12

11

14

13

16

15

18

17

20

19

Not used

VOUT-2

Not used

IOUT-2 RTN

RTN

17

VOUT-7

VOUT-3 20

6

RTN

Shield ground

IOUT-2

RTN

3

Not used

VOUT-2

VOUT-6

4

Not used

IOUT-1

IOUT-5

VOUT-0

Not used

7

VOUT-5

+

1

Not used i

3

IOUT-4

IOUT-7

Shield Ground Not used

Not used

19

RTN-5

9

OUT-5

17

ALT-5

10

Not used

OUT-4

–

OUT-2

RTN-3

15

OUT-5

7

RTN-0

Shield Ground Not used

16

8

Not used

RTN-2

Not used

5

OUT-3

ALT-2

RTN-3

6

RTN-1

OUT-2

User Analog Output Device

Not used

7

OUT-3

3

Not used

5

RTN-1

+

1

OUT-1 i

3

ALT-1

7-19

Not used

VOUT-3

19

IOUT-3

NOTES: 1. Place additional loop devices (e.g strip chart recorders) at the A location shown above. 2. Do not connect more than 2 wires to any single terminal. 3. All RTN terminals are connected internally.

Not used

IOUT-3

NOTES: 1. Do not connect more than 2 wires to any single terminal. 2. All RTN terminals are connected internally.

Publication CIG-WD001B-EN-P - May 2005

Page 80

7-20

1756 ControlLogix I/O Modules

1756-OG16

1756-OH8I Isol ated W iri ng

DC power wire + 5V dc power

2

–

OUT-0 4

OUT-2 6

5

OUT-5 8

7

10

9

12

11

DC COM 0

OUT-9

OUT-8 14

13

16

15

OUT-11 Capacitor 0.01µ F typical (See notes below)

-

OUT-6

DC-0(+)

–

+

OUT-4

OUT-7 I/O wire

-

3

OUT-3

+

+

1

OUT-1

Non-Isol ated Wi ri ng

OUT-10

OUT-13

OUT-12 18

17

OUT-15

OUT-14 20

DC-1(+)

19

Daisy chain to other RTBs

DC COM 1

GENERAL NOTES: 1. We recommend you use Belden M 8761 cable where shielded cables are shown. 2. Do not connect more than two wires to any single terminal. CE REQUIREMENT NOTES: 1. DC power wire and I/O wire should not exceed 10m (30ft) in length. 2. The 0.01µ F capacitors shown must be rated for 2000V dc.

Daisy chain to other RTBs

DC-0 (+)

2

1

OUT-0

RTN OUT-0

4

3

OUT-0

DC-1 (+)

6

5

OUT-1

RTN OUT-1 DC-2 (+)

8

7

10

9

OUT-1 OUT-2

RTN OUT-2

12

11

OUT-2

DC-3 (+)

14

13

OUT-3

RTN OUT-3

16

15

OUT-3

DC-4 (+)

18

17

OUT-4

RTN OUT-4

20

19

OUT-4

DC-5 (+)

22

21

OUT-5

RTN OUT-5

24

23

OUT-5

DC-6 (+)

26

25

OUT-6

RTN OUT-6

28

27

OUT-6

DC-7 (+)

30

29

OUT-7

RTN OUT-7

32

31

OUT-7

Not used

34

33

Not used

Not used

36

35

Not used

+

NOTES

1. All terminals with the same name are connected together on the module. For example, the load can be connected to either terminal marked OUT-0. 2. When you daisy chain to other RTBs, always connect the daisy chain to the terminal directly connected to the supply wire, as shown in the example above. Do not connect more than 2 wires to any single terminal. 3. If separate power sources are used, do not exceed the specified isolation voltage.

1756-ON8

1756-OV16E

Daisy chain to other RTBs 2

4

Group 0

OUT-1 5

8

7

10

9

12

11

L1-0

OUT-2

L1-0

14

18

17

L1-1

8

7

10

9

12

11

14

13

16

15

18

17

OUT-4

OUT-5

RTN OUT-0 OUT-8

OUT-9

OUT-10

OUT-11

Group 1

Group 1

Group 0

OUT-6

OUT-12

OUT-13

Group 1

OUT-14

OUT-15 20

OUT-6

L1-1

5

DC-0(+)

OUT-5 15

6

OUT-7

13

16

3

OUT-2

OUT-4

L1-1

19

RTN OUT-1

DC-1(+)

OUT-7 20

L1-1

Group 0

Not used

L1-1

Group 1

Group 0

OUT-3

L1-0

4

OUT-3

3

6

1

OUT-0

OUT-0

L1-0

2

OUT-1

1

L1-0

– DC COM

19

Not used

L2

+

– DC COM

L1

NOTES: 1. All terminals with the same name are connected together on the module. For example, L1 can be connected to any terminal marked L1-1. 2. When you daisy chain from a group to another RTB, always connect the daisy chain to the terminal directly connected to the supply wire, as shown above. Do not connect more than 2 wires to any single terminal. 3. This wiring example shows a single voltage source.

Publication CIG-WD001B-EN-P - May 2005

Daisy chain to other RTBs

Daisy chain to other RTBs

NOTES: 1. When you daisy chain from a group to another RTB, always connect the daisy chain to the terminal directly connected to the supply wire, as shown above. Do not connect more than 2 wires to any single terminal. 2. This wiring example shows a single voltage source. 3. If separate power sources are used, do not exceed the specified isolation voltage.

Page 81

1756 ControlLogix I/O Modules

1756-OW16I

1756-OV32E

Isol ated w iring L1-0

L1-0 L1-1 L1-2 L1-2 L1-3 DC-4 (+) L1-4 L1-5 L1-6 Jumper bar - Cut to length L1-7 (Part number 97739201) L1-8 L1-9 L1-10 L1-11 Non -isol ated L1-12 wi ring L1-13 L1-14 L1-15 L1-15 L1 Not used

2

1

4

3

6

5

8

7

10

9

12 11 14 13 16 15 18 17 20 19 22 21 24 23 26 25 28 27 30 29 32 31 34 33 36 35

L2-0

OUT-0 OUT-1 N.O. OUT-2 N.O. OUT-3 N.O. OUT-4 N.O. OUT-5 N.O. OUT-6 N.O. OUT-7 N.O. OUT-8 N.O. OUT-9 N.O. OUT-10 N.O. OUT-11 N.O. OUT-12 N.O. OUT-13 N.O. OUT-14 N.O. OUT-15 N.O Not used Not used

Daisy chain to other RTBs

L2-2 DC-4 (-)

Group 0

Group 1

L2

Daisy chain to other RTBs OUT-1 OUT-3 OUT-5

2

1

4

3

6

5

OUT-7 OUT-9 OUT-11

8

7

10

9

14 13

OUT-17 OUT-19 OUT-21

20 19

OUT-23 OUT-25 OUT-27

26 25

OUT-29 OUT-31 DC-1(+)

32 31

24 23

4

3

6

5

8

7

10

9

12 11 14 13 16 15 18 17 20 19 22 21 24 23 26 25 28 27 30 29 32 31 34 33 36 35

OUT-22 OUT-24 OUT-26

28 27 30 29

Group 1

OUT-28 OUT-30 RTN OUT-1

34 33 36 35

_ DC COM

NOTES: 1. When you daisy chain from a group to another RTB, always connect the daisy chain to the terminal directly connected to the supply wire, as shown above. 2. This wiring example uses a single voltage source. 3. If separate power sources are used, do not exceed the specified isolation voltage 4. Do not physically connect more than two wires to a single RTB terminal.

Isol ated wi ring 1

OUT-16 OUT-18 OUT-20

22 21

1756-OX8I

Isol ated w iring 2

Group 0

OUT-12 OUT-14 RTN OUT-0

18 17

1756-OW16I

L1-0 L1-1 L1-2 L1-2 L1-3 DC-4 (+) L1-4 L1-5 L1-6 Jumper bar - Cut to length L1-7 (Part number 97739201) L1-8 L1-9 L1-10 L1-11 Non -isol ated L1-12 wi ring L1-13 L1-14 L1-15 L1-15 L1 Not used

OUT-6 OUT-8 OUT-10

16 15

+

NOTES: 1. All terminals with the same name are connected together on the module. For example, L1 can be connected to either terminal marked L1-15. 2. When daisy chaining the second L1-15 terminal to other RTBs, always connect the daisy chain to the terminal directly connected to the supply wire, as shown in the example above. Do not connect more than 2 wires to any single terminal. 3. If separate power sources are used, do not exceed the specified isolation voltage.

OUT-0 OUT-2 OUT-4

12 11

OUT-13 OUT-15 DC-0(+)

Daisy chain to other RTBs

L1-0

7-21

L2-0

OUT-0 OUT-1 N.O. OUT-2 N.O. OUT-3 N.O. OUT-4 N.O. OUT-5 N.O. OUT-6 N.O. OUT-7 N.O. OUT-8 N.O. OUT-9 N.O. OUT-10 N.O. OUT-11 N.O. OUT-12 N.O. OUT-13 N.O. OUT-14 N.O. OUT-15 N.O Not used Not used

L1-0

OUT-0 N.C.

3

OUT-0 N.O.

6

5

L1-1

8

7

OUT-1 N.O.

L1-2

10

9

OUT-2 N.C.

L1-2

12 11

OUT-2 N.O.

L1-3

14 13

OUT-3 N.C.

L1-3

16 15

OUT-3 N.O.

L1-4

18 17

OUT-4 N.C.

L1-4

20 19

OUT-4 N.O.

L1-5

22 21

OUT-5 N.C.

L1-5

24 23

OUT-5 N.O.

L1-6

26 25

OUT-6 N.C.

L1-6

28 27

OUT-6 N.O.

L1-7

30 29

OUT-7 N.C.

L1-7

32 31

OUT-7 N.O

L1-7

34 33

Not used

Not used

36 35

Not used

Jumper bar - Cut to length (Part number 97739201)

L1

1

4

OUT-1 N.C.

DC-2 (+)

Non- isolated wi ring

2

L1-0 L1-1

L2-2 DC-4 (-)

L1-0

NOTES: 1. All terminals with the same name are connected together on the module. For example, L1 can be connected to either terminal marked L1-15. 2. When daisy chaining the second L1-15 terminal to other RTBs, always connect the daisy chain to the terminal directly connected to the supply wire, as shown in the example above. Do not connect more than 2 wires to any single terminal. 3. If separate power sources are used, do not exceed the specified isolation voltage.

DC-2 (-)

L2

L2 Daisy chain to other RTBs

L2-0

Daisy chain to other RTBs

NOTES: 1. All terminals with the same name are connected together on the module. For example, L1-0 can be connected to either terminal marked L1-0. 2. When you use the third L1-7 terminal to daisy chain to other RTBs, always connect the daisy chain to the terminal directly connected to the supply wire, as shown in the example above. Do not connect more than 2 wires to any single terminal. 3. If separate power sources are used, do not exceed the specified isolation voltage.

Publication CIG-WD001B-EN-P - May 2005

Page 82

7-22

1756 ControlLogix I/O Modules

1756-PLS Resolver Module 2

1

Do not use

Do not use 4

3

6

5

Do not use

Do not use Do not use

10

12

11

14

13

G (S4)

A

White

R1

19 (Reference-)

B

Black of white

R2

Do not use

1 4 ( Sine+ )

F

Black of red

S3

16 (S ine-)

D

Red

S1

18 (Cosine+)

E

Green

S2

20 (Cosi ne- )

G

Black of green

S4

Do not use Do not use

Sine +

E (S2)

Resolver Signal Name

17 (Refere nce+)

Do not use

Do not use

D (S1)

845-CA-E-25 845-CA-F-25 Connector Cables Color Pairs

Do not use

9

Do not use

F ( S3)

846-SJxNxCG-R3 846-SAxNxCG-R3 Allen-Bradley Resolvers Designation

7

8

Do not use

Allen-Brad ley Resolver 846-S JDA1CG-R3-C

RTB Terminal Number

16

15

18

17

20

19

Do not use

Sine –

Reference +

Cosine +

Reference –

Cosine –

A (R1) B (R2)

NOTE: Do not connect more than 2 wires to any single terminal.

1756-PLS Left Section I/O Module 2

1

OUTPUT 0 4

3

6

5

8

7

10

9

12

11

INPUT 2

OUTPUT 3

INPUT 3

DC PWR 0- 3

+

13

16

15

OUTPUT 5

INPUT 6 18

17

20

19

INPUT 7

OUTPUT 7

6

5

8

7

10

9

12

11

14

13

16

15

18

17

20

19

INPUT 8 INPUT 9 INPUT 10 INPUT 11

DC PWR 8- 11

10- 30V dc

DC COM 8-11

OUTPUT 12

INPUT 12

OUTPUT 13

INPUT 5

OUTPUT 6

3

OUTPUT 11

INPUT 4 14

4

OUTPUT 10

_

DC COM 0-3

OUTPUT 4

1

OUTPUT 9

INPUT 1

OUTPUT 2

2

OUTPUT 8

INPUT 0

OUTPUT 1

DC PWR 4- 7

1756-PLS Right Section I/O Module

+

INPUT 13 INPUT 14

OUTPUT 14 OUTPUT 15

_

DC PWR 12- 15

DC COM 4- 7

INPUT 15 DC COM 12-15

+ NOTE: Do not connect more than 2 wires to any single terminal.

_

NOTE: Do not connect more than 2 wires to any single terminal.

Publication CIG-WD001B-EN-P - May 2005