Page 93
Chapter
9
1762 I/O on MicroLogix 1200 Controllers Unlike the other product sections in this document, this section does not list the 1762 catalog numbers in alphabetical order; instead, we first list the embedded controller I/O catalog numbers first because of their regular use in most 1762 applications. As you use this section, keep the following in mind:
IMPORTANT
• Catalog numbers that begin with 1762-Lxx (e.g. 1762-L24AWA) represent embedded I/O products • Catalog numbers that begin in any combination other than 1762-Lxx (e.g. 1762-IA8) represent expansion I/O products
1762-L24AWA 1762-L24AWAR Input Wiring L1a
Terminal Groupings
L1b L2b
NC NC
IN 0
COM 0
COM 1
IN 2 IN 1
Inpu t Gro u p Group 0 Group 1
IN 3
IN 5 IN 4
IN 7 IN 6
IN 9 IN 8
IN 11
IN 10
C o m m o n T e rm in al AC COM 0 AC COM 1
Inpu t Te rm in a ls I/0 through I /3 I/4 through I /13
IN 13
IN 12
NC - No connection
L2a L1a
L1b
Output Wiring Terminal Groupings -DCa
L2a
L2b
L1c
L2c
Ou tput Group Group 0 Group 1 Group 2 Group 3 Group 4
L2d
L2 CR
CR
L1
VAC L1
VAC OUT 0 OUT 1 OUT 2 NEUT VAC DC 0
VAC DC 1
VAC DC 2
VAC OUT 5 OUT 6 OUT 8 DC 3
OUT 3 OUT 4
VAC DC 4
CR
Voltage Te rm in a l VAC/VD C 0 VAC/ VDC 1 VAC/VD C 2 VAC/ VDC 3 VAC/VD C 4
Ou tput Te rm in al O/ 0 O/1 O/2 through O/3 O4 through O /5 O/6 through O/9
OUT 7 OUT 9
CR
L2d +DCa
1
L1a
L1b
L2b
L2c
L1d
Publication CIG-WD001B-EN-P - May 2005
Page 94
9-2
1762 I/O on MicroLogix 1200 Controllers
1762-L24BWA 1762-L24BWAR Sinking Input Wiring -DCb +DCa
+DC
+DCb Terminal Groupings
+24 VDC
IN 0
24 COM COM 0
IN 2 COM 1
IN 1
IN 3
IN 5
IN 4
IN 7 IN 6
IN 9
IN 8
IN 11
IN 10
IN 13
Inpu t Grou p
C o m m o n T e rm i n al
Inpu t Te rm in a l
Group 0 Group 1
DC COM 0 DC COM 1
I/0 through I /3 I/4 through I /13
IN 12
The 24V dc sensor power source must not be used to power output circuits. It should only be used to power input devices (e.g. sensors, switches).
+DCb -DC
-DCa +DCa
Sourcing Input Wiring +DCb -DCa
24V dc Sensor Power
-DCb Terminal Groupings
+DC
+24 VDC
IN 0
24 COM COM 0
IN 1
IN 2 COM 1 IN 3
IN 5
IN 4
IN 7 IN 6
IN 9 IN 11
IN 8
IN 10
IN 13
Inpu t Grou p
C o m m o n T e rm in al
Inpu t Te rm in a l
Group 0 Group 1
DC COM 0 DC COM 1
I/0 through I /3 I/4 through I /13
IN 12
The 24V dc sensor power source must not be used to power output circuits. It should only be used to power input devices (e.g. sensors, switches).
-DCb -DC +DCa
-DCa
Output Wiring -DCa
L2a
L2b
L1c
L2c
Terminal Groupings
L2d
L2 CR
CR
L1
VAC L1
VAC OUT 0 OUT 1 OUT 2 NEUT VAC DC 0
VAC DC 1
VAC DC 2
VAC OUT 5 OUT 6 OUT 8 DC 3
OUT 3 OUT 4
VAC DC 4
CR
OUT 7 OUT 9
CR
L2d +DCa
L1a
L1b
Publication CIG-WD001B-EN-P - May 2005
L2b
L2c
L1d
Ou tput Group Group 0 Group 1 Group 2 Group 3 Group 4
Voltage Termin a l VAC/VD C 0 VAC/ VDC 1 VAC/VD C 2 VAC/ VDC 3 VAC/VD C 4
Output Te rm in al O/0 O/1 O/2 through O/3 O4 through O /5 O/6 through O/9
Page 95
1762 I/O on MicroLogix 1200 Controllers
9-3
1762-L24BXB 1762-L24BXBR Sinking Input Wiring
NC
+DCb
IN 0
NC
Terminal Groupings
-DCb
+DCa
IN 2 COM 1
COM 0
IN 1
-DCa
+DCa
IN 3
IN 5
IN 4
IN 7
IN 6
IN 9
IN 8
IN 11
IN 10
IN 13
IN 12
Input Grou p
C o m m o n T e rm in al
Inpu t Te rm in a l
Group 0 Group 1 Group 0
DC COM 0 DC COM 1 AC COM 0
I/0 through I /3 I/4 through I /13 I/0 through I /3
NC - No connection
+DCb
Sourcing Input Wiring -DCa
0
NC NC
+DCb
IN 2
COM0
IN 1
+DCa
-DCa
IN 5
COM1
IN 3
Terminal Groupings
-DCb
IN 4
IN 7
IN 6
IN 9
IN 8
IN 11
IN 10
IN 13
IN 12
Input Grou p
C o m m o n T e rm in al
Inpu t Te rm in a l
Group 0 Group 1 Group 0
DC COM 0 DC COM 1 AC COM 0
I/0 through I /3 I/4 through I /13 I/0 through I /3
NC - No connection
-DCb
Output Wiring -DCa +DC
+24 VDC
-DCb
L1d
-DCc
Terminal Groupings
L2d
-DC
VDC NEUT
OUT 0
VAC DC 0
OUT 1 VAC DC 1
CR
CR
OUT 2
OUT 4
VDC 2
OUT 3
CR
+DCa +DCb
+DCc
-DCc
OUT 6
OUT 5
VAC DC 3
COM 2
OUT 8
OUT 7
OUT 9
Ou tput Grou p
Voltage Te rmin a l
Ou tput Te rm i n al
Group 0 Group 1 Group 2 Group 3
VAC/VD C 0 VAC/ VDC 1 VD C 2, VD C C OM 2 VAC/ VDC 3
O/ 0 O/1 O/2 thr ough O/6 O/7 thr ough O/9
CR
L2d
Publication CIG-WD001B-EN-P - May 2005
Page 96
9-4
1762 I/O on MicroLogix 1200 Controllers
1762-L40AWA 1762-L40AWAR Input Wiring L1a
L1b
Terminal Groupings
L1c Input Group Group 0 Group 1 Group 2
L2b COM IN 5 IN 7 IN 8 IN 10 IN 12 IN 14 IN 16 IN 18 IN 20 IN 22 NC IN 0 IN 2 1
NC
COM IN 1 0
IN 3
IN 4
IN 6
COM 2
Common Terminal AC COM 0 AC COM 1 AC COM 2
Input Terminal I/0 through I/3 I/4 through I/7 I/8 through I/23
IN 9 IN 11 IN 13 IN 15 IN 17 IN 19 IN 21 IN 23
NC - No connection L2a L2c
L1a L1b
L1c
Output Wiring Terminal Groupings L1d L2a
L2b
L1f L2d
L2c
Output Group
L2f
L2e
L2 CR
L1 VAC L1
VAC NEUT
OUT 0 VAC DC 0
OUT 1 VAC DC 1
OUT 2 VAC DC 2
CR
VAC DC 3 OUT 3
OUT 5 OUT 4
L2c L1b
L1c
Publication CIG-WD001B-EN-P - May 2005
OUT 6
OUT 8 VAC DC 4
OUT 10 OUT 9
L2d
CR
VAC DC 5 OUT 11
L2e L1e
OUT 15
OUT 13 OUT 12
OUT 14
CR
CR
CR
CR
L1a
OUT 7
CR
L2f
Group 0 Group 1 Group 2 Group 3 Group 4 Group 5
Voltage Terminal VAC/VD C 0 VAC/ VDC 1 VAC/VD C 2 VAC/ VDC 3 VAC/VD C 4 VAC/ VDC 5
Output Terminal O/0 O/1 O/2 thr ough O/3 O/4 thr ough O/7 O/8 thr ough O/11 O/12 thr ough O/15
Page 97
1762 I/O on MicroLogix 1200 Controllers
9-5
1762-L40BWA 1762-L40BWAR Sinking Input Wiring
+DC
+DCa
+24 VDC
IN 0
Terminal Groupings
+DCb
-DCb
Input Group Group 0 Group 1 Group 2
+DCc
24 COM
COM 0
-DC
-DCa
COM 1
IN 2 IN 1
IN 5
IN 3
IN 4
IN 7
IN 8
COM 2
IN 6
IN 10 IN 9
IN 12
IN 11
IN 14
IN 13
IN 16
IN 15
IN 18
IN 17
IN 20
IN 19
Common Terminal DC COM 0 DC COM 1 DC COM 2
Input Terminal I/0 through I/3 I/4 through I/7 I/8 through I/23
IN 22
IN 21
IN 23
The 24V dc sensor power source must not be used to power output circuits. It should only be used to power input devices (e.g. sensors, switches). +DCc
-DCc
+DCb
+DCa
Sourcing Input Wiring Terminal Groupings -DCb
+DCb -DCa
Input Group Group 0 Group 1 Group 2
-DCc
+DC
+24 VDC 24 COM
IN 0
COM 0
-DC
IN 2 IN 1
COM 1 IN 3
IN 5 IN 4
-DCa
IN 7 IN 6
IN 8
COM 2
IN 10 IN 9
IN 12
IN 11
IN 14
IN 13
IN 16
IN 15
IN 18
IN 17
IN 20
IN 19
Common Terminal DC COM 0 DC COM 1 DC COM 2
Input Terminal I/0 through I/3 I/4 through I/7 I/8 through I/23
IN 22
IN 21
IN 23
The 24V dc sensor power source must not be used to power output circuits. It should only be used to power input devices (e.g. sensors, switches).
-DCb
-DCc
+DCa
+DCc
Output Wiring Terminal Groupings L1d L2a
L2b
L1f L2d
L2c
Output Group
L2f
L2e
L2 CR
L1 VAC L1
VAC NEUT
OUT 0 VAC DC 0
OUT 1 VAC DC 1
OUT 2 VAC DC 2
CR
VAC DC 3 OUT 3
OUT 5 OUT 4
L2c L1b
L1c
OUT 6
OUT 8 VAC DC 4
OUT 10 OUT 9
L2d
CR
VAC DC 5 OUT 11
L2e
OUT 15
OUT 13 OUT 12
Voltage Terminal VAC/VD C 0 VAC/ VDC 1 VAC/VD C 2 VAC/ VDC 3 VAC/VD C 4 VAC/ VDC 5
Output Terminal O/ 0 O/1 O/2 through O/3 O/4 through O/7 O/8 through O/11 O/12 through O/15
OUT 14
CR
CR
CR
CR
L1a
OUT 7
CR
Group 0 Group 1 Group 2 Group 3 Group 4 Group 5
L2f
L1e
Publication CIG-WD001B-EN-P - May 2005
Page 98
9-6
1762 I/O on MicroLogix 1200 Controllers
1762-L40BXB 1762-L40BXBR Sinking Input Wiring Terminal Groupings
-DCb +DCb
+DCa
+DCc
IN 0
NC
COM 0
NC
IN 2 IN 1
COM 1 IN 3
IN 5 IN 4
IN 7
IN 8
IN 12
IN 14
IN 16
IN 18
IN 20
Common Terminal DC COM 0 DC COM 1 DC COM 2
Input Terminal I/0 through I/3 I/4 through I/7 I/8 through I/23
IN 22
NC - No connection
COM 2
IN 6
IN 10
Input Group Group 0 Group 1 Group 2
IN 9 IN 11
IN 13
IN 15
IN 17
IN 19
IN 21
IN 23
+DCc +DCa
-DCa
+DCb -DCc
Sourcing Input Wiring Terminal Groupings
+DCb -DCb
-DCa
-DCc
NC NC
IN 0
COM 0
+DCa
IN 2 IN 1
COM 1
IN 5
IN 3
IN 4
IN 7 IN 6
IN 8
IN 10
IN 12
IN 14
IN 16
IN 18
IN 20
Input Group Group 0 Group 1 Group 2
Common Terminal DC COM 0 DC COM 1 DC COM 2
Input Terminal I/0 through I/3 I/4 through I/7 I/8 through I/23
IN 22
NC - No connection
COM 2
IN 9
IN 11
IN 13
IN 15
IN 17
IN 19
IN 21
IN 23
-DCc
-DCa
-DCb
+DCc
Output Wiring
-DCa
-DC
-DCc
-DCb
CR
+DC
+24 VDC
VDC NEUT
OUT 0
VAC DC 0
OUT 1 VAC DC 1
VDC 2
OUT 4 OUT 3
OUT 8
OUT 6 OUT 5
CR
+DCe
COM
OUT 7
OUT 9
CR
CR
OUT 10 VAC DC3
CR
VAC DC 4 OUT 11
CR
-DCd
+DCa +DCb +DCc
Publication CIG-WD001B-EN-P - May 2005
+DCd
Terminal Groupings
-DCe
CR
CR
OUT 2
-DCd
OUT 15
OUT 13 OUT 12
OUT 14
CR
-DCe
Ou tp ut G rou p Group 0 Group 1 Group 2 Group 3 Group 4
Vo lta ge Te rm in a l VAC/VD C 0 VAC/VDC 1 VD C 2 , VD C C OM 2 VAC/VDC 3 VAC/VD C 4
O u tp ut Te rm in al O/0 O/1 O/2 through O/9 O/10 through O/11 O/12 through O/15
Page 99
1762 I/O on MicroLogix 1200 Controllers
9-7
1762-IA8 L1 Be careful when stripping wires. Wire fragments that fall into a module could cause damage when power is applied. Once wiring is complete, ensure the module is free of all metal fragments.
IN 0 IN 1 IN 2 IN 3 100/120V ac
IN 4
A current limiting resistor can be used to limit inrush current; however, the operating characteristics of the ac input circuit will be affected. If a 6.8KΩ resistor is placed in series with the input, the inrush current is reduced to 35 mA. In this configuration the minimum on-state voltage increases to 92V ac. Before adding the resistor in a hazardous environment, be sure to consider the operating temperature of the resistor and the temperature limits of the environment. The operating temperature of the resistor must remain below the temperature limit of the environment.
IN 5 IN 6 IN 7 AC COM AC COM
L2
Commons are connected internally.
Also, this product is intended to be mounted to a well-grounded mounting surface such as a metal panel. Additional grounding connections from the module’s mounting tabs or DIN rail (if used) are not required unless the mounting surface cannot be grounded.
1762-IF2OF2
Differential Sensor Transmitter Types
IN 0 +
Analog Sensor
IN 0 IN 1 + IN 1 V out 0 I out 0
Analog Load
V out 1 I out 1 COM COM
2-Wire Transmitter Power + Supply (1)
Commons connected internally.
Transmitter
+
-
Module IN +
-
IN COM
3-Wire Transmitter Power + Supply(1)
Analog outputs may fluctuate for less than a second when power is applied or removed. This characteristic is common to most analog outputs. While the majority of loads will not recognize this short signal, it is recommended that preventive measures be taken to ensure that connected equipment is not affected.
Transmitter Supply
Signal
All power supplies rated N.E.C. Class 2. Module IN +
-
Grounding the cable shield at the module end only usually provides sufficient noise immunity. However, for best cable shield performance, earth ground the shield at both ends, using a 0.01µF capacitor at one end to block AC power ground currents, if necessary.
IN -
Select the input type, current or voltage, using the switch located on the module’s circuit board and the input type/range selection bits in the Configuration Data File.
COM
The output type selection, current or voltage, is made by wiring to the appropriate terminals, Iout or Vout, and by the type/range selection bits in the Configuration Data File.
4-Wire Transmitter Power + Supply(1)
-
Transmitter Supply
+ -
Signal
Module
+ -
IN + IN COM
Publication CIG-WD001B-EN-P - May 2005
Page 100
9-8
1762 I/O on MicroLogix 1200 Controllers
1762-IF4 Differential Sensor Transmitter Types
IN0 +
Analog Sensor
IN0 IN1 + IN1 IN2 + IN2 IN3 + IN3 -
COM
COM
2-Wire Transmitter
Commons connected internally.
Grounding the cable shield at the module end only usually provides sufficient noise immunity. However, for best cable shield performance, earth ground the shield at both ends, using a 0.01µF capacitor at one end to block AC power ground currents, if necessary.
Transmitter
+
Power + Supply (1)
Module
-
IN +
-
IN COM
All power supplies rated N.E.C. Class 2. Select the input type, current or voltage, using the switch located on the module’s circuit board and the input type/range selection bits in the Configuration Data File.
Transmitter
3-Wire Transmitter
Supply
Power + Supply(1)
Module
Signal
IN +
-
IN COM
Transmitter
4-Wire Transmitter
Supply
Power + Supply(1)
+ -
-
Signal
Module
+ -
IN + IN COM
1762-IQ16 +DC (sinking) -DC (sourcing)
IN 0 IN 1 IN 2 IN 3 IN 4
24V dc
Be careful when stripping wires. Wire fragments that fall into a module could cause damage when power is applied. Once wiring is complete, ensure the module is free of all metal fragments.
IN 5 IN 6 IN 7
-DC (sinking)
DC COM 0
+DC (sinking)
+DC (sourcing)
-DC (sourcing) IN 8 IN 9 IN 10 24V dc
IN 11 IN 12 IN 13
-DC (sinking)
IN 14 IN 15
+DC (sourcing)
Publication CIG-WD001B-EN-P - May 2005
Miswiring of the module to an AC power source will damage the module.
DC COM 1
Sinking/Sourcing Inputs - Sourcing/sinking describes the current flow between the I/O module and the field device. Sourcing I/O circuits supply (source) current to sinking field devices. Sinking I/O circuits are driven by a current sourcing field device. Field devices connected to the negative side (DC Common) of the field power supply are sinking field devices. Field devices connected to the positive side (+V) of the field supply are sourcing field devices. Also, this product is intended to be mounted to a well-grounded mounting surface such as a metal panel.
Page 101
1762 I/O on MicroLogix 1200 Controllers
9-9
1762-IQ8 +D C (sinking) -DC (sourcing)
Be careful when stripping wires. Wire fragments that fall into a module could cause damage when power is applied. Once wiring is complete, ensure the module is free of all metal fragments.
IN 0 IN 1 IN 2 IN 3 24V dc
Miswiring of the module to an AC power source will damage the module.
IN 4 IN 5 IN 6 IN 7 DC COM DC COM
-DC (sinking) +D C (sourcing)
Commons are connected internally.
Sinking/Sourcing Inputs - Sourcing/sinking describes the current flow between the I/O module and the field device. Sourcing I/O circuits supply (source) current to sinking field devices. Sinking I/O circuits are driven by a current sourcing field device. Field devices connected to the negative side (DC Common) of the field power supply are sinking field devices. Field devices connected to the positive side (+V) of the field supply are sourcing field devices. Also, this product is intended to be mounted to a well-grounded mounting surface such as a metal panel.
1762-IR4 2-Wire Potentiometer Interconnection
Cable Shield (to Ground)
EXC 2
Potentiometer Cable Shield (to Ground)
RTD EXC
SENSE 2
Return
Potentiometer
Sense Return
RTN 2 Belden 9501 Shielded Cable
NC
Belden 83503 or 9533 Shielded Cable
NC Cable Shield (to Ground)
Cable Shield (to Ground)
Potentiometer
RTD EXC
EXC 2 EXC 2
SENSE 2 Return
SENSE 2
RTN 2 NC
Run RTD and sense wires from the module to potentiometer terminal and tie terminal to one point.
RTD EXC
EXC 2
SENSE 2 RTN 2
1762-IR4 3-Wire Potentiometer Interconnection
Belden 9501 Shielded Cable
RTN 2 NC
TIP: The potentiometer wiper arm can be connected to either the EXC or return terminal depending on whether you want increasing or decreasing resistance.
TIP:
Run RTD and sense wires from the module to potentiometer terminal and tie terminal to one point.
RTD EXC Potentiometer
Sense Return Belden 83503 or 9533 Shielded Cable
The potentiometer wiper arm can be connected to either the EXC or return terminal depending on whether you want increasing or decreasing resistance.
IMPORTANT: Using 2-wire configurations does not permit the module to compensate for resistance error due to lead wire length. The resulting analog data includes the effect of this uncompensated lead wire resistance. The module continues to place the uncompensated analog data in the input data file, but the open-circuit status bit (OCx) is set in word 4 of the input data file for any enabled channel using a 2-wire configuration. These status bits may be used in the control program to indicate that the analog data includes error due to uncompensated lead wires.
Publication CIG-WD001B-EN-P - May 2005
Page 102
9-10
1762 I/O on MicroLogix 1200 Controllers
1762-IR4 2-Wire RTD
1762-IR4 3-Wire RTD
Cable Shield (to Ground)
Cable Shield (to Ground)
RTD EXC
RTD EXC
Return
Return
SENSE 2
SENSE 2
RTN 2
RTN 2 Belden 9501 Shielded Cable
NC
IMPORTANT:
RTD EXC
RTD EXC
Sense
Sense
Return
Return
EXC 2
EXC 2
NC
Belden 83503 or 9533 Shielded Cable
1762-IR4 4-Wire RTD
Using 2-wire configurations does not permit the module to compensate for resistance error due to lead wire length. The resulting analog data includes the effect of this uncompensated lead wire resistance. The module continues to place the uncompensated analog data in the input data file, but the open-circuit status bit (OCx) is set in word 4 of the input data file for any enabled channel using a 2-wire configuration. These status bits may be used in the control program to indicate that the analog data includes error due to uncompensated lead wires.
Cable Shield (to Ground) RTD EXC
RTD EXC
EXC 2 Sense
Sense
Return
Return
SENSE 2 RTN 2 NC
Belden 83503 or 9533 Shielded Cable Leave one sensor wire open.
1762-IT4
CJC sensor
CJC+
-
+ grounded thermocouple
IN 0- ungrounded thermocouple
+
IN 0+
CJC -
IN 1 +
IN 2+
IN 1-
IN 2- within 10V dc
+
IN 3+ IN 3-
- grounded thermocouple
COLD JUNCTION COMPENSATION To obtain accurate readings from each of the channels, the temperature between the thermocouple wire and the input channel must be compensated for. A cold junction compensating thermistor has been integrated in the terminal block. The thermistor must remain installed to retain accuracy.
Do not remove or loosen the cold junction compensating thermistor assembly. This assembly is critical to ensure accurate thermocouple input readings at each channel. The module will operate in the thermocouple mode, but at reduced accuracy if the CJC sensor is removed.
IMPORTANT: When using grounded and/or exposed thermocouples that are touching electrically conductive material, the ground potential between any two channels cannot exceed ±10V dc, or temperature readings will be inaccurate.
TIP:
When using an ungrounded thermocouple, the shield must be connected at the module end.
Publication CIG-WD001B-EN-P - May 2005
Page 103
1762 I/O on MicroLogix 1200 Controllers
9-11
1762-OA8 VAC 0
OUT 0 CR
L2
100 to 240V ac
OUT 1
CR
OUT 3
CR
OUT 4
CR
L2
OUT 2
VAC 1
L1 100 to 240V ac
L1
CR
OUT 5
CR
OUT 6
Be careful when stripping wires. Wire fragments that fall into a module could cause damage when power is applied. Once wiring is complete, ensure the module is free of all metal fragments. Miswiring of the module to an AC power source will damage the module. To limit the effects of leakage current through triac outputs, a loading resistor can be connected in parallel with your load. For typical 120V ac applications, use a 15k ohm, 2W resistor. For typical 240V ac applications, use a 15k ohm, 5W resistor.
OUT 7
1762-OB16 +DC
VDC+ CR CR
OUT 0 OUT 1
CR
OUT 3
CR
OUT 2 OUT 4
Be careful when stripping wires. Wire fragments that fall into a module could cause damage when power is applied. Once wiring is complete, ensure the module is free of all metal fragments.
OUT 5 CR
OUT 6
CR
OUT 7
CR
OUT 8
CR
OUT 9
CR
OUT 11
Miswiring of the module to an AC power source will damage the module.
24V dc (source)
OUT 10
Surge Suppression – Connecting surge suppressors across your external inductive load will extend the life of the relay contacts. For additional details, refer to Industrial Automation Wiring and Grounding Guidelines, Allen-Bradley publication 1770-4.1.
OUT 12 CR
OUT 13 OUT 14 OUT 15 DC COM
-DC
1762-OB8 +DC
+VDC CR
OUT 0
CR
OUT 2
OUT 1
CR
OUT 3
CR
OUT 4 OUT 5 CR
OUT 6
CR
OUT 7
24V dc (source)
Be careful when stripping wires. Wire fragments that fall into a module could cause damage when power is applied. Once wiring is complete, ensure the module is free of all metal fragments.
DC COM -DC
Publication CIG-WD001B-EN-P - May 2005
Page 104
9-12
1762 I/O on MicroLogix 1200 Controllers
1762-OF4 V out 0
Voltage Load
I out 0
Current Load
V out 1 I out 1 V out 2 I out 2 V out 3 I out 3 COM COM
Analog outputs may fluctuate for less than a second when power is applied or removed. This characteristic is common to most analog outputs. While the majority of loads will not recognize this short signal, it is recommended that preventive measures be taken to ensure that connected equipment is not affected.
TIP
Grounding the cable shield at the module end only usually provides sufficient noise immunity. However, for best cable shield performance, earth ground the shield at both ends, using a 0.01 µF capacitor at one end to block AC power ground currents, if necessary.
1762-OX6I L1-0
L1 OR +DC
OUT0 N.C.
L1 OR +DC
OUT0 N.O.
CR
OUT1 N.C.
CR
L1-1 OUT1 N.O.
L2 OR -DC
L1-2 L2 OR -DC
L2 OR -DC
CR
L1 OR +DC
OUT2 N.C. OUT2 N.O.
L1 OR +DC L2 OR -DC
CR
L1-3
Surge Suppression – Connecting surge suppressors across your external inductive load will extend the life of the relay contacts. For additional details, refer to publication 1770-4.1.
OUT3 N.C. OUT3 N.O.
L1 OR +DC
L1-4 OUT4 N.C.
CR
OUT4 N.O.
L2 OR -DC
L1-5 CR
L1 OR +DC
OUT5 N.C. OUT5 N.O.
Publication CIG-WD001B-EN-P - May 2005
This product is intended to be mounted to a well-grounded mounting surface such as a metal panel. Additional grounding connections from the module’s mounting tabs or DIN rail (if used) are not required unless the mounting surface cannot be grounded. For more information, refer to Industrial Automation Wiring and Grounding Guidelines, Allen-Bradley publication 1770-4.1.
L2 OR -DC
Page 105
1762 I/O on MicroLogix 1200 Controllers
9-13
1762-OW16 OUT 0 CR
L1 or +DC
VAC-VDC 0 OUT 1
CR
OUT 3
CR
OUT 5
CR
L2 or -DC
OUT 2 OUT 4
CR
OUT 6
CR
OUT 7
Be careful when stripping wires. Wire fragments that fall into a module could cause damage when power is applied. Once wiring is complete, ensure the module is free of all metal fragments.
VAC-VDC 1
L1 or +DC
OUT 8 CR
OUT 9
CR
OUT 11
CR
OUT 13
CR
OUT 15
CR
L2 or -DC Surge Suppression – Connecting surge suppressors across your external inductive load will extend the life of the relay contacts. For additional details, refer to Industrial Automation Wiring and Grounding Guidelines, Allen-Bradley publication 1770-4.1.
OUT 10 OUT 12
CR
OUT 14
1762-OW8
OUT 0 CR
L2 or - DC
L1 or +D C
OUT 1
CR
OUT 3
CR
L2 or -D C
OUT 2
VAC-VDC 1
L1 or +D C
VAC-VDC 0
CR
OUT 5
CR
OUT 6 OUT 7
OUT 4
CR
Be careful when stripping wires. Wire fragments that fall into a module could cause damage when power is applied. Once wiring is complete, ensure the module is free of all metal fragments.
Surge Suppression – Connecting surge suppressors across your external inductive load will extend the life of the relay contacts. For additional details, refer to Industrial Automation Wiring and Grounding Guidelines, Allen-Bradley publication 1770-4.1.
Publication CIG-WD001B-EN-P - May 2005
Page 106
9-14
1762 I/O on MicroLogix 1200 Controllers
Notes:
Publication CIG-WD001B-EN-P - May 2005