Page 111

Chapter

11

1769 Compact I/O Modules

1769-HSC – Differential Encoder applications

1769-HSC – Discrete Device applications

Cable(1)

+VDC

+VDC VS COM

GND

Power Supply

COM

Proximity Sensor

Power Supply

VS A1(+)

OUT

A1(–)

COM

Allen-Bradley 845H Series differential encoder

A

A1(+)

A

A1(–)

B

B1(+)

B

B1(–)

Z

Z1(+)

Z

Z1(–)

VS

Solid-State Switch OUT

R

1

B1(+)

COM

B1(–)

Z1(+) Z1(–)

COM

Photo-electric Sensor with Open Collector Sinking Output

Shield shield/housing Connect only if housing is electronically isolated from the motor and ground.

OUT

VS

Module Inputs

Earth Module Inputs

1. Refer to your encoder manual for proper cable type. The type of cable used should be twisted pair, individually shielded cable with a maximum length of 300m (1000 ft.).

1. External resistors are required if they are not internal to the sensor. The pull-up resistor (R) value depends on the power supply value. The table below shows the maximum resistor values for typical supply voltages. To calculate the maximum resistor value, use the following formula: ( V dc – Vmin) R = --------------------------------------Imin where: R = maximum pull-up resistor value Vdc = power supply voltage Vmin = 2.6V dc Imin = 6.8 mA

Power Supply Voltage (V dc)

Maximum Pull-Up Resistor Value (a)

5V dc

35 2 Ω

12 V dc

1 38 2 Ω

24 V dc

3 14 7 Ω

(a) Resistance values may change, depending on your application. The minimum resistor (R) value depends on the current sinking capability of the sensor. Refer to your sensor's documentation.

1

Publication CIG-WD001B-EN-P - May 2005

Page 112

11-2

1769 Compact I/O Modules

1769-HSC – Output Device applications OUT DC

CR

A0B0Z0A1B1Z1-

Cable1

+DC

OUT 0 +5/24VDC OUT 1 OUT 2 OUT 3 OUT DC COM

1769-HSC – Single-Ended Encoder applications +VDC

VS GND

CR

COM

R

CR

Power Supply

(2)

A1(+)

A

A1(–)

A0+

B

Allen-Bradley 845H Series single-ended encoder

B0+

B1(+) B1(–) Z1(+)

Z

Z1(–)

+5/24V dc

Z0+

Shield shield/housing Connect only if housing is electronically isolated from the motor and ground.

A1+

Earth Module Inputs

B1+ 1. Refer to your encoder manual for proper cable type. The type of cable used should be twisted pair, individually shielded cable with a maximum length of 300m (1000ft).

Z1+

2. External resistors are required if they are not internal to the sensor. The pull-up resistor (R) value depends on the power supply value. The table below shows the maximum resistor values for typical supply voltages. To calculate the maximum resistor value, use the following formula:

-DC

( V dc – Vmin) R = --------------------------------------Imin where: R = maximum pull-up resistor value Vdc = power supply voltage Vmin = 2.6V dc Imin = 6.8 mA

Power Supply Voltage (V dc)

Maximum Pull-Up Resistor Value (a)

5V dc

35 2 Ω

12 V dc

1 38 2 Ω

24 V dc

3 14 7 Ω

(a) Resistance values may change, depending on your application. The minimum resistor (R) value depends on the current sinking capability of the sensor. Refer to your sensor's documentation.

1769-IA16

1769-IA8I L1a

L1

100/120V ac

IN 0 IN 1

AC COM 0

L2a

IN 2

IN 0

L1b

IN 3 IN 4

100/120V ac

IN 5 IN 6 100/120V ac

AC COM 1

L2b

IN 7

IN 1

L1c

IN 8 IN 9

100/120V ac

IN 10 IN 11 L2c

IN 12

AC COM 2

IN 2

IN 13 IN 14 IN 15 L2

AC COM

AC COM

Commo ns are connected internally.

AC COM3 AC COM4 AC COM5 AC COM6 AC COM7 NC

Publication CIG-WD001B-EN-P - May 2005

IN 3 IN 4 IN 5 IN 6 IN 7 NC

Page 113

1769 Compact I/O Modules

1769-IF4 – Differential Inputs applications Belden 8761 cable (or equivalent)

analog source V/I in 0 ANLG Com V/I in 1 ANLG Com V/I in 2 ANLG Com V/I in 3 ANLG Com dc NEUT

I in 0+ V in 1 + I in 1+ V in 2 +

– earth ground the shield locally at the module

1769-IF4 Terminal Block

Signal

V in 0 + V/I in 0 I in 0 + ANLG Com V in 1 + V/I in 1 I in 1 + ANLG Com V in 2 + V/I in 2 I in 2 + ANLG Com V in 3 + V/I in 3 I in 3 + ANLG Com +24V dc dc NEUT

+

Differential Voltage Transmitter – Supply +

+

V in 0 +

1769-IF4 – Mixed Transmitter Type applications Single-ended Voltage Transmitter

–

+ Signal – –

Differential Signal Current + Transmitter – Supply +

I in 2+ V in 3 + I in 3+ +24V dc

External 24V dc Power Supply(1) (optional)(2) +

11-3

2-Wire Current Transmitter

Signal

Sensor/ Transmitter Supply

+

+

– External 24V dc + Power Supply(1) (optional)(2) –

1. The external power supply must be rated Class 2, with a 24V dc range of 20.4 to 26.4V dc and 60 mA minimum. 2. Series B and later modules provide this option. 1. The external power supply must be rated Class 2, with a 24V dc range of 20.4 to 26.4V dc and 60 mA minimum. 2. Series B and later modules provide this option.

1769-IF4 – Single-Ended Sensor/Transmitter Type applications Sensor/ + Transmitter Supply

1769-IF4I – Differential Inputs applications

1769-IF4 Terminal Block Current Transmitter + Signal

Voltage Transmitter

+ Ground

Signal

Voltage Transmitter

+ Ground Signal

V in 0 + V/I in 0 I in 0 + ANLG Com V in 1 + V/I in 1 I in 1 + ANLG Com V in 2 + V/I in 2 I in 2 + ANLG Com V in 3 + V/I in 3 I in 3 + ANLG Com +24V dc dc NEUT

Belden 8761 cable (or equivalent) analog source

External 24V dc + Power Supply(1) (optional)(2)

1. The external power supply must be rated Class 2, with a 24V dc range of 20.4 to 26.4V dc and 60 mA minimum. 2. Series B and later modules provide this option.

Publication CIG-WD001B-EN-P - May 2005

Page 114

11-4

1769 Compact I/O Modules

1769-IF4I – Mixed Transmitter Type applications

1769-IF4I – Single-Ended Sensor/Transmitter Type applications

1769-IF4I Terminal Block

Sensor/ + Transmitter Supply

Ch0+

Sensor/ + Transmitter Supply -

N/C

Current Transmitter + Signal

Ch0_iRtn

Current Transmitter Signal +

N/C Ch0Ch1+ N/C

Voltage Transmitter

Ch1_iRtn

Voltage Transmitter

N/C Ch1-

+

Ground

Signal

+

Ground

Signal

Ch2+ N/C

+ Ground

Voltage Transmitter

Ch2_iRtn

Voltage Transmitter

N/C

Signal

+

Ch2-

Ground

Signal

Ch3+ N/C Ch3_iRtn N/C

Differential Voltage Transmitter

Ch3-

+ Signal

_

+

1769-IF8 – Differential Inputs applications Belden 8761 cable (or equivalent)

analog source

– V in 0+

V/I in 0-

+

I in 0+

ANLG Com

I in 1+

ANLG Com

V in 2+

V/I in 2-

I in 2+ ANLG Com V in 3+

V/I in 3-

I in 3+

ANLG Com NC

Publication CIG-WD001B-EN-P - May 2005

NC

V in 4+

V/I in 4-

I in 4+

ANLG Com

V in 1+

V/I in 1-

–

V in 5+

V/I in 5- earth ground the shield locally at the module

I in 5+

ANLG Com

V in 6+

V/I in 6-

I in 6+ ANLG Com V in 7+

V/I in 7-

I in 7+

ANLG Com NC

NC

+

Page 115

1769 Compact I/O Modules

1769-IF8 – Mixed Transmitter Type applications Single-ended Voltage Transmitter

–

V in 0 + V/I in 0 -

+

Differential Voltage Transmitter – Supply +

Current Transmitter Signal

V in 0 + V/I in 0 -

+

I in 0 + AN LG C o m V in 1 +

V/I in 1 -

–

+ Ground

V in 2 + V/I in 2 -

V in 2 + I in 2 + AN LG C o m

Voltage Transmitter + Ground

V in 3 +

V in 3 +

Signal

V/I in 3 -

+

I in 1 + AN LG C o m

Signal

V/I in 2 -

I in 2 + ANLG Com

Signal

V/I in 1 -

Voltage Transmitter

I in 1 + ANLG Com

–

Sensor/ Transmitter Supply

1769-IF8 Terminal Block

Sensor/Trans + mitter Supply

I in 0 + ANLG Com V in 1 +

+ Signal

Differential Signal Current + Transmitter – Supply +

2-Wire Current Transmitter

1769-IF8 – Single-Ended Sensor/Transmitter Type applications

1769-IF8 Terminal Block

Signal

11-5

I in 3 +

V/I in 3 -

ANLG Com NC NC

AN LG C o m

I in 3 + NC NC

Wiring for channels 4-7 are identical.

+ – Wiring for channels 4-7 are identical.

1769-IF4XOF2 – Analog Output Device applications

1769-IF4XOF2 – Differential Input applications

1769-IF4XOF2 Terminal Block

Voltage Load earth ground Current Load

V in 0+ I in 0+ V/I in 0 V in 1+ I in 1+ V/I in 1V in 2+ I in 2+ V/I in 2V in 3+ I in 3+ V/I in 3ANLG Com ANLG Com V out 0+ I out 0+ V out 1+ I out 1 +

Belden 8761 cable (or equivalent) V in 1+ V/I in 1 I in 1+ V in 3+ V/I in 3 I in 3+ ANLG Com V out 1+ I out 1+

V in 0+ V/I in 0-

+

I in 0+

–

V in 2 + V/I in 2I in 2+ earth ground the shield locally at the module differential voltage transmitter

ANLG Com V out 0+ I out 0+ earth ground

Publication CIG-WD001B-EN-P - May 2005

Page 116

11-6

1769 Compact I/O Modules

1769-IF4XOF2 – Mixed Transmitter Type applications 1769-IF4XOF2 Terminal Block

Signal Single-ended Voltage Transmitter + –

V in 0+ I in 0+ V/I in 0 V in 1+ I in 1+ V/I in 1V in 2+ I in 2+ V/I in 2V in 3+ I in 3+ V/I in 3ANLG Com ANLG Com V out 0+ I out 0+ V out 1+ I out 1 +

+ Differential Signal Voltage Transmitter – – Supply + + Differential Signal Current Transmitter – – Supply + Signal 2-Wire Current Transmitter + Sensor/ + Transmitter Power Supply(1) –

1769-IF4XOF2 – Single-Ended Sensor/Transmitter applications Sensor/ Transmitter Power Supply(1)

1769-IF4XOF2 Terminal Block

+

+

Current Transmitter Signal

Voltage Transmitter

+

Ground

Signal

(1) The sensor power supply must be rated Class 2.

V in 0+ I in 0+ V/I in 0 V in 1+ I in 1+ V/I in 1V in 2+ I in 2+ V/I in 2V in 3+ I in 3+ V/I in 3ANLG Com ANLG Com V out 0+ I out 0+ V out 1+ I out 1 +

1. The sensor power supply must be rated Class 2.

1769-IM12

1769-IQ16 +DC (sinking) -DC (sourcing)

L1 IN 0 IN 1

IN 0

IN 2

IN 1

IN 3

IN 2

IN 4

IN 4

IN 6 200/240V ac

IN 7 IN 8 IN 9 IN 10

24V dc

IN 3

IN 5

Note: Do no t use the NC terminal s as co nn ec tion

IN 11

IN 5 IN 6 IN 7 +DC (sinking) -DC (sourcing)

DC COM 1

NC NC NC L2

AC COM

NC

IN 9

AC COM

IN 11

IN 8

Commo ns ar e co nn ec ted internally.

24V dc

IN 10 IN 13 IN 12 IN 15

-DC (sinking) +DC (sourcing)

Publication CIG-WD001B-EN-P - May 2005

DC COM 2

IN 14

-DC (sinking) +DC (sourcing)

Page 117

1769 Compact I/O Modules

11-7

1769-IQ16F +D C (sinking ) -DC (sou rcing)

IN 0 IN 1 IN 2 24V dc

IN 3 IN 4 IN 5 IN 6 IN 7 +D C (sinking ) -DC (sou rcing)

DC CO M 1

-DC (sinking ) +D C (sou rcin

IN 9 IN 8 IN 11 24V dc

IN 10 IN 13 IN 12 IN 15 DC CO M 2

-DC (sinking ) +D C (sou rcing)

IN 14

1769-IQ32 +DC (sinking) -DC (sourcing)

+DC (sinking) -DC (sourcing)

IN 0

IN 16

IN 1

IN 17 IN 2

IN 18 24V dc

IN 3

IN 20

IN 5

IN 21 IN 22

IN 6 IN 7 +DC (sinking) -DC (sourcing)

DC COM 1

IN 23 -DC (sinking) +DC (sourcing)

+DC (sinking) -DC (sourcing)

IN 9

IN 10

IN 24 24V dc

IN 26 IN 29

IN 12

IN 28

IN 15 DC COM 2

-DC (sinking) +DC (sourcing)

IN 27

IN 13

-DC (sinking) +DC (sourcing)

DC COM 3

IN 25 IN 8

IN 11 24V dc

24V dc

IN 19

IN 4

IN 31 IN 14 -DC (sinking) +DC (sourcing)

DC COM 4

IN 30

Publication CIG-WD001B-EN-P - May 2005

Page 118

11-8

1769 Compact I/O Modules

1769-IQ32T

1769-IQ6XOW4 CR CR

OUT 0

VAC VDC

L1 or +DC

OUT 1

CR

OUT 3

CR

L2 or -DC

OUT 2

NC NC NC NC NC NC

+DC (sinking) -DC (sourcing)

No te: Do not use the NC terminals as connection points.

IN 0 IN 1 24V dc

IN 2 IN 3

-DC (sinking) +DC (sourcing)

IN 4 DC COM

IN 5

(1) Surge Suppression - Connecting surge suppressors across your external inductive load will extend the life of the relay contacts. For additional details, refer to Industrial Automation Wiring and Grounding Guidelines, Allen-Bradley publication 1770-4.1. (2) Sinking/Sourcing Inputs - Sourcing/sinking describes the current flow between the I/O module and the field device. Sourcing input circuits supply (source) current to sinking field devices. Sinking input circuits are driven by a current sourcing field device. Europe: DC sinking input and sourcing output module circuits are the commonly used options.

Publication CIG-WD001B-EN-P - May 2005

Page 119

1769 Compact I/O Modules

1769-IR6 – 2-Wire Potentiometer Interconnection applications Add Jumper

Cable Shield (to Ground)

Potentiometer

1769-IR6 – 2-Wire RTD applications Cable Shield (to Ground)

Add Jumper

EXC 3

RTD EXC

EXC 3

RTD EXC

Return Belden 9501 Shielded Cable

RTN 3

Return

RTD EXC

Return

SENSE 3

SENSE 3

11-9

RTN 3

EXC 4

Belden 9501 Shielded Cable

Add Jumper

Cable Shield (to Ground) Potentiometer

RTD EXC

EXC 3 SENSE 3

Return

RTN 3

Belden 9501 Shielded Cable

1769-IR6 – 3-Wire Potentiometer Interconnection applications

Cable Shield (to Ground)

EXC 3

Run RTD EXC and sense wires from the module to potentiometer terminal and tie terminal to one point. Potentiometer

RTD EXC

Return

RTN 3

Cable Shield (to Ground)

SENSE 3 RTN 3

EXC 3 SENSE 3

RTD EXC

RTD EXC

Sense

Sense

Return

Return

EXC 4

Belden 83503 or 9533 Shielded Cable

EXC 3

Cable Shield (to Ground)

Sense

SENSE 3 RTN 3

1769-IR6 – 3-Wire RTD applications

Belden 83503 or 9533 Shielded Cable

Run RTD EXC and sense wires from the module to potentiometer terminal and tie terminal to one point.

RTD EXC Potentiometer Sense

1769-IR6 – 4-Wire RTD applications

Return

Cable Shield (to Ground)

Belden 83503 or 9533 Shielded Cable

EXC 3 SENSE 3 RTN 3 EXC 4

RTD EXC

RTD EXC

Sense

Sense

Return

Return

Belden 83503 or 9533 Shielded Cable Leave one sensor wire open.

Publication CIG-WD001B-EN-P - May 2005

Page 120

11-10

1769 Compact I/O Modules

1769-IT6

CJC sensor

1769-OA16

NC

CJC 0+

IN 0+

+

CJC 0-

IN 0-

IN 3+

IN 1 +

- grounded thermocouple

-

IN 2+ IN 2-

IN 5+

CR

OUT 2

CR

OUT4

CR

+

IN 4+ IN 4-

OUT6

CR

OUT 3

CR

OUT 5

CR

OUT 7

CR

100 to 240V ac

L2 L1

VAC 2

IN 5-

CJC sensor

CJC 1+

L1

OUT 1 grounded thermocouple

-

CJC 1-

NC

VAC 1

OUT 0 within 10V dc

IN 1-

IN 3- ungrounded thermocouple

CR

+

100 to 240V ac

CR

OUT 8

CR

OUT10

CR

OUT 12

CR

OUT 14

OUT 9

CR

OUT11

CR

OUT 13

CR

OUT 15

CR

L2 (1) Surge Suppression - Connecting surge suppressors across your external load will extend the life of the triac outputs. For additional details, refer to Industrial Automation Wiring and Grounding Guidelines, Allen-Bradley publication 1770-4.1.

1769-OA8

1769-OB16 +DC

+VDC

CR CR

OUT0 OUT2

L1

VAC 1 OUT1

CR

OUT3

CR

CR

OUT 2

100 to 240V ac

CR

OUT4 OUT6

OUT 1

CR

OUT 3

CR

OUT 5 CR

OUT 6

CR

OUT 8

VAC 2 CR

100 to 240V ac

OUT 0

OUT 4

L2 L1

CR

OUT5

CR

OUT 10

OUT7

CR

OUT 12

OUT 7

CR

OUT 9

CR

OUT 11

CR

OUT 13

CR

24V dc (source)

OUT 14 OUT 15 DC COM -DC

L2

1769-OB16P +DC

+VDC CR

OUT 0

CR

OUT 2

OUT 1

CR

OUT 3

CR

OUT 4 OUT 5 CR

OUT 6

CR

OUT 8

OUT 7

CR

OUT 9

CR

OUT 11

CR

OUT 13

CR

24V dc

OUT 10 OUT 12 OUT 14 OUT 15 DC COM -DC

Publication CIG-WD001B-EN-P - May 2005

Page 121

1769 Compact I/O Modules

11-11

1769-OB32

1769-OB8

OUT 0 OUT 2 DC COM 1

DC -

NC NC NC CR

OUT 4

CR

OUT 6 DC COM 2

DC+

+VDC 1 OUT 1

Tr an sient Pu lse Duration as a Function of Load Curren

OUT 3 t

CR

NC

Time - Duration of Transient (ms)

CR

NC NC DC+

+VDC 2 OUT 5

CR

OUT 7

CR

On-State Load Current (mA)

DC-

Publication CIG-WD001B-EN-P - May 2005

Page 122

11-12

1769 Compact I/O Modules

1769-OF2

1769-OF4CI 1769-OF2 Terminal Block

Voltage Load earth ground Current Load earth ground External 24V dc Power + Supply(1) (optional)(2) -

V out 0 + I out 0 + ANLG Com NC V out 1 + I out 1 + ANLG Com NC +24V dc dc NEUT

1. The external power supply must be rated Class 2, with a 24V dc range of 20.4 to 26.4V dc and 60 mA minimum. 2. Series B and later modules provide this option.

1769-OF4VI

1769-OF8C

I out 0+

ANLG Com ANLG Com

I out 1+ ANLG Com I out 2+ ANLG Com

Current Load

I out 3+ ANLG Com earth ground External 24V dc Power + Supply (optional)

I out 4+ ANLG Com I out 5+ ANLG Com

I out 6+

ANLG Com I out 7+ dc NEUT +24V dc

Publication CIG-WD001B-EN-P - May 2005

Page 123

1769 Compact I/O Modules

1769-OF8V

1769-OV16 +DC

+VDC ANLG Com

CR

OUT 0

ANLG Com

CR

OUT 2

V out 0+

V out 1+

V out 2+ ANLG Com ANLG Com earth ground

OUT 6

CR

OUT 8

Supply (optional)

CR

OUT 7

CR

OUT 9

CR

OUT 11

CR

OUT 13

CR

OUT 10

V out 5+ ANLG Com

-

OUT 3

24V dc (sink)

ANLG Com

External 24V dc Power +

CR

OUT 5 CR

V out 3+

V out 4+

OUT 1

OUT 4

ANLG Com

Voltage Load

11-13

V out 6+

OUT 12 ANLG Com

V out 7+

OUT 14 dc NEUT

OUT 15

+24V dc

DC COM -DC

1769-OV32T

1769-OW16 OUT 0 CR CR

VAC-VDC 1

L1 or +DC

OUT 1

CR

OUT 3

CR

OUT 2 OUT 4 OUT 5 OUT 6 OUT 7

CR L2 or -DC

VAC-VDC 2

L1 or +DC

OUT 9

CR

OUT 11

CR

OUT 8 CR CR

OUT 10 OUT 13 OUT 12 OUT 14

OUT 15

CR

L2 or -DC

(1) Surge Suppression - Connecting surge suppressors across your external inductive load will extend the life of the relay contacts. For additional details, refer to Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.

Publication CIG-WD001B-EN-P - May 2005

Page 124

11-14

1769 Compact I/O Modules

1769-OW8

1769-OW8I L1a or +DCa

L2a or -DCa OUT 0 CR

VAC-VDC 1

L1 or +DC

OUT 1

CR

OUT 3

CR

OUT 2

CR

OUT 0

VAC-VDC 0

L1b or +DCb

L2 or -DC

L2b or -DCb

OUT 1

VAC-VDC 1

L1c or +DCc VAC-VDC 2

L1 or +DC L2 or -DC

CR

OUT 4

CR

OUT 6

OUT 5

CR

L2c or -DCc

OUT 2

VAC-VDC 2

OUT 7

OUT 3 OUT 4 OUT 5 OUT 6 OUT 7

VAC-VDC 3 VAC-VDC 4 VAC-VDC 5 VAC-VDC 6 VAC-VDC 7 NC

NC

Publication CIG-WD001B-EN-P - May 2005