Page 21

Chapter

4

1738 ArmorPoint

1738-232ASCM12

1738-485ASCM12 (view into connector) Pin 1 Tx Pin 2 Tx + Pin 3 Rx + Pin 4 Rx Pin 5 No Connect

(view into connector) Pin 1 Pin 2 Pin 3 Pin 4 Pin 5

No Connect Tx + Rx + Common No Connect

1738-ACNR

1738-ADN12

Male In Connector (view into connector) Pin 1 Pin 2 Pin 3 Pin 4 -

User Power + Adapter Power + Adapter Power User Power -

Male In Connector

Female Out Connector (view into connector) Pin 1 Drain Pin 2 +V Pin 3 -V Pin 4 CAN_High Pin 5 CAN_Low

DeviceNet Auxiliary Power Male In Connector (view into connector) Pin 1 User Power + Pin 2 Adapter Power + Pin 3 Adapter Power Pin 4 User Power -

1

Publication CIG-WD001B-EN-P - May 2005

Page 22

4-2

1738 ArmorPoint

1738-ADN18

1738-ADN18P

Male In Connector

Male In Connector (view into connector) Pin 1 Pin 2 Pin 3 Pin 4 Pin 5

Female Out Connector (view into connector) Pin 1 Drain Pin 2 +V Pin 3 -V Pin 4 CAN_High Pin 5 CAN_Low

Drain +V -V CAN_High CAN_Low

DeviceNet Auxiliary Power DeviceNet Auxiliary Power Male In Connector Male In Connector

(view into connector) Pin 1 User Power + Pin 2 Adapter Power + Pin 3 Adapter Power Pin 4 User Power -

(view into connector) Pin 1 User Power + Pin 2 Adapter Power + Pin 3 Adapter Power Pin 4 User Power -

1738-ADNX

Male In Connector

1738-AENT

Female Out Connector

Network Connector

(Subnet out) Female In Connector (view into connector) Pin 1 Tx + Pin 2 Rx + Pin 3 Tx Pin 4 Rx -

(view into connector) Pin 1 Drain Pin 2 +V Pin 3 -V Pin 4 CAN_High Pin 5 CAN_Low

Auxiliary Power DeviceNet Auxiliary Power Male In Connector (view into connector) Pin 1 User Power + Adapter/Subnet + Pin 2 Adapter/Subnet Pin 3 Pin 4 User Power -

Publication CIG-WD001B-EN-P - May 2005

Male In Connector (view into connector) Pin 1 User Power + Pin 2 Adapter Power + Pin 3 Adapter Power Pin 4 User Power -

Page 23

1738 ArmorPoint

1738-APB

4-3

1738-EP24DC

Male In Connector

Female In Connector (view into connector) Pin 1 +5VBUS Pin 2 A-Line Pin 3 GNDBUS Pin 4 B-Line! Pin 5 Shield

Male In Connector (view into connector) Pin 1 User Power + Pin 2 Adapter + Pin 3 Adapter Pin 4 User Power -

Male Auxiliary Male In connector ((view into connector) Pin 1 User Power Pin 2 Adapter Power Pin 3 Protective GND Pin 4 Adapter Power + Pin 5 User Power +

IMPORTANT

Profibus Adapter Network connections have earth grounded metal rings. This should be considered when choosing shielded cables and grounding techniques.

1738-EXT1, -EXT3 Module will bridge the extension unit and the base

1738-FPD

Module will bridge the extension unit and the base

1738-IA2M12AC3

(view into connector) Pin 1 Chassis Pin 2 L1 Pin 3 Input 0 (M12-A) Input 1 (M12-B)

Male In Connector (view into connector) Pin 1 User Power + Pin 2 No Connect Pin 3 No Connect Pin 4 User Power -

1738-IA2M12AC4

(view into connector) Pin 1 L1 Pin 2 L2/N Pin 3 Input 0 (M12-A) Input 1 (M12-B) Pin 4 Chassis

Publication CIG-WD001B-EN-P - May 2005

Page 24

4-4

1738 ArmorPoint

1738-IB2M12

1738-IB4M12 (view into connector) Pin 1 24V dc Pin 2 No Connect Pin 3 Common Pin 4 Input 0 (M12-A) Input 1 (M12-B) Input 2 (M12-C) Input 3 (M12-D) Pin 5 No Connect

(view into connector) Pin 1 24V dc Pin 2 No Connect Pin 3 Common Pin 4 Input 0 (M12-A) Input 1 (M12-B) Pin 5 No Connect

1738-IB4M8

1738-IB8M12 (view into connector) Pin 1 24V dc Pin 2 I nput 1 (M12-A) Input 3 (M12-B) Input 5 (M12-C) Input 7 (M12-D) Pin 3 Common Pin 4 Input 0 (M12-A) Input 2 (M12-B) Input 4 (M12-C) Input 6 (M12-D) Pin 5 No Connect

(view into connector) Pin 1 24V dc Pin 3 Common Pin 4 Input 0 (M8-A) Input 1 (M8-B) Input 2 (M8-C) Input 3 (M8-D)

1738-IB8M23 1

8

9

7

2 10

12 6

3 11 4

5

Pin 1 Pin 2 Pin 3 Pin 4 Pin 5 Pin 6

1738-IB8M8 (view into connector) Pin 1 24V dc Pin 4 Input 0 (M8-A) Pin 3 Common Input 1 (M8-B) Input 2 (M8-C) Input 3 (M8-D) Input 4 (M8-E) Input 5 (M8-F) Input 6 (M8-G) Input 7 (M8-H)

(view into connector) Input 0 Pin 7 Input 6 Input 1 Pin 8 Input 7 Input 2 Pin 9 Return (Com) Input 3 Pin 10 Return (Com) Input 4 Pin 11 24V dc Input 5 Pin 12 Chassis

1738-IE2CM12

IMPORTANT

1738-IE2VM12

(view into connector)

(view into connector)

Pin 1 24V dc Pin 2 Input 0 (M12-A) Input 1 (M12-B) Pin 3 Common Pin 4 Common Pin 5 No Connect

Pin 1 24V dc Pin 2 Input 0 (M12-A) Input 1 (M12-B) Pin 3 Common Pin 4 Common Pin 5 No Connect

Analog and specialty modules have earth grounded metal rings. This should be considered when choosing shielded cables and grounding techniques.

Publication CIG-WD001B-EN-P - May 2005

IMPORTANT

Analog and specialty modules have earth grounded metal rings. This should be considered when choosing shielded cables and grounding techniques.

Page 25

1738 ArmorPoint

1738-IJM23

1

8

9

7

2 10

12

6

3 11

4

5

1738-IR2M12

(view into connector)

(view into connector)

Pin 1 Pin 2 Pin 3 Pin 4 Pin 5 Pin 6 Pin 7 Pin 8 Pin 9 Pin 10 Pin 11 Pin 12

Pin 1 Pin 2

+A ~A +B ~B +Z ~Z Chassis Chassis Return (Com) Return (Com) 5V dc Chassis

Pin 3 Pin 4 Pin 5

IMPORTANT IMPORTANT

Analog and specialty modules have earth grounded metal rings. This should be considered when choosing shielded cables and grounding techniques.

1738-IT2IM12

No Connect Input 0A (M12-A) Input 1A (M12-B) Input 0C (M12-A) Input 1C (M12-B) Input 0B (M12-A) Input 1B (M12-B) No Connect

Analog and specialty modules have earth grounded metal rings. This should be considered when choosing shielded cables and grounding techniques.

1738-IV4M12 (view into connector) Pin 1 24V dc Pin 2 No Connect Pin 3 Common Pin 4 Input 0 (M12-A) Input 1 (M12-B) Input 2 (M12-C) Input 3 (M12-D) Pin 5 No Connect

(view into connector) Pin 1 CJC + Pin 2 TC 0 + (M12-A) TC 1 + (M12-B) Pin 3 CJC Pin 4 TC 0 - (M12-A) TC 1 - (M12-B) Pin 5 No Connect

IMPORTANT

4-5

Analog and specialty modules have earth grounded metal rings. This should be considered when choosing shielded cables and grounding techniques.

1738-IV8M12 (view into connector) Pin 1 24V dc Pin 2 Input 1 (M12-A) Input 3 (M12-B) Input 5 (M12-C) Input 7 (M12-D) Pin 3 Common Pin 4 Input 0 (M12-A) Input 2 (M12-B) Input 4 (M12-C) Input 6 (M12-D) Pin 5 No Connect

1738-IV8M23

1

8

9

7

2 10

12 6

3 11 4

5

Pin 1 Pin 2 Pin 3 Pin 4 Pin 5 Pin 6

(view into connector) Input 0 Pin 7 Input 6 Input 1 Pin 8 Input 7 Input 2 Pin 9 Return (Com) Input 3 Pin 10 Return (Com) Input 4 Pin 11 24V dc Input 5 Pin 12 Chassis

Publication CIG-WD001B-EN-P - May 2005

Page 26

4-6

1738 ArmorPoint

1738-IV8M8

1738-OA2M12AC3

(view into connector) Pin 1 24V dc Pin 4 Input 0 (M8-A) Pin 3 Common Input 1 (M8-B) Input 2 (M8-C) Input 3 (M8-D) Input 4 (M8-E) Input 5 (M8-F) Input 6 (M8-G) Input 7 (M8-H)

(view into connector) Pin 1 Chassis Pin 2 L2/N Pin 3 Output 0 (M12-A) Output 1 (M12-B)

1738-OB2EM12

1738-OB2EPM12

(view into connector) Pin 1 24V dc Pin 2 No Connect Pin 3 Common Pin 4 Output 0 (M12-A) Output 1 (M12-B) Pin 5 No Connect

(view into connector) Pin 1 24V dc Pin 2 No Connect Pin 3 Common Pin 4 Output 0 (M12-A) Output 1 (M12-B) Pin 5 No Connect

1738-OB4EM12

1738-OB4EM8

(view into connector) Pin 1 24V dc Pin 2 No Connect Pin 3 Common Pin 4 Output 0 (M12-A) Output 1 (M12-B) Output 2 (M12-C) Output 3 (M12-D) Pin 5 No Connect

(view into connector) Pin 1 24V dc Pin 3 Common Pin 4 Output 0 (M8-A) Output 1 (M8-B) Output 2 (M8-C) Output 3 (M8-D)

1738-OB8EM12 (view into connector) Pin 1 24V dc Pin 2 Output 1 (M12-A) Output 3 (M12-B) Output 5 (M12-C) Output 7 (M12-D) Pin 3 Common Pin 4 Output 0 (M12-A) Output 2 (M12-B) Output 4 (M12-C) Output 6 (M12-D) Pin 5 No Connect

Publication CIG-WD001B-EN-P - May 2005

1738-OB8EM23

1

8

9

7

2 10

12 6

3 11 4

5

(view into connector) Pin 1 Output 0 Pin 2 Output 1 Pin 3 Output 2 Pin 4 Output 3 Pin 5 Output 4 Pin 6 Output 5 Pin 7 Output 6 Pin 8 Output 7 Pin 9 Return (Com) Pin 10 Return (Com) Pin 11 24V dc Pin 12 Chassis

Page 27

1738 ArmorPoint

1738-OB8EM8

1738-OE2CM12

(view into connector) Pin 1 24V dc Pin 3 Common Pin 4 Output 0 (M8-A) Output 1 (M8-B) Output 2 (M8-C) Output 3 (M8-D) Output 4 (M8-E) Output 5 (M8-F) Output 6 (M8-G) Output 7 (M8-H)

(view into connector) Pin 1 Pin 2 Pin 3 Pin 4 Pin 5

IMPORTANT

1738-OE2VM12

Pin 2 Pin 3 Pin 4 Pin 5

IMPORTANT

Output 0 (M12-A) Output 1 (M12-B) 24V dc Common Common No Connect

Analog and specialty modules have earth grounded metal rings. This should be considered when choosing shielded cables and grounding techniques.

1738-OV4EM12

(view into connector) Pin 1

4-7

Output 0 (M12-A) Output 1 (M12-B) 24V dc Common Common No Connect

(view into connector) Pin 1 24V dc Pin 2 No Connect Pin 3 Common Pin 4 Output 0 (M12-A) Output 1 (M12-B) Output 2 (M12-C) Output 3 (M12-D) Pin 5 No Connect

Analog and specialty modules have earth grounded metal rings. This should be considered when choosing shielded cables and grounding techniques.

1738-OW4M12 (view into connector) Pin 1 24V dc Pin 2 Output 0B (M12-A) Output 1B (M12-B) Output 2B (M12-C) Output 3B (M12-D) Pin 3 Common Pin 4 Output 0A (M12-A) Output 1A (M12-B) Output 2A (M12-C) Output 3A (M12-D) Pin 5 No Connect

1738-OW4M12AC4 (view into connector) Pin 1 L1 Pin 2 L2/N Pin 3 Output 0A (M12-A) Output 1A (M12-B) Output 2A (M12-C) Output 3A (M12-D) Pin 4 Output 0B (M12-A) Output 1B (M12-B) Output 2B (M12-C) Output 3B (M12-D)

Publication CIG-WD001B-EN-P - May 2005

Page 28

4-8

1738 ArmorPoint

1738-SSIM23

1738-VHSC24M23

(view into connector) 1

8

9

7

2 10

12

6

3 11

4

IMPORTANT

5

Pin 1 Pin 2 Pin 3 Pin 4 Pin 5 Pin 6 Pin 7 Pin 8 Pin 9 Pin 10 Pin 11 Pin 12

Data + Data V+ VShield Input 0 Clock + Clock Return (Com) Return (Com) 24 V dc Chassis

Analog and specialty modules have earth grounded metal rings. This should be considered when choosing shielded cables and grounding techniques.

Publication CIG-WD001B-EN-P - May 2005

(view into connector) 1

8

9

7

2 10

12

6

3 11

4

IMPORTANT

5

Pin 1 Pin 2 Pin 3 Pin 4 Pin 5 Pin 6 Pin 7 Pin 8 Pin 9 Pin 10 Pin 11 Pin 12

+A ~A +B ~B +Z ~Z Output 0 Output 1 Return (Com) Return (Com) 24V dc Chassis

Analog and specialty modules have earth grounded metal rings. This should be considered when choosing shielded cables and grounding techniques.