Browse
(440) 299-7778
Menu
(440) 299-7778
One-year parts and labor warranty30-day money-back guaranteeContact

The text of a manual · part 6 of 26

Allen-Bradley I/O Modules Wiring Diagrams: 5 - 1746 I/O Modules, pages 29 to 37

Pages 29 to 37 of 200, from Allen-Bradley I/O Modules Wiring Diagrams

The original document is the PDF (4.7 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

Filed in the catalog under the Allen-Bradley 1771-IT

Page 29

Chapter

5

1746 I/O Modules

1746-BLM Desc riptio n

40 2 : : : : : : : : : : : : : : : : : : : : 1 39 1492-IFM40F

14

+

13

-

16 40

2

15 1

39

Axis 1

Axis 2

Axis 3

Axis 4

Dig ital OUT+ (+24EXT )

17 18

13 14

9 10

5 6

Digit al I N-

19

15

11

7

Digit al I N+

20

16

12

8

Re se rve d Digit al O UT- digital output sync output + 24V EXT + digital input dc common start-of-drop trigger -

22 +

24V dc supply

21 -

4, 3, 2, 1

-24V dc RET

21

+24V dc EX T

22

An al og OUT- (GND)

23

27

31

35

An al og OUT+

24

28

32

36

An al og IN-

25 26

29 30

33 34

37 38

An al og IN+

We recommend making connections to the 1746-BLM module with: -- Interface module (1492-IFM40F) -- Interface cable (1492-CABLE010H)

System

Excitation- (-10V)

39

Excitation+ (+1 0V)

40

1746-BTM Retaining Screw

CJC A+ CJC Assembly

Channel 0+

CJC A-

Channel 0Channel 1+

ATTENTION

Channel 1-

Do NOT use these connections

Channel 2+

Do not remove or loosen the cold junction compensating thermistors located on the terminal block. Both thermistors are critical to ensure accurate thermocouple input readings at each channel. The module will not operate in the thermocouple mode if a thermistor is removed

Channel 2Channel 3+

CJC B+ CJC Assembly

CJC BRetaining Screw

Channel 3spare part catalog number: 1746-RT32 n/c

1746-FIO4I

1746-FIO4V

+

+ analog source

- earth ground

Jumper unused inputs.

LOAD earth ground

1

Do not jumper unused outputs.

0 1 2

IN 0+ IN 0ANL COM

3 4 5

IN 1+ IN 1ANL COM

6 7 8 not used OUT 0 ANL COM

9 10 11 not used OUT 1 ANL COM analog source

- earth ground

Jumper unused inputs.

LOAD earth ground

Do not jumper unused outputs.

0 1 2

IN 0+ IN 0ANL COM

3 4 5

IN 1+ IN 1ANL COM

6 7 8 not used OUT 0 ANL COM

9 10 11 not used OUT 1 ANL COM

Publication CIG-WD001B-EN-P - May 2005

Page 30

5-2

1746 I/O Modules

1746-HSCE Differential Encoder cab le (1)

+ V DC COM

VS GN D

Input and Output Connections

Power Supply

Belden 9503 or equivalent 305m (1000ft) max length

Upper Retaining Screw Maximum Torque = 0.7 to 0.9 Nm (6 to 8 in-lbs)

Allen-Bradley 845H Series differential encoder

Discrete Output Wiring The user must supply the external VDC.

A

A(+)

A

A(-)

B

B(+)

B

B(-)

Z

Z(+) Z(-)

Z Shie ld (2)

Terminal Wiring max. #14 AWG (2mm2) max. 2 wires per terminal max. torque: 0.9Nm (8 in-lbs)

encoder connector housing

ON SW1

1 234

OF F

(all switches ON) Earth

Module Inputs 1. Refer to your encoder manual for proper cable type and length. 2. Due to the topology of the module’s input circuits, terminating the shield at the encoder end provides the highest immunity to EMI interference. Connect EARTH ground directly to the encoder connector housing.

Limit Switch and Encoder Input Wiring

Differential Encoder Output Waveforms Lower Retaining Screw Maximum Torque = 0.7 to 0.9 Nm (6 to 8 in-lbs)

The figure below shows the different encoder output waveforms. If your encoder matches these waveforms, the encoder signals can be directly connected to the associated screw terminals on the module. For example, the A lead from the encoder is connected to the module’s A+ screw. If your encoder does not match these waveforms, some wiring modifications may be necessary. See the High-Speed Counter Module User Manual, publication 1746-6.5 for a description of these modifications. A A B B Z Z

1746-HSCE Limit Switch (12V dc Hard Contact) Input and Output Connections

1746-HSCE module

Upper Retaining Screw Maximum Torque = 0.7 to 0.9 Nm (6 to 8 in-lbs)

Hard Contact Limit Switch LS (24V dc) LS (12V dc ) VS

Discrete Output Wiring The user must supply the external VDC.

12V dc

+ -

CO M

LS (5V dc ) LS COM Do not connect LS (5V dc) or LS (12V dc) Terminals

Terminal Wiring max. #14 AWG (2mm2) max. 2 wires per terminal max. torque: 0.9Nm (8 in-lbs) Limit Switch and Encoder Input Wiring

Lower Retaining Screw Maximum Torque = 0.7 to 0.9 Nm (6 to 8 in-lbs)

Publication CIG-WD001B-EN-P - May 2005

321 Jumper placed for 10 ms filtering

Connect only one LS input range at a time, or the module will be damaged.

JW 1

Page 31

1746 I/O Modules

5-3

1746-HSCE Limit Switch (24V dc Hard Contact) Input and Output Connections Hard Contact Limit Switch LS (24V dc) VS

LS (12V dc)

+

24V dc

1746-HSCE module

LS (5V dc)

CO M

LS COM Do not connect LS (5V dc) or LS (12V dc) Terminals

321 Jumper placed for 10 ms filtering

JW 1

Connect only one LS input range at a time, or the module will be damaged.

1746-HSCE Limit Switch (5V dc Solid State) Input and Output Connections

1746-HSCE module

Solid State Limit Switch COM VS VS

+ 5V dc

COM

OUT

LS (24V dc) LS (12V dc) LS (5V dc) LS COM

Do not connect LS (12V dc) or LS (24V dc) Terminals

Jumper placed for 300 µs filtering

321

JW1

Connect only one LS input range at a time, or the module will be damaged.

Publication CIG-WD001B-EN-P - May 2005

Page 32

5-4

1746 I/O Modules

1746-HSCE Outputs Input and Output Connections 1746-HSCE module VDC OUT 0 User Supplied 24V dc

+

OUT 1

-

OUT 2

All switches OFF ON

OUT 3 DC COM

1 234

OFF Dip Switch SW2 wiring terminals

Do not use incandescent lamps as output indicators. The high peak inrush current required to heat the filament can damage the module’s output circuits. Use LED type indicators that satisfy the output circuit ratings, such as Allen-Bradley 800A and 800T LED indicators. The outputs are not electrically isolated from each other. (They are referenced to the same output common terminal.) However, outputs are isolated from the rest of the circuitry to a level of 1500 volts.

1746-HSCE Single-Ended (Discrete Devices) Input and Output Connections

+V DC CO M proximity sensor with

VS OU T CO M

R1 photoelectric sensor with open

A(+) A(-)

solid-state switch (5V output)

VS OU T CO M

Power Supply

R2

VS OU T CO M

B(+) B(-) Z(+) Z(-) ON

1 2 34

SW1 OF F (All switches OFF) Module Inputs

I M PORTA NT

This diagram shows the sensors operation from a common power supply. Separate power supplies for each circuit can be used. The resistor (R1) value depends on the power supply value (VS). The pullup resistor (R2) value depends on the power supply value (VS).

Publication CIG-WD001B-EN-P - May 2005

Page 33

1746 I/O Modules

5-5

1746-HSCE Single-Ended Encoder (Open-Collector) Input and Output Connections cable (1)

VS GN D

+ V DC CO M

Power Supply

(3)

R

Allen-Bradley 845H Series differential encoder

Shield (2)

A

A(+) A(-)

B

B(+) B(-) Z(+) Z(-)

Z

ON

Belden 9503 or equivalent 305m (1000tft) max length

SW1 encoder connector housing

1 234

OF F (All switches OFF)

Earth Module Inputs (1) Refer to your encoder manual for proper cable type and length. (2) Due to the topology of the module’s input circuits, terminating the shield at the encoder end provides the highest immunity to EMI interference. Connect EARTH ground directly to the encoder connector housing. (3) The pullup resistor (R) value depends on the power supply value (VS). The table below lists the resistor values for typical power supply values. These resistors must be located at the encoder end of the cable.

VS V alue

R Value

+5V dc

150 ohm 1/4W 5%

Max imu m Outpu t Leak age 6.3 mA

+12V dc

1800 ohm 1/4W 5%

1.5 mA

+24V dc

4700 ohm 1/4W 5%

1.2 mA

Single-Ended Encoder Output Waveforms The figure below shows the single-ended output waveforms. When the waveform is low, the encoder output transistor is ON. A low = transistor ON high = transistor OFF

B Z

1746-HSCE Single-Ended Encoder (Sourcing) Input and Output Connections cable (1)

VS

+ V DC COM

GND

Power Supply

Belden 9503 or equivalent 305m (1000tft) max length

A(+)

A single ended encoder(4)

R (3) A(-) B(+) (3) R B(-) Z(+) R (3) Z(-)

B Z Sh ield (2)

ON SW1

1 2 34

OF F (All switches OFF) Module Inputs Earth (1) Refer to your encoder manual for proper cable type and length. (2) Due to the topology of the module’s input circuits, terminating the shield at the encoder end provides the highest immunity to EMI interference. Connect EARTH ground directly to the encoder connector housing. (3) The resistor (R) value depends on the power supply value (VS). The table below lists the resistor values for typical power supply values. These resistors must be located at the encoder end of the cable.

(4) The Allen-Bradley 845H sourcing encoder is not compatible with this module.

VS Value

R Value

+5V dc no resistor needed

Max imu m Outpu t Leak age 6.3 µA

+12V dc

1800 ohm 1/4W 5%

1.5 µA

+24V dc

4700 ohm 1/4W 5%

1.2 µA

Single-Ended Encoder Output Waveforms (Sourcing) The figure below shows the single-ended encoder output waveforms. When the waveform is low, the encoder output transistor is OFF. low = transistor OFF high = transistor ON

A B Z

Publication CIG-WD001B-EN-P - May 2005

Page 34

5-6

1746 I/O Modules

1746-HSCE2 – Differential Encoder Cabl e (1)

Input and Output Connections

+VDC

VS GND

COM

A

A(+)

A

A(–)

B

B(+)

B

B(–)

Z

Z(+)

Power S upply

Release screw

A1 + A1 -

B1 +

B1-

Z1+ Z1-

A2 +

Allen-Bradley 845H Series differential encoder

A2-

B2 +

B2 -

Z2+

Shi e ld

Z2-

Output common shield/housing Connect only if housing is electronically isolated from the motor and ground.

OUTPUT 0

OUTPUT 1

OUTPUT 2

OUTPUT 3 Release screw

Z(–)

Z

+V dc

E arth

Module Inputs

1 Refer to your encoder manual for proper cable type. The type of cable used should be twisted pair, individually shielded cable with a maximum length of 300m (1000 ft.).

Differential Encoder Output Waveforms The figure below shows the different encoder output waveforms. If your encoder matches these waveforms, the encoder signals can be directly connected to the associated screw terminals on the module. For example, the A lead from the encoder is connected to the module’s A+ screw. If your encoder does not match these waveforms, some wiring modifications may be necessary. See the user’s manual for your encoder. A A B B Z Z

1746-HSCE2 Single-Ended Encoder (Open-Collector) cab le (1 )

Input and Output Connections

+VDC COM

Release screw

A1 + B1 +

VS GND

R

A1 -

B2 + Z2+ Output common OUTPUT 1 OUTPUT 3 Release screw

A(–)

Z

B(+)

B

Z1A2B2 Z2OUTPUT 0 OUTPUT 2 +V dc

The figure below shows the single-ended encoder output waveforms. When the waveform is low, the encoder output transistor is on. When the waveform is high, the encoder output transistor is off.

B

A(+)

B1-

Single-Ended Encoder Output Waveforms

A

(2)

A

Z1+ A2 +

B(–)

Allen-Bradley 845H Series differential encoder

Z(+)

Z

Z(–)

shi e ld shield/housing Connect only if housing is electronically isolated from the motor and ground.

Earth

Module Inputs

1. Refer to your encoder manual for proper cable type. The type of cable used should be twisted pair, individually shielded cable with a maximum length of 300m (1000 ft.).(2) 2. External resistors are needed if not internal to the encoder. The pull-up resistor (R) value depends on the power supply value. The table below shows resistor values for typical supply voltages. To calculate the resistor value, use one of the following formulas: For 5V dc jumper position: R =

(Vcc - Vmin) Imin

For 24V dc jumper position: R =

[

(Vcc - Vmin) - 1KΩ Imin

[ where: R = pull-up resistor value Vcc = power supply voltage Vmin = 4.2V dc Imin = 6.3mA

Power Supply Voltage (Vcc)

Pull-up Resistor Value (R)1

5V dc 12 V dc 24 V dc

127 W 238 W 21 40 W

1 Resistance values may change, depending upon your application.

Publication CIG-WD001B-EN-P - May 2005

P o wer Su ppl y

Page 35

1746 I/O Modules

5-7

1746-HSCE2 Single-Ended (Discrete Devices) +VDC

Input and Output Connections

COM

Release screw

A1 + B1 + proximity sensor

A1 -

VS

A2 +

Z2+ Output common OUTPUT 1 OUTPUT 3 Release screw

VS solid-state switch

A2-

OUT

B(+)

COM

B(–)

VS

B2 -

OUT

Z2-

OUTPUT 2

A(–)

COM

Z1-

OUTPUT 0

A(+)

OUT

B1-

Z1+

B2 +

Power S uppl y

R

(1)

Z(+)

COM

Z(–)

photoelectric sensor with open collector sinking output

+V dc Module Inputs 1. External resistors are needed if not internal to the encoder. The pull-up resistor (R) value depends on the power supply value. The table below shows resistor values for typical supply voltages. To calculate the resistor value, use one of the following formulas: For 5V dc jumper position: R =

(Vcc - Vmin) Imin

For 24V dc jumper position: R =

[

(Vcc - Vmin) - 1KΩ Imin where: R = pull-up resistor value Vcc = power supply voltage Vmin = 4.2V dc Imin = 6.3mA

[

Power Supply Voltage (Vcc) 5V dc 12 V dc 24 V dc

Pull-up Resistor Value (R)1 127 W 238 W 21 40 W

1 Resistance values may change, depending upon your application.

Publication CIG-WD001B-EN-P - May 2005

Page 36

5-8

1746 I/O Modules

1746-HSRV – Wiring a 15V Encoder

ENCODER C H A. HI

A

1

CH A. LO

A

AB SHLD CH B. HI

B

1

CH B. LO

B

Z SHLD CH Z. HI

B

Z

1

CH Z. LO

I C J

Z ENCODER POWER +5 V

A 3

Optical Encoder G F D

+15V Return

2

RET

Case Ground

+1 5 V SHLD

+15V

1

Use three pair 22 gauge individually twisted and shielded cable.

2

Use one pair 18 gauge twisted and shielded cable.

3

Encoders must have +5V compatible differential line drive outputs on channels A, B, and Z (DS 8830 or equivalent (845H)).

Wiring the power supply

+5V +5 V COMM L1

14 AWG

+1 5V

L2

+/ - 15V COMM E X T P O W E R

- 1 5V

+5 V RET +15V - /+ R E T

+ 24V P o wer Supply

- 15V +2 4 +24R E T E G ND

14 AWG AC HI AC L O

+2 4V +24 V R E T 14 AWG (3)

14 AWG

A C L ine

Electrical Cabinet Ground Bus

Publication CIG-WD001B-EN-P - May 2005

H

Page 37

1746 I/O Modules

5-9

1746-HSRV – Wiring a 5V Encoder

ENCODER C H A. HI

A

1

CH A. LO

A

AB SHLD CH B. HI

B

1

CH B. LO

B

Z SHLD CH Z. HI

Z

1

CH Z. LO

Z ENCODER POWER +5 V

I

H

B

A 3

Optical Encoder

C J

F

D

G

+5V

2

RET +1 5 V

+5V Return

SHLD

Case Ground

1

Use three pair 22 gauge individually twisted and shielded cable.

2

Use one pair 18 gauge twisted and shielded cable.

3

Encoders must have +5V compatible differential line drive outputs on channels A, B, and Z (DS 8830 or equivalent (845H)).

Wiring the power supply +5V +5 V COMM L1

14 AWG

+1 5V

L2

+/ - 15V COMM E X T P O W E R

- 1 5V

+5 V RET +15V - /+ R E T

+ 24V P o wer Supply

- 15V +2 4 +24R E T E G ND

14 AWG AC H I AC L O

+2 4V +24 V R E T 14 AWG (3)

14 AWG

A C L ine

Electrical Cabinet Ground Bus

Publication CIG-WD001B-EN-P - May 2005