DC (10-30V) Input Module, Cat. No. 1771-IVN, Installation Data, pages 1 to 8
Pages 1 to 8 of 8
The original document is the PDF (100 KB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
For the Allen-Bradley 1771-IVN
Page 1
DC (10-30V) Input Module Cat. No. 1771-IVN Installation Data
To The Installer
This document provides information on: important pre–installation considerations power supply requirements installing the module connecting the wiring using the indicators on the module for troubleshooting module specifications
Pre-installation Considerations
The 1771–IVN DC input module is a source input and requires a sink output. A source input provides a positive voltage path and a sink output provides a path to ground. You must use this module in a series B 1771 I/O chassis. Refer to the table below for processor compatibility. Table A Processor Compatibility Chart System Type
Use with Processors:
Local
Mini-PLC-2/02 (cat. no. 1772-LZ, -LZP) Mini-PLC-2/16 (cat. no. 1772-LX, -LXP) Mini-PLC-2/17 (cat. no. 1772-LW, -LWP) PLC-5/15, Series B and later (cat. no. 1785-LT)
Remote (with a 1771-ASB PLC-2/20 (cat. no. 1772-LP2) remote I/O adapter) PLC-2/30 (cat. no. 1772-LP3) PLC-3 (cat. no. 1775-L1, -L2, -L3, -L4) PLC-3/10 (cat. no. 1775-LP4, -LP8) PLC-5/15, Series B and later (cat. no. 1785-LT)
Page 2
Installation Data DC (10 - 30V) Input Module (Cat. No. 1771-IVN)
Do not place this module in the same I/O chassis as the 1771–IX thermocouple module. You can use this module in the same chassis as the 1771–IXE thermocouple module. This module has input filtering to limit the effects of voltage transients caused by contact bounce and/or electrical noise. Specifications for input filtering are listed in the specifications at the end of this document.
Power Supply Requirements
The controller or I/O chassis power supply, connected through the backplane of the I/O chassis, powers the logic circuitry of the DC input module. The maximum current drawn from this supply is 280mA.
Installing Your Module
In this section we tell you how to initially handle your module, key your I/O chassis, install your module and make your wiring connections.
Initial Handling Procedures ATTENTION: Remove power from the 1771 I/O chassis backplane and wiring arm before removing or installing an I/O module. Failure to remove power from the backplane or wiring arm could cause module damage, degradation of performance, or injury. Failure to remove power from the backplane could cause injury or equipment damage due to possible unexpected operation.
The input module contains components which can be damaged by electrostatic discharge. The module is shipped in an electrostatic shielded bag for protection. Follow the handling procedures outlined below to guard against damage to your module. Touch a grounded object to discharge yourself before handling the module. Do not touch the backplane connector or connector pins. If you configure or replace internal components, do not touch other circuit components inside the module. If available, use a static–safe work station. When not in use, keep the module in its static–free shield bag. 2
Page 3
Installation Data DC (10 - 30V) Input Module (Cat. No. 1771-IVN)
Keying the I/O Chassis Use the plastic keying bands, shipped with each I/O chassis, to key your I/O slots to accept only this type of module. Place the keying bands on the chassis backplane between: 14 and 16 30 and 32 Slots on the rear edge of the circuit board are matched to these slots to allow insertion of this type of module. You can key any connector in an I/O chassis to receive this module except for the leftmost connector reserved for adapter or processor modules.
Inserting the Module Into the Chassis 1.
Position the module so that the circuit board on the rear of the module lines up with the top and bottom card guides in the chassis.
2.
Slide the module into the chassis.
3.
Press firmly to seat the module in the chassis backplane connector.
4.
Swing the module locking latch down into place over the front edge of the module.
Connecting Wiring to the Module You make connections to the module through the field wiring arm cat. no. 1771–WN. The arm pivots on the I/O chassis to connect with terminals on the front of the module and acts as a terminal strip. The wiring arm allows the module to be removed from the chassis without disconnecting wiring. 1.
Make certain all power is removed from the module before making wiring connections.
2.
Swing the wiring arm up into position on the front of the module. The locking tab on the module will secure it into place.
3.
Make your connections to the field wiring arm as shown in Figure 1. (Use the label on the front of the wiring arm to identify your wiring.) ATTENTION: The field wiring arm terminal identification number is not the same as the number of the bit which controls that output.
3
Page 4
Installation Data DC (10 - 30V) Input Module (Cat. No. 1771-IVN)
I/O Module Groups Each module condenses 2 full module groups (32 inputs) into each I/O chassis slot. For example: Module group 1 = inputs 00 through 17 Module group 2 = inputs 00 through 17 (module group 2 represents the second set of inputs). In figure 1, terminals 1 through 20 represent module group 1, with terminals 1, 2, 11 and 12 10–30V DC power. Terminals 21 through 40 represent module group 2, with terminal 21, 22, 31 and 32 DC power. Figure 1 Connection Diagram for the 1771-IVN DC Input Module (See applicable codes and laws.)
–
+ 2-Wire Devices
–
-
DC Supply –
Input 01
4
Input 03
6
10-30V DC Input 11
+ 3-Wire Devices
2
Input 05 Input 07
DC Supply –
10-30V DC
-
8 10 12 14
Input 13
16
Input 15
18
Input 17
20
10-30V DC Input 01
22
Input 03 Input 05 Input 07
26
10-30V DC
32
Input 11
34
Input 13 Input 15
36
Input 17
40
24
28 30
38
10-30V DC Input 00 Input 02 Input 04 Input 06 10-30V DC Input 10 Input 12 Input 14 Input 16 10-30V DC Input 00 Input 02 Input 04 Input 06 10-30V DC Input 10 Input 12 Input 14 Input 16
Note: Terminals on the left are even numbered (2 thru 40) , and terminals on the right are odd numbered (1 thru 39).
(Actual wiring runs in this direction.)
4
10433-I
Page 5
Installation Data DC (10 - 30V) Input Module (Cat. No. 1771-IVN)
ATTENTION: Observe proper polarity with Ddc power connections. Reverse polarity, or application of ac voltage could damage the module. Table B Module Input Terminal Assignments Terminal Number
Input Assignment
I/O program address
Terminal Number
Input Assignment
I/O program address
01
1 10 to 30V DC
-
21
1 10 to 30V DC
-
02
10 to 30V DC
-
22
10 to 30V DC
-
03
Input 00
1RG00
23
Input 00
1RG00
04
Input 01
1RG01
24
Input 01
1RG01
05
Input 02
1RG02
25
Input 02
1RG02
06
Input 03
1RG03
26
Input 03
1RG03
07
Input 04
1RG04
27
Input 04
1RG04
08
Input 05
1RG05
28
Input 05
1RG05
09
Input 06
1RG06
29
Input 06
1RG06
10
Input 07
1RG07
30
Input 07
1RG07
11
1 10 to 30V DC
-
31
1 10 to 30V DC
-
12
10 to 30V DC
-
32
10 to 30V DC
-
13
Input 10
1RG10
33
Input 10
1RG10
14
Input 11
1RG11
34
Input 11
1RG11
15
Input 12
1RG12
35
Input 12
1RG12
16
Input 13
1RG13
36
Input 13
1RG13
17
Input 14
1RG14
37
Input 14
1RG14
18
Input 15
1RG15
38
Input 15
1RG15
19
Input 16
1RG16
39
Input 16
1RG16
20
Input 17
1RG17
40
Input 17
1RG17
Where:
R = rack number (1, 2, 3, etc.) G = I/O group (0 - 7)
1 You can connect a different power supply to each pair of 10-30V dc terminals (01/02, 11/12, 21/22, 31/32). Each pair of terminals is independent of the others. Terminals 01/02 supply terminals 03 thru 10; 11/12 for 13 thru 20; 21/22 for 23 thru 30; and 31/32 for 33 thru 40.
5
Page 6
Installation Data DC (10 - 30V) Input Module (Cat. No. 1771-IVN)
Interpreting the Status Indicators
The module has 32 status indicators on the module front plate. These represent the control status of the inputs. Each indicator is lit when voltage is present at the corresponding input. Figure 2 Status Indicators
00 10 01 11 02 12 03 13 04 14 05 15 06 16 07 17
00 10 01 11 02 12 03 13 04 14 05 15 06 16 07 17
Status Indicators (red)
10434-I
6
Page 7
Installation Data DC (10 - 30V) Input Module (Cat. No. 1771-IVN)
7
Page 8
Installation Data DC (10 - 30V) Input Module (Cat. No. 1771-IVN)
Specifications
Inputs per module
32
Module Location
1771-A1B thru -A4B I/O Chassis
Input Voltage Range (+dc)
10 to 30V dc
Nominal Input Current
4.5mA @ (+dc - 10V dc)
Minimum Off-state Current
1.7mA @ (+dc - 5V dc)
Maximum Off-state Voltage
(+dc - 5V dc)
Minimum On-state Voltage
(+dc - 10V dc)
Input Impedance
2.2K
Input Signal Delay
Low to high propagation: 6ms(+2ms) High to low propagation: 6ms(+2ms)
Power Dissipation
15.6W (max); 1.5W (min)
Thermal Dissipation
53.3 BTU/hr (max); 5.1 BTU/hr (min)
Backplane Current
280mA @ 5V dc maximum
Isolation Voltage
1500V ac RMS
Conductors Wire Size Category
14 gauge stranded (max)1 3/64 inch insulation (max) Category 12
Environmental Conditions Operational Temperature Storage Temperature Relative Humidity
0o to 60oC (32o to 140oF) -40o to 85oC (-40o to 185oF) 5 to 95% (without condensation)
Keying
Between 14 and 16 Between 30 and 32
Field Wiring Arm Wiring Arm Screw Torque
1771-WN 7-9 inch-pounds
1 14 gauge wire connected to all terminals may not allow the cover on the field wiring arm to close. 2A smaller gauge wire may be used.You use this conductor-category information for planning conductor routing as described in the system-level installation manual.
With offices in major cities worldwide WORLD HEADQUARTERS Allen-Bradley 1201 South Second Street Milwaukee, WI 53204 USA Tel: (1) 414 382-2000 Telex: 43 11 016 FAX: (1) 414 382-4444
EUROPE/MIDDLE EAST/AFRICA HEADQUARTERS Allen-Bradley Europe B.V. Amsterdamseweg 15 1422 AC Uithoorn The Netherlands Tel: (31) 2975/43500 Telex: (844) 18042 FAX: (31) 2975/60222
As a subsidiary of Rockwell International, one of the world’s largest technology companies, Allen-Bradley meets today’s challenges of industrial automation with over 85 years of practical plant-floor experience. More than 11,000 employees throughout the world design, manufacture and apply a wide range of control and automation products and supporting services to help our customers continuously improve quality, productivity and time to market. These products and services not only control individual machines but integrate the manufacturing process, while providing access to vital plant floor data that can be used to support decision-making throughout the enterprise. ASIA/PACIFIC HEADQUARTERS Allen-Bradley (Hong Kong) Limited Room 1006, Block B, Sea View Estate 28 Watson Road Hong Kong Tel: (852) 887-4788 Telex: (780) 64347 FAX: (852) 510-9436
8 Publication 1771–2.169 – June 1990 Supersedes publication 1771–2.115 – July 1987 and 1771–2.115–DU1 – November 1987
CANADA HEADQUARTERS Allen-Bradley Canada Limited 135 Dundas Street Cambridge, Ontario N1R 5X1 Canada Tel: (1) 519 623-1810 FAX: (1) 519 623-8930
LATIN AMERICA HEADQUARTERS Allen-Bradley 1201 South Second Street Milwaukee, WI 53204 USA Tel: (1) 414 382-2000 Telex: 43 11 016 FAX: (1) 414 382-2400
P/N 955106–91 Printed in USA