For the Allen-Bradley 1771-KA2
Page 131
Chapter 10 Design Aids and Documentation
Figure 10.4 PLC-2/30 Memory Organization Total Decimal Words
Octal Word Address
Decimal Words Per Area
000 8
8
Processor Work Area No. 1 Rack 1
010–017
Rack 2
020–027
Rack 3 Rack 4 Rack 5
030–037 040–047 050–057 060–067 070–077
64
56
Rack 6 Rack 7
72
8
Processor Work Area No. 2
128
56
007 010 1
77 100 107 110
Rack 1
110–117
Rack 2
120–127
Rack 3 Rack 4 Rack 5
130–137 140–147 150–157
Rack 6 Rack 7
160–167 170–177
256
128
Timer/Counter Preset Values or Internal Storage
384
128
Expansion 1
512
128
Expansion 2
128
Input Image Table Rack address areas that are not configured as input image table become available for timer/counter preset values or word/bit storage.
2
177 200
Timer/Counter ACC Values or Internal Storage
640
Output Image Table Rack address areas that are not configured as output image table become available for timer/counter accumulated values or word/bit storage.
277 300 377 400 Data table can be expanded in 128 word increments (unused sections are utilized for user program storage) up to 8064 words maximum.
577 600 777 1000
Expansion 3 (etc.)
1177 1200
User Program Storage (User Program Begins After End of Last Data Table Expansion)
1
027 –– Bits in this word are used by the processor for battery low condition, message generation and data highway.
2
125 and 126 –– These words are used to indicate remote rack fault status in a remote I/O system.
3
Report generation messages can be stored in memory locations not used by data table or user program.
End of Program
Up to 8192
Message Storage
3
17777
10-5
Page 132
Chapter 10 Design Aids and Documentation
Figure 10.5 Mini-PLC-2 Memory Organization Octal Address
Decimal Words Used in Each Area
Total Decimal Words Used
8
8
Word
17 16 15 14 13 12 11 10 07 06 05 04 03 02 01 00 000 Processor Work Area No. 1 007
00
010
00
017 020
17 00
026
17
0
16
8
Bit
0
0
0
1
1
1
0
1
0
0
16 Data Bit Word Output Image Table
1
1
0
0
0
17
Bit/Word Storage 24
64
8
40
Not Available for Word Storage Timer/Counter Accumulated Values (AC) (or Bit/Word Storage)
027 030
00
077
17
100
00
107
17
110
00
120
00
127
17
130
00
177
17
200
00
Processor Work Area No. 2 72
80
8
8
Input Image Table
Bit/Word Storage 88
128
8
40
Timer/Counter Preset Values (PR) (or Bit/Word Storage)
User Program 512
1024
10-6
384
512
End of Memory Optional Second Memory Area (512 Words)
DATA TABLE
Page 133
Chapter 10 Design Aids and Documentation
Figure 10.6 Mini-PLC-2/05 Memory Organization
Total Decimal Words
Bit Address
Word Address
Decimal Words Per Area
000
00
007 010
17 00
017 020
17 00
026 027 030
17
077 100
17 00
Processor Work Area No. 1 8
8
Output Image Table 8
16
Bit/Word Storage 8
24
Reserved
64
40
72
8
1
2
Timer/Counter Accumulated Values (AC) (or Bit/Word Storage)
3
00
Processor Work Area No. 2 107 110
17 00
117 120
17 00
Factory– Configured Data Table 6
Maximum Size of Data Table
Input Image Table 80
8
88
8
Bit/Word Storage
4 5
40
128
127 130
17 00
177 200
17 00
Timer/Counter Preset Values (PR) (or Bit/Word Storage)
Expanded Data Table and/or User Program 2944
2816
3072
128 1 2 3 4 5 6
5577 17 User Program End of Memory
May not be used for accumulated values. Not available for bit/word storage. Bits in this word are used by the processor. Unused timer/counter memory words can reduce data table size and increase user program area. May not be used for preset values. Do not use word 127 for block transfer data storage. Can be decreased to 48 words.
10-7
Page 134
Chapter 10 Design Aids and Documentation
Figure 10.7 Sample Form (publication 5030) for Switch Settings on Communication Adapter Module (cat. no. 1771-KA2)
DATE: BY:
ALLEN–BRADLEY DATA HIGHWAY SWITCH SETTINGS COMMUNICATIONS ADAPTER MODULE CAT. NO. 1771–KA (Publication 5030 –– October, 1980) STATION NO. INSTRUCTIONS: USE A PENCIL TO DARKEN SWITCHES TO SHOW PROPER SETTINGS, AS SHOWN. KEEP THIS FORM WHERE IT CAN BE EASILY REFERENCED.
NO. 5 –– SEND UNPROTECTED COMMANDS w ON –– ENABLED w OFF –– DISABLED
NO. 2 –– RECEIVE UNPROTECTED COMMANDS w ON –– ENABLED w OFF –– DISABLED
ON EXAMPLE:
STATION NO.
NO. 1 –– RECEIVE PROTECTED COMMANDS w ON –– ENABLED w OFF –– DISABLED O 1 N
2
3
4
5
6
O F F
NO. 3 –– UNUSED, MAY BE ON OR OFF
FIRST DIGIT
SECOND DIGIT
O 1 N
O 1 N
2
2
THIRD DIGIT 3
O F F
O F F
O 1 N
2
3
O F F
O 1 N
2
O F F
ON
2 1
4 2 1
4 2 1
OFF
0 0
0 0 0
0 0 0 BOTH ON FOR 57.6 BAUD RATE SWITCH LOCATIONS
NO. 4 –– RECEIVE PRIVILEGED WRITE w ON –– ENABLED w OFF –– DISABLED NO. 6 –– PROCESSOR LINK BAUD RATE w ON –– PLC-2/20 PROCESSOR OR MINI-PROCESSOR MODULE w OFF –– PLC-2 PROCESSOR
COVER PLATE SWITCH LOCATION
10-8
OFF
Page 135
Chapter 10 Design Aids and Documentation
Figure 10.8 Sample Form (publication 5032) for Command Listing--From Station
DATE: BY:
ALLEN–BRADLEY DATA HIGHWAY COMMAND LISTING – FROM STATION (Publication 5032 – October, 1980)
STATION NO.
EXAMPLE:
COMMANDS AT THIS STATION
COMMAND TYPE
PRIORITY/ NORMAL
REMOTE STATION NO. ADDRESSED
04010
WRITE
N
022
COMMAND TYPE
PRIORITY/ NORMAL
REMOTE STATION NO. ADDRESSED
AREAS CONTROLLED
START BITS
DONE BIT
ENTER WORD ADDRESSES
(ENTER INFORMATION AS SHOWN)
START BIT STATUS WORDS
AREAS CONTROLLED
START BITS
1
AT LOCAL STATION
AT REMOTE STATION
060 – 062
051 – 053
AT LOCAL STATION
COMMENTS PARTS COUNT
AT REMOTE STATION
COMMENTS
17 16 15 14 13 12 11 10 07 06 05 04 03 02 01 00 START/DONE
(DARKEN USED BITS FOR QUICK REFERENCE.)
ADJACENT STATUS WORDS
REMOTE/LOCAL FAULT REMOTE FAULT BITS 1
LOCAL FAULT BITS
NOTE: WHEN A START BIT IS SELECTED, A DONE BIT, A REMOTE FAULT BIT, AND A LOCAL FAULT BIT ARE AUTOMATICALLY ASSIGNED. REFER TO USER’S MANUAL, COMMUNICATION ADAPTER MODULE.
10-9
Page 136
Chapter 10 Design Aids and Documentation
Figure 10.9 Sample Form (publication 5033) for Command Listing--To Station
DATE: BY: ALLEN–BRADLEY DATA HIGHWAY COMMAND LISTING – TO STATION (Publication 5033 – October, 1980) STATION NO. DIRECTIONS: USE THIS FORM TO DOCUMENT COMMANDS RECEIVED AT THIS STATION FROM OTHER STATIONS. EXAMPLE:
10-10
REMOTE STATION SENDING COMMAND STATION NO.
COMMAND TYPE
DATA WRITTEN TO ADDRESS(ES)
COMMENTS
010
WRITE
023–025
TEMP. VALUES
REMOTE STATION SENDING COMMAND STATION NO.
COMMAND TYPE
DATA WRITTEN TO ADDRESS(ES)
COMMENTS
Page 137
Chapter 10 Design Aids and Documentation
We have tried to present information on the KA2 module in a way that will be most helpful to you. Obviously we don’t try to make errors and omissions, but they crop up. If you feel there’s a way we could be of greater assistance, please contact us at Allen-Bradley Industrial Computer Group, Publication Department, 747 Alpha Drive, Highland Heights, Ohio 44143. Many thanks.
10-11
Page 138
Chapter 10 Design Aids and Documentation
10-12
Page 139
Appendix
A
Error Code Listing
Code 00 01, 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 26 27 28 29
STS Byte of Reply Message (in Hex) 00
Meaning No Error Processor communications problem. May be processor fault. No memory in communication adapter module for START bit file MEMORY ACCESS RUNG FORMAT First GET instruction incorrectly entered Invalid station number Second GET instruction incorrectly entered Third GET instruction incorrectly entered Third GET address less than second GET address (improper access boundary definition) Invalid end of access branch (BRANCH END instruction must be inserted. Invalid end of access rung Beginning of next rung invalid. (Refers to any rung after a memory access rung.) Or, BRANCH START instruction missing. COMMAND RUNG FORMAT START bit in lower byte. (START bit must be selected from upper byte, bits 10-17) Second EXAMINE element incorrectly entered Invalid command code Invalid remote station number in command code Invalid element in bit write rung First GET incorrectly entered (word command format) Second GET incorrectly entered (word command format) Third GET incorrectly entered (word command format) End of rung incorrectly entered (word command format) Beginning of new command rung invalid or memory access rung programmed following command rung. REMOTE/LOCAL FAULT word not in data table. (START/DONE word incorrectly chosen.) Unprotected command not allowed by switch setting at local station. Same start bit used in more than one command rung. Excessive number of command rungs (more than 256). Timeout setting too large. Valid timeout settings are 011 to 407. A setting of 010 disables the timeout. Bad address in command rung. Bad size in read/write command.
A-1
Page 140
Appendix A Error Code Listing
Code
STS Byte of Reply Message (in Hex)
Meaning COMMUNICATIONS ERRORS (MAY BE DISPLAYED IN CONJUNCTION WITH REMOTE/LOCAL FAULT BITS)
30 31 32 33 34 35 36
Processor memory discrepancy Controller communications problem. May be processor fault. Improper command message size Invalid command code Invalid station number Attempt to send unprotected command invalid Command execution aborted by sending station processor
37 38 50 51 52 53 54 55
Command execution aborted. Execution time exceeds timeout preset value. Local processor entered the program mode Processor communications problem. May be processor fault. Invalid transparent word in reply message No communication zone rungs in program Reply not expected. (Reply received, but START bit is OFF) Processor memory not in format for communication Invalid reply. (Reply received, but communication zone rungs are incorrectly entered. Or, reply received when processor mode select keylock switch is in the PROGRAM LOAD POSITION.) Program status indicator (PROG) may be ON to indicate this type of error condition. May mean memory access rung missing for received protected command
56 57 81 82 83 84 85
A-2
10 30 40 50
86 87 88
60 70 80
89
90
8B
B0
92 93
02 03
Incorrect sequence number in reply. (Refers to transparent word in message format.) Reply message is of incorrect size Illegal command Station processor communication problem Remote station processor faulted or OFF I/O fault at remote station processor Transmitted command disallowed by switch setting or memory access rung programming at remote station Transmitted command disallowed by switch setting at remote station Remote station processor in PROG or PROGRAM LOAD mode Communication zone invalid at remote station processor. Program status indicator (PROG) may be ON at that station. Remote station communication adapter module unable to buffer received command in memory Remote station is in download mode; or error in download command; or operation not allowed in upload or download mode; or operation not allowed when not in download mode. Destination station fails to respond Contention between master stations prevents message transmission